background image

14

Model MSCF Modular Small Cabinet Fan

®

Installation of Electric Heater 

(optional)

WARNING

Electrical Shock Hazard! Disconnect all power 
sources before doing any work on the unit.

Effect of Low Voltage on Wattage and 

British Thermal Unit (BTU)

The heating elements may be used on voltages 
lower than the design voltage of the heater, however, 
the wattage and BTU output will be reduced to the 
percentages listed in the table below.

1

 

For 7-24 conductors in raceway or cable, reduce allowable 

heater line currents to 87½% of those shown above.

2

 

Based on 30°C. (86°F) ambient temperature, for higher 

ambient temperature see National Electric Code table 

310-16 and 310-18 Note 13.

3

 

Based on 80% of ratings in the National Electric Code 

table 310-16 for 75°C insulation.

De-rated Wattage for Low Voltage

Heater

Voltage

Line

Voltage

% of 

Heater

Wattage 

and BTU

Heater

Voltage

Line

Voltage

% of 

Heater

Wattage 

and BTU

480

460

92

208

200

92

440

84

190

83

277

265

92

120

115

92

254

84

110

84

240

230

92

220

84

208

75

200

69

Supply Wire Size

(Not more than six conductors in Single Conduit 

1

)

AWG or 

MCM

Max. Heater 

Line Current 

2

AWG or 

MCM

Max. Heater 

Line Current 

2

Copper 

3

Copper 

3

14

12

0000

184

12

16

250

204

10

24

300

228

8

36

350

248

6

52

400

268

4

68

500

304

3

80

600

336

2

92

700

368

1

104

750

380

0

120

800

392

00

140

900

416

000

160

1000

436

General:

The requirements and practices described below 
are based on the National Electric Code (NEC) and 
The Space Heating Standard of the Underwriters 
Laboratories Inc. (UL). Although UL requirements 
are uniform throughout the country, local electrical 
codes may deviate from the National Electrical Code. 
Therefore, local inspection authorities should be 
consulted regarding local requirements.

Electrical Wiring Instructions:

1.   Use the wiring diagram supplied with the heater 

as a guide in correlating field wiring with the 
heater internal wiring.

2.  All field wiring to the heater must meet the 

requirements of the National Electric Code and 
any other applicable local or state codes.

3.  Wiring to the heater must be rated for 75°C 

(167°F) minimum.

4.  If heater does not have a built-in disconnect 

switch or main circuit breaker, install a remote 
disconnect (furnished by others) in accordance 
with the National Electric Code, Article 424-65.

Calculation of Line Currents (amps):

Single Phase Current =  watts

volts

EXAMPLE:   5 kW, 208 volt

5000 watts = 24 amps

208 volts

Three Phase Current =

watts

volts x 1.73

EXAMPLE:   14.4 kW, 208 volt

14400 watts = 14400 = 40 amps

208 volts x 1.73

360

Sizing of Supply Conductors

The required minimum size of supply conductors 
is marked at the field wiring terminals within the 
heater control box or reference the Supply Wire Size 
table included in this section. The wire gauges are 
calculated for 125% of the heater line current as 
required by the National Electric Code, Article 424-3(b) 
based on conductor insulation rated for 75°C (167°F).

Summary of Contents for MSCF-BI

Page 1: ...ation and Maintenance Manual Please read and save these instructions Read carefully before attempting to assemble install operate or maintain the product described Protect yourself and others by obser...

Page 2: ...are accounted for by referencing the bill of lading to ensure all items were received Inspect each crate for shipping damage before accepting delivery Notify the carrier if any damage is noticed The c...

Page 3: ...Electric Heater 15 Maintenance Fan 16 Coil 16 Drain Pan 16 Reference Start Up Documentation 17 Maintenance Log 18 19 Warranty Backcover Unit Layout 1 Fan and Cabinet Section 2 Cooling Section Chilled...

Page 4: ...3 0 inch 3 8 16 Spinlock Nut Two required per assembly 3 8 16 Spinlock Nut Two required per assembly HANGING ASSEMBLY BASE ASSEMBLY Mounting Instructions Greenheck s Modular Small Cabinet Fan MSCF sho...

Page 5: ...4 Row HW Steam 15 6 75 18 5 18 5 6 75 6 75 18 5 6 75 9 5 18 5 19 38 2 5 3 5 43 20 6 75 18 5 18 5 6 75 6 75 18 5 6 75 9 5 18 5 19 38 2 5 3 5 43 25 6 75 21 18 5 6 75 6 75 21 6 75 9 5 18 5 23 38 2 5 3 5...

Page 6: ...ertical Quantity Face Area Sloped Quantity Face Area 15 9x18 2 1 8 12x12 1 2 5 12x24 1 20 12x12 1 2 5 16x16 1 3 4 12x24 1 16x20 1 25 14x18 2 3 0 16x20 2 3 8 30 16x16 1 3 4 12x24 1 5 3 16x20 1 24x24 1...

Page 7: ...15 50 9 38 3 188 1 375 4 0 26 0 85 8 6 62 12 75 9 38 3 188 1 375 4 0 26 0 All dimensions are in inches NOTE With airflow from left to right the fluid enters the coil from the bottom connection Inlet...

Page 8: ...2 50 24 5 21 0 10 12 14 1 38 1 63 65 6 7 50 24 5 26 0 10 12 14 1 38 1 63 85 8 6 62 24 5 26 0 10 12 14 1 38 1 63 All dimensions are in inches Unit Size Face Area A B C L M N P 4 Row 6 Row 8 Row All Al...

Page 9: ...should be capped off cap Unit Size Face Area A B C D E F G 4 Row 6 8 Row 4 Row 6 Row 8 Row 30 3 2 38 24 5 18 5 9 25 11 0 7 88 8 50 8 5 7 00 12 0 45 4 5 50 24 5 18 5 9 25 11 0 7 88 8 50 8 5 7 00 12 5 5...

Page 10: ...rage and Fan RPM All access doors must be installed Measure and record the input voltage and motor amperage s To measure the fan RPM the blower door will need to be removed Minimize measurement time b...

Page 11: ...ductwork Repair Elbows or other obstructions may restrict fan outlet Correct or improve ductwork Belt slippage Adjust belt tension Unit running backwards Correct as shown in System Start Up section S...

Page 12: ...independently of the coils Undue stress should not be applied at the connection to coil headers 2 The condensate drain pipe should be sized adequately to ensure the condensate drains properly See Drai...

Page 13: ...are recommended for low pressure steam On high pressure systems bucket traps are normally recommended The thermostatic traps should be used only for air venting 3 Bucket traps are recommended for use...

Page 14: ...he requirements and practices described below are based on the National Electric Code NEC and The Space Heating Standard of the Underwriters Laboratories Inc UL Although UL requirements are uniform th...

Page 15: ...with the thermostat set to 70 F the heater will be off with a temperature sensing above 70 F As the temperature varies the steps turn on and off to hold the setpoint discharge temperature The colder...

Page 16: ...n air Occasionally oil and dust may accumulate on the wheel causing imbalance When this occurs the wheel and housing should be cleaned to assure smooth and safe operation Inspect fan impeller and hous...

Page 17: ...rated enough to prevent freeze up NOTE Carefully read instructions for mixing antifreeze solution used Some products will have a higher freezing point in their natural state than when mixed with water...

Page 18: ...___________________________ _________________________________________________ _________________________________________________ Date___________________ Time______________ AM PM Notes _________________...

Page 19: ...___________________________ _________________________________________________ _________________________________________________ Date___________________ Time______________ AM PM Notes _________________...

Page 20: ...or installation costs As a result of our commitment to continuous improvement Greenheck reserves the right to change specifications without notice Phone 715 359 6171 Fax 715 355 2399 E mail gfcinfo g...

Reviews: