Receiving and Handling

Upon receiving dampers, check for both obvious 
and hidden damage. If damage is found, record all 
necessary information on the bill of lading and file 
a claim with the final carrier. Check to be sure that 
all parts of the shipment, including accessories, are 
accounted for. 
Dampers must be kept dry and clean. Indoor storage 
and protection from dirt, dust, and the weather is 
ideal. Do not store at temperatures in excess of  
100°F (37°C).

Table of Contents

General Information  ................................................ 1

Receiving and Handling  ......................................... 1

Pre-Installation Guidelines ...................................... 2

Electrical Guidelines  ............................................... 2

Installation  .........................................................3-10

Setup & Operation for AMD-xx-TD Series 

Dampers  ................................................................. 3

AMD-xx-TD Series without a Factory Supplied 
Controller  ................................................................ 4

AMD-xx-TD Series Ordered with a Factory Supplied 
Actuator  ...............................................................4-5

  Analog Factory Supplied Controller  ..................... 4

  BACnet Enabled Factory Supplied Controller ...... 5

Setting the Actuator/Controller’s BACnet 
Configuration  .......................................................6-9

Optimal Placement for AMD-xx-TD  ................10-11

Minimum Installation Requirements  ..................... 12

Maintenance  ......................................................... 12

Warranty  ............................................................... 12

Our Commitment  .................................................. 12

®

AMD-xx-TD Series

1

Document 478799

AMD-xx-TD Series

Installation, Operation and Maintenance Manual

Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, 
operate or maintain the product described. Protect yourself and others by observing all safety information. Failure 
to comply with these instructions will result in voiding of the product warranty and may result in personal injury 
and/or property damage.

Summary of Contents for AMD TD Series

Page 1: ...stallation 3 10 Setup Operation for AMD xx TD Series Dampers 3 AMD xx TD Series without a Factory Supplied Controller 4 AMD xx TD Series Ordered with a Factory Supplied Actuator 4 5 Analog Factory Supplied Controller 4 BACnet Enabled Factory Supplied Controller 5 Setting the Actuator Controller s BACnet Configuration 6 9 Optimal Placement for AMD xx TD 10 11 Minimum Installation Requirements 12 Mai...

Page 2: ... of such foreign materials include but are not limited to a Mortar dust b Drywall dust c Firesafing materials d Wall texture e Paint overspray Spreader Bar Attachments Multi section dampers 6 Damper should be sufficiently covered as to prevent overspray if wall texturing or spray painting will be performed within 5 feet 1 5m of the damper Excessive dirt or foreign material deposits on the damper can...

Page 3: ...pposite lower corners of each section 5 Damper blades axles and linkage must operate without binding Before system operation you can cycle dampers after installation to assure proper operation On multiple section assemblies all sections should open and close simultaneously Setup and Operation for AMD xx TD Series Damper All AMD xx TD s are supplied with a Vari Green airflow rate transmitter that is...

Page 4: ...s 1 2 5 Measured Velocity Max Velocity Measured Voltage 10 Measured Velocity 2 000 3 5 10 Measured Velocity 700 fpm and Measured CFM Measured Velocity Area Measured CFM 700 fpm 4 ft2 Measured CFM 2 800 cfm AMD xx TD Series Ordered with a Factory Supplied Controller When you order a factory supplied controller it comes with a Greenheck exclusive VAF24 BAC GTD actuator which has the controller integ...

Page 5: ...mper such that it maintains a desired cfm setpoint The setpoint is established by the BACnetSetpoint datapoint Table 1 lists all of the BACnet datapoints The BACnet Setpoint is a percentage of the MaxCFMSetpoint datapoint which is set at the factory based on the maximum velocity which is selected at the time the unit is ordered Example 3 Determine the BACnet setpoint for a 24 in x 24 in AMD with a...

Page 6: ...work Connections Right click on the Local Area Connection and select Properties Access IP Address Settings 1 Select Internet Protocol Windows 7 or 8 Select Internet Protocol Version 4 TCP IPv4 the click on Properties Windows XP Select Internet Protocol TCP IP the select Properties 2 Change the IP Address to the value shown below Then hit the Tab key and the Subnet mask will populate Then click OK ...

Page 7: ...en the Setpoint Source is set not set to BACnet this variable has no impact on controlling the damper SafetyStatus BI 1 C Represents the status of the safety circuit Inactive Open Failure Active Closed OK MaximumFPM MV 1 C Represents the maximum setpoint velocity in fpm The value this variable is set to corresponds to a 10 VDC input to the actuator This value is set at the factory based on maximum...

Page 8: ...s MS TP Address is done via the integrated web server BACnet Standard Device Profile BACnet Application Specific Controller B ASC BACnet Interoperability Building Blocks supported Data Sharing ReadProperty B DS RP B Data Sharing ReadPropertyMultiple B DS RPM B Data Sharing WriteProperty B DS WP B Device Management DynamicDeviceBinding B DM DDB B Device Management DynamicObjectBinding B DM DOB B De...

Page 9: ...ion APDU_Timeout Number_Of_APDU_Retries Max_Master 2 Max_Info_Frames2 Multistate Input Description State_Text Multistate Value Description State_Text Relinquish_Default1 Priority_Array1 Present_Value Multistate Output Description State_Text Relinquish_Default1 Priority_Array1 Present_Value The properties Object_Name and Location of the Device Object support up to 255 characters all other character...

Page 10: ... 1 5D 90 Elbow Without Vanes 1 2D 1D Round Sweep Elbow Optimal Placement for AMD xx TD Damper Series Fans 2D Centrifugal Fan Discharge 3 4D Centrifugal Fan Inlet 3D Vane Axial Fan Discharge 1D Vane Axial Fan Inlet AMD xx TD Series 10 ...

Page 11: ...TD Damper Series Takeoffs 1 5D Branch Takeoff 2 1D Branch Takeoff B1 Transitions 1 2D Į Į Transition 1 Bellmouth Inlets 1 2D Į Į Transition 3 Circular Duct D Duct Diameter 4 x Width x Height H Rectangular Duct D AMD xx TD Series 11 ...

Page 12: ...ts When installing the AMD xx TD the installation should match as closely as possible to one othe examples shown on pages 10 and 11 Failure to match the installation examples may negatively affect the performance and accuracy of the AMD xx TD Avoid locating the AMD xx TD where they will be exposed to condensing moisture such as downstream of a coil or humidifier Design requirements for installing t...

Reviews: