34
Troubleshooting
Check inlet gas pressure.
(Direct Gas Start-Up Step #1)
Is the low fire set properly
(Direct Gas Start-Up Step #6)
Gas pressure between the min
and max shown on the direct gas
label?
Correct gas pressure
(Reference Direct Gas Start-Up Step #1)
Proper spark?
Crossed flame and spark wires
(Uncross wires and reconnect)
Incorrect spark plug gap
(Set spark plug gap to 0.062 in.)
Defective spark plug
(Replace spark plug)
Pressure drop across the burner
between 0.60 and 0.675 in. wc?
Adjust burner baffles
(Reference Direct Gas Start-Up Step #3)
Check burner pressure drop
(Direct Gas Start-Up Step #3)
Air in the gas line?
Purge gas line
No
Yes
No
No
Yes
Yes
No
Heater Does Not Operate
Attempts to light but no flame (Visible spark)
Yes
With proper airflow, gas pressure and spark,
the unit should light.
If problems remain, consult the factory
Adjust the low fire setting
(Reference Direct Gas Start-Up Step #6)
No
Yes
Troubleshooting