GreenJet – Centrifugal Jet Fan

7

®

General maintenance for the GJI model:
•  Motor bearings are sealed and do not need 

lubrication.

•  Inspection and cleaning should be limited to remove 

any dirt accumulation on the fan wheel, fan inlet and 
fan discharge.

If the fan environment possesses a consistent humidity 
of 80% or more, the fan must be run for 2 hours on 
high, once a month to remove condensation.

Paint Touch-Up for Scratched Areas

For field paint repairs, refer to replacement part 
HAZ2920 Concrete Gray, Touch Up Paint,  
Spray Can RAL 7023.

Controller Setup

MB Holding Register 4, Address: h3

COM Parameter

Communication parameters for serial MODBUS communication. Settings made in this register will be made active 
after a device reset or by entering a PIN code, press h0.
Access / necessary PIN protection level

RW, NV / 1

Minimal value

0

Maximum value

65535

Bit [15:8]

Bus Address: 1 - 247, Default 247

Bit [7:4]

COM Baudrate: 19200Bd (default) 
 
0 = 4800 
1 = 9600 
2 = 19200 (fix @: ECblue lite IP54, ECblue motor size B IP54) 
3 = 38400 (only AM-MODBUS) 
4 = 115200 (only AM-MODBUS from Firmware 04)

Bit [3:0]

COM Mode 8E1 (default) 
 
0 = 8N1 
1 = 8O1 
2 = 8E1 (fix @: ECblue lite IP54, ECblue motor size B IP54) 
3 = 8N2 (from AM-MODBUS version 9.00)

MB Holding Register 3, Address: h2

Speed control

Used for speed control of the device. The interpretation of the value depends on control mode register (h4)  
Bit [3:0].
Access / necessary PIN protection level

RW / 0

Minimal value

0

Maximum value

65535

Default

0

Bit [15:0]

Decimal value 0 - 65535

Maintenance

Summary of Contents for GreenJet GJI

Page 1: ...el should have a clear understanding of these instructions and should be aware of general safety precautions Improper installation can result in electric shock possible injury due to coming in contact...

Page 2: ...utions need to be taken to prevent deterioration of the unit during storage The user assumes responsibility of the unit and accessories while in storage The manufacturer will not be responsible for da...

Page 3: ...on safety practices involving industrial and commercial fans please refer to AMCA Publication 410 Electrical Disconnects Fan is provided with an integrated service disconnect Service disconnects shall...

Page 4: ...using vibration isolators Anchor Ceiling Fan Rail Washer 3 8 inch MAX rod nut and washer mounting hardware by others 20 00 27 56 Mounting Holes Qty 4 Figure 1 Top view of GJI mounting hole locations...

Page 5: ...requires either a 0 10VDC or MODBUS signal to control the fan speed Particular attention should be given when connecting power to the unit Supply wiring must be properly fused and conform to local an...

Page 6: ...6 General example for MODBUS device connection Recommended Wire Types 1 CAT5 CAT7 cables 2 J Y St 2x2x0 6 telephone wire 3 AWG22 2x2 twisted pair When using telephone flex with four cable cores it is...

Page 7: ...US communication Settings made in this register will be made active after a device reset or by entering a PIN code press h0 Access necessary PIN protection level RW NV 1 Minimal value 0 Maximum value...

Page 8: ...describing the equipment fan performance available accessories and specification data Problem Cause Corrective Action Excessive noise Wheel unbalance Clean all dirt off wheel Check wheel balance repl...

Reviews: