4.3 ANALOG OUTPUT SIGNALS

Airflow:

  Available on connector J1, terminals AO1+ and AO1- or AO2+ and AO2-. The full scale output is equal to 

Max flow as inputted into the Vari-Green transmitter on the Flow Configuration submenu.

Temperature:

 Available on connector J1, terminals AO1+ and AO1- or AO2+ and AO2-. The temperature analog 

output has a fixed scale of -20º F to 140º F.

SECTION 5.0: Maintenance / Inspections / 
Troubleshooting

5.1 MAINTENANCE / INSPECTIONS

The Vari-Green

 system h

as been designed to operate in most HVAC applications without the need 

for periodic maintenance or calibration. In some applications, it may be necessary to perform a visual 
inspection of the probe and sensors, and if necessary clean them using a soft, small brush and/or 
compressed air to remove any accumulated particulate or debris. 

5.2 TROUBLESHOOTING

The Vari-Green

 system is i

ntended to provide long-term, trouble-free operation. In the event there is an 

issue with the Vari-Green measurement system, or the BMS or the controller ceases to receive valid 
airflow and/or temperature signals, make certain the following have been checked and confirmed:
•  The power wiring is securely connected to the proper terminals and is providing the intended 24V AC/

DC power.

• The signal wiring is securely connected to the proper terminals.
•  The probe-to-probe and probe-to-transmitter cables and connections are properly connected and 

secure.

• Power cycles the transmitter.
If after following the above troubleshooting steps, the Vari-Green system continues to operate improperly, 
contact Greenheck for technical assistance.

Technical Support:

E-mail: [email protected] or

Phone: 1-800-717-6540

482599 • Vari-Green® Transmitter IOM, Rev. 3, October 2018 

Copyright 2018 © Greenheck Fan Corporation

10

As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications 
without notice.

Product warranties can be found online at Greenheck.com, either on the specific product page or in the literature 
section of the website at Greenheck.com/Resources/Library/Literature.

®

Phone: 715.359.6171 • Fax: 715.355.2399 • Parts: 800.355.5354 • E-mail: [email protected] • Website: www.greenheck.com

Our Commitment

Summary of Contents for AMD-TD Series

Page 1: ...y for the customer s failure to comply with these requirements If this product is used in a manner not specified in this manual the protection providied by this product may be impaired Regarding This Manual This manual should be passed on to the end user Before use read this manual thoroughly to comprehend its contents The contents of this manual may be changed without prior notice All rights rese...

Page 2: ...s also measured via these sensors The Vari Green transmitter can receive up to 32 individual flow sensors measuring airflow in a single duct and it generates the outputs including network and analog signals which are conveyed to a local controller or BMS Physical installation details for the probe array or flow stations can be found in Greenheck s Installation Instructions Typical Vari Green Insta...

Page 3: ...r APPROVALS UL 60730 PENDING BTL FCC Part 15 Subpart B Class A Device 2 1 PROBE ASSEMBLY INDIVIDUAL SENSOR ACCURACY Velocity 2 of reading from 0 5000 FPM Temperature 0 1 F Multi point NIST traceable calibration of both temperature and velocity SENSOR TYPE Her metically sealed precision matched thermistors with laser trimmed resistive heating element mounted in flow conditioning aperture Max number...

Page 4: ... 4 POWER and SIGNAL CONNECTIONS NOTE The Vari Green transmitter terminal connections for power and signal wire are labeled on the board for installation convenience Power wiring is located at terminal strip J4 Signal wiring is located at terminal strip J1 The REMOVABLE terminal strips for power and signal are located in the lower portion of the transmitter and are accessible by opening the hinged ...

Page 5: ... FPM set point drives display and output to zero Alarm Alert Configuration Configure alarm type upper and lower limits Network Configuration Configure network type baud rate and address information Field Characterization For information on field characterization please see section below SERVICE MENU SELECTION DESCRIPTION Password Configuration Enable disable and change password Total System Scan D...

Page 6: ... ID can be entered through the Service Menu It is typically used to describe the transmitter location in the building Brightness Allows the user to set the brightness of the display in real time Inactivity Timeout The time period which holds the display in menu mode When the timer expires the display is returned to the main display screen showing the process values Analog Output Configuration The ...

Page 7: ...nable Reg Alerts will turn ON OFF Enable Global Alerts will turn ON OFF Field Characterization Field characterization K factoring of a flow element is the adjustment of the flow measurement system to match a known reference measurement most commonly airflow traverse testing Field characterization is typically done when there is insufficient straight duct run or another issue that creates questiona...

Page 8: ... See below for sensor control If Missing yellow is at a value other than zero the transmitter is not communicating with the associated node Sensor Control An enabled sensor will report measurement data to the Vari Green transmitter This is the default condition after initially powering the system A disabled sensor will not report measurement data to the Vari Green transmitter Disabled sensors may ...

Page 9: ...xternal 24 VAC 24 VDC power source 1 Press the power button located on the bottom left corner of the front cover to turn the system ON 2 The display will show a loading bar After reaching 100 the display will indicate which sensors have been discovered for approximately 2 seconds Then the normal operating screen will be displayed The default normal operating screen will display Total Flow on the f...

Page 10: ... controller ceases to receive valid airflow and or temperature signals make certain the following have been checked and confirmed The power wiring is securely connected to the proper terminals and is providing the intended 24V AC DC power The signal wiring is securely connected to the proper terminals The probe to probe and probe to transmitter cables and connections are properly connected and sec...

Reviews: