28
Step 8 Enter Program Mode
Press and hold the Enter Key for three seconds.
The display will read “Pro” when Program Mode is
active (see figure #56).
Step 9 Adjust the Freeze Temperature
While in Program Mode, use the Up and Down
Keys to navigate through the Menu Options until
“Frt” is displayed (see figure #57). Press the Enter
Key to access the selected Menu Option setting.
Use the Up and Down Keys to adjust the Freeze
Temperature setting as needed. Press the Enter
Key to set the Freeze Temperature and return to
the Program Menu.
Step 10 Exit Program Mode
After ten seconds of idle time the controller will exit
Program Mode.
Step 7 Exit Program Mode
After ten seconds of idle time the controller will exit Program Mode.
NOTE!
The Freeze Temperature is the temperature at which the supply solenoid closes and the drain
solenoid opens to drain the supply line, preventing possible freeze damage. A drain solenoid is
required for this option.
NOTE!
The Freeze Temperature is preset to the factory recommended 41ºF. Steps 8-10 should only be
completed if the Freeze Temperature needs adjustment.
Step 6 Adjust the Minimum Cooling
Temperature
While in the Program Menu, use the Up and Down
Keys to navigate the Menu Options until “toF” is
displayed (see figure #55). Press the Enter Key to
access the selected Menu Option setting.
Use the Up and Down Keys to adjust the Minimum
Cooling Temperature as needed. Press the Enter
Key to save the Minimum Cooling Temperature
setting and return to the Program Menu.
IMPORTANT!
The Enter Key must be pressed to save
the new Freeze Temperature .
IMPORTANT!
The Enter Key must be pressed to save
the new Minimum Cooling Temperature.
Start-Up - Water Wizard™
Figure 55.
Minimum Cooling Temperature Display
Figure 56.
Program Display
Figure 57.
Freeze Temperature Display