Sensor Alert Scan

Displays alert codes for expected sensors. Sensors operating properly will 
display NoAlert.

Other Alert Codes

Alert Code

Type

Description

Corrective Action

Missing

ALERT

Transmitter cannot communicate with Sensor

Power cycle system and recheck.

SensAOOR
or
SensBOOR

ALERT

Sensor fault

Replace sensor. Contact Greenheck.

DeltaOOR

ALERT

Sensor Delta Temperature out of range

Contact Greenheck.

TempOOR

RANGE

Temperature measurement out of range 
(-20 to 140°F)

Verify application temperature is not outside -20 
to 140°F. If Vari-Green appears to be reporting 
incorrectly, contact Greenheck.

Disabled

ALERT

Sensor resets abnormally

Power cycle system and recheck.

VelOOR

RANGE

Average velocity exceeds 5000 FPM for ducted 
and 10,000 FPM for Fan Inlet

Verify factory set-up information is correct. If 
application velocity exceeds 5000 FPM, contact 
Greenheck.

4.2 START-UP / OPERATION

After power and signal wiring has been verified in accordance with section 
3.4, activate the external 24 VAC / 24 VDC power source.
1.  Press the power button located on the bottom left corner of the front 

cover to turn the system ON.

2.  The display will show a loading bar. After reaching 100%, the display 

will indicate which sensors have been discovered for approximately 2 
seconds. Then the normal operating screen will be displayed. 

The default normal operating screen will display Total Flow on the first 
process line, Velocity (average of all enabled sensors) on the second 
process line and Temperature (average of all enabled sensors) on the third 
process line. Application tagging information is at the bottom of the screen 
and is customer configurable.

Sensor Alert Scan

 

ESC - Leave UP/DN - Scroll

 

Sensor 1:  Disabled

SENSOR

ALERT CODE

FREQ

1

Disabled

41

2

NoAlLert

 

Total Flow

520  ACFM

 

417.1   AFPM

 

Velocity

 72.71   F

 

Temperature

Send/Receive arrows flashing indicates the sensor(s) and transmitter are communicating 
normally

Transmitter processor normal

Field Characterization has been turned on

The following icons will always be displayed at the top of the normal operating screen. Press 

ENT

 to enter 

menu screens. Follow instructions in section 4.1 to navigate.

Vari-Green® Transmitter

9

®

Summary of Contents for AMD-TD Series

Page 1: ...y for the customer s failure to comply with these requirements If this product is used in a manner not specified in this manual the protection providied by this product may be impaired Regarding This Manual This manual should be passed on to the end user Before use read this manual thoroughly to comprehend its contents The contents of this manual may be changed without prior notice All rights rese...

Page 2: ...s also measured via these sensors The Vari Green transmitter can receive up to 32 individual flow sensors measuring airflow in a single duct and it generates the outputs including network and analog signals which are conveyed to a local controller or BMS Physical installation details for the probe array or flow stations can be found in Greenheck s Installation Instructions Typical Vari Green Insta...

Page 3: ...r APPROVALS UL 60730 PENDING BTL FCC Part 15 Subpart B Class A Device 2 1 PROBE ASSEMBLY INDIVIDUAL SENSOR ACCURACY Velocity 2 of reading from 0 5000 FPM Temperature 0 1 F Multi point NIST traceable calibration of both temperature and velocity SENSOR TYPE Her metically sealed precision matched thermistors with laser trimmed resistive heating element mounted in flow conditioning aperture Max number...

Page 4: ... 4 POWER and SIGNAL CONNECTIONS NOTE The Vari Green transmitter terminal connections for power and signal wire are labeled on the board for installation convenience Power wiring is located at terminal strip J4 Signal wiring is located at terminal strip J1 The REMOVABLE terminal strips for power and signal are located in the lower portion of the transmitter and are accessible by opening the hinged ...

Page 5: ... FPM set point drives display and output to zero Alarm Alert Configuration Configure alarm type upper and lower limits Network Configuration Configure network type baud rate and address information Field Characterization For information on field characterization please see section below SERVICE MENU SELECTION DESCRIPTION Password Configuration Enable disable and change password Total System Scan D...

Page 6: ... ID can be entered through the Service Menu It is typically used to describe the transmitter location in the building Brightness Allows the user to set the brightness of the display in real time Inactivity Timeout The time period which holds the display in menu mode When the timer expires the display is returned to the main display screen showing the process values Analog Output Configuration The ...

Page 7: ...nable Reg Alerts will turn ON OFF Enable Global Alerts will turn ON OFF Field Characterization Field characterization K factoring of a flow element is the adjustment of the flow measurement system to match a known reference measurement most commonly airflow traverse testing Field characterization is typically done when there is insufficient straight duct run or another issue that creates questiona...

Page 8: ... See below for sensor control If Missing yellow is at a value other than zero the transmitter is not communicating with the associated node Sensor Control An enabled sensor will report measurement data to the Vari Green transmitter This is the default condition after initially powering the system A disabled sensor will not report measurement data to the Vari Green transmitter Disabled sensors may ...

Page 9: ...xternal 24 VAC 24 VDC power source 1 Press the power button located on the bottom left corner of the front cover to turn the system ON 2 The display will show a loading bar After reaching 100 the display will indicate which sensors have been discovered for approximately 2 seconds Then the normal operating screen will be displayed The default normal operating screen will display Total Flow on the f...

Page 10: ... controller ceases to receive valid airflow and or temperature signals make certain the following have been checked and confirmed The power wiring is securely connected to the proper terminals and is providing the intended 24V AC DC power The signal wiring is securely connected to the proper terminals The probe to probe and probe to transmitter cables and connections are properly connected and sec...

Reviews: