30
Operation - Electrical
1. Exhaust Fan Switch (S1) Closed
• Power passes to exhaust starter(s) ST2(3)
• N.O. exhaust starter switches are energized
and closed
• Power passes to exhaust fans
• Exhaust fans start
2. Supply Fan Switch (S2) Closed
• N.O. contact(s) ST2(3) are closed
• Power passes to optional freeze protection
relay (FZ1) and if temperature is acceptable
N.C. contact (FZ1) remains closed
• Power passes to damper which opens
• When damper is fully opened, damper relay
(D1) is energized and N.O. damper limit switch
(DL1) closes.
• Power passes to and energizes supply starter
relay (ST1)
• Supply starter contact (ST1) closes and power
reaches and energizes supply fan
• Supply fan starts
4. Evaporative Cooling Switch (S4)
Closed*
• N.O. contact ST1(AUX) is energized and closed
• Power passes to and energizes cool relay (R1)
• N.O. contact R1 is energized and closed
• Power passes to evaporative cooling pump (P1)
*If DX or chilled water coils are used rather than
an evaporative cooler, the cooling sequence of
operation will depend on the coil controls.
Cooling coil controls are supplied by others.
3. Heat Switch (S3) Closed
• Power passes to N.O. ST1 which is energized
and closed
• Power passes to inlet air sensor contact (TS1)
which is energized and closed if proper inlet air
temperature is present
• Power passes to and energizes heat relay (R2)
• N.O. heat relay contact (R2) closes
• Power passes to N.C. high limit control contact
(HLC1) which is closed if temperature has
remained below set point
• Power passes to N.O. and N.C. gas pressure
contacts (PS1) which are both closed if gas
pressure is within the set range
• Power passes to N.O. and N.C. airflow switch
(PS2) which are closed if there is proper airflow
across the burner
• Power passes to terminal L1 on the FSG which
begins it’s sequence (see direct gas sequence)
1. Supply Fan Switch Closed
• Power passes to the supply fan and heat switch
2. Heat Switch Closed
• Power passes to the heat relay then to the
Flame Safe Guard
3. Flame Safe Guard (FSG) Sequence
• Checks for proper airflow
• Verifies no flame present at burner
• Initiates 15 second prepurge
• Sends power to open gas valve (V2) and
energizes the spark generator (clicking of the
spark generator may be heard).
• Tries for up to 10 seconds to light and confirm
flame.
• Shuts down spark generator
• Continuously monitors the flame and airflow
Electrical Sequence
Direct Gas Burner Sequence
Operation