AMD-xx-TD Series Damper Without a 
Factory Supplied Controller

Units ordered without a factory supplied controller are 
supplied with a standard modulating actuator. The Vari-
Green transmitter and actuator are wired to a factory 
supplied terminal block.

 Figure 1

 shows the field wiring 

side of the terminal block.

The 0-10 VDC analog output at terminals 3 and 4 comes 
from the Vari-Green transmitter and is proportional 
to the velocity going through the AMD-xx-TD. A 10 
VDC signal represents the maximum velocity that was 
selected at the time the unit was ordered. The selected 
maximum velocity and the area of the AMD-xx-TD 
are listed on a label adjacent to the terminal block. An 
example of how you can determine the velocity and/or 
cfm going through the unit is shown below.

1 2 3 4 5 6

9

7 8

S

S

~

D

D

D

24VAC

0-10VDC Output 

Proportional to 

Flow

Control 

Signal to 

Actuator

AMD-XX-TD w/o Factory 

Supplied Controller

Factory Installed 

Terminal Block

 On multiple section high dampers, the 

actuators on the sections without the 

terminal block will need to be field wired 

into Terminals 1, 2, & 5

***

***

 Measured 

Velocity

 = Max Velocity * (Measured 

 

 

Voltage / 10) 

 

Measured Velocity

 = 2,000 * (3.5 / 10) 

 

Measured Velocity

 = 700 fpm

and

 Measured 

CFM

 = Measured Velocity * Area 

 

Measured CFM

 = 700 fpm * 4 ft2 

 

Measured CFM

 = 2,800 cfm

AMD-xx-TD Series Ordered with a 
Factory Supplied Controller

When you order a factory supplied controller, it comes 
with a Greenheck exclusive VAF24-BAC-GTD actuator 
which has the controller integrate inside of it. The 
actuator/controller is configured by the factory at the 
time the unit was ordered for either analog or BACnet 
operation. This selection is made by setting the Setpoint 
Source datapoint to Local AI or BACnet. A complete list 
of all the BACnet datapoints is listed in Table 1 (page 7).

AMD-xx-TD Series Damper with an 
Analog Factory Supplied Controller

Figure 2 

shows field wiring for an AMD-xx-TD ordered 

with a factory supplied controller configured for analog 
operation.

1 2 3 4 5 6

9

7 8

S

S

~

D

D

D

24VAC

Factory Installed 
Terminal Block

0-10 VDC Output 

Proportional to 

Flow

0-10VDC 

Input 

Setpoint

AMD-XX-TD w/Analog 

Factory Supplied 

Controller

Figure 2

Figure 1

Example 1:

 

Determine the CFM  from a 24 in. x 24 in. AMD-xx-TD 
(area of 4 ft

2

) with a selected maximum velocity of 2,000 

fpm and a voltage reading across terminals 3 and 4 of 
3.5 VDC.

AMD-xx-TD Series

4

Summary of Contents for AMD TD Series

Page 1: ...stallation 3 10 Setup Operation for AMD xx TD Series Dampers 3 AMD xx TD Series without a Factory Supplied Controller 4 AMD xx TD Series Ordered with a Factory Supplied Actuator 4 5 Analog Factory Supplied Controller 4 BACnet Enabled Factory Supplied Controller 5 Setting the Actuator Controller s BACnet Configuration 6 9 Optimal Placement for AMD xx TD 10 11 Minimum Installation Requirements 12 Mai...

Page 2: ... of such foreign materials include but are not limited to a Mortar dust b Drywall dust c Firesafing materials d Wall texture e Paint overspray Spreader Bar Attachments Multi section dampers 6 Damper should be sufficiently covered as to prevent overspray if wall texturing or spray painting will be performed within 5 feet 1 5m of the damper Excessive dirt or foreign material deposits on the damper can...

Page 3: ...pposite lower corners of each section 5 Damper blades axles and linkage must operate without binding Before system operation you can cycle dampers after installation to assure proper operation On multiple section assemblies all sections should open and close simultaneously Setup and Operation for AMD xx TD Series Damper All AMD xx TD s are supplied with a Vari Green airflow rate transmitter that is...

Page 4: ...s 1 2 5 Measured Velocity Max Velocity Measured Voltage 10 Measured Velocity 2 000 3 5 10 Measured Velocity 700 fpm and Measured CFM Measured Velocity Area Measured CFM 700 fpm 4 ft2 Measured CFM 2 800 cfm AMD xx TD Series Ordered with a Factory Supplied Controller When you order a factory supplied controller it comes with a Greenheck exclusive VAF24 BAC GTD actuator which has the controller integ...

Page 5: ...mper such that it maintains a desired cfm setpoint The setpoint is established by the BACnetSetpoint datapoint Table 1 lists all of the BACnet datapoints The BACnet Setpoint is a percentage of the MaxCFMSetpoint datapoint which is set at the factory based on the maximum velocity which is selected at the time the unit is ordered Example 3 Determine the BACnet setpoint for a 24 in x 24 in AMD with a...

Page 6: ...work Connections Right click on the Local Area Connection and select Properties Access IP Address Settings 1 Select Internet Protocol Windows 7 or 8 Select Internet Protocol Version 4 TCP IPv4 the click on Properties Windows XP Select Internet Protocol TCP IP the select Properties 2 Change the IP Address to the value shown below Then hit the Tab key and the Subnet mask will populate Then click OK ...

Page 7: ...en the Setpoint Source is set not set to BACnet this variable has no impact on controlling the damper SafetyStatus BI 1 C Represents the status of the safety circuit Inactive Open Failure Active Closed OK MaximumFPM MV 1 C Represents the maximum setpoint velocity in fpm The value this variable is set to corresponds to a 10 VDC input to the actuator This value is set at the factory based on maximum...

Page 8: ...s MS TP Address is done via the integrated web server BACnet Standard Device Profile BACnet Application Specific Controller B ASC BACnet Interoperability Building Blocks supported Data Sharing ReadProperty B DS RP B Data Sharing ReadPropertyMultiple B DS RPM B Data Sharing WriteProperty B DS WP B Device Management DynamicDeviceBinding B DM DDB B Device Management DynamicObjectBinding B DM DOB B De...

Page 9: ...ion APDU_Timeout Number_Of_APDU_Retries Max_Master 2 Max_Info_Frames2 Multistate Input Description State_Text Multistate Value Description State_Text Relinquish_Default1 Priority_Array1 Present_Value Multistate Output Description State_Text Relinquish_Default1 Priority_Array1 Present_Value The properties Object_Name and Location of the Device Object support up to 255 characters all other character...

Page 10: ... 1 5D 90 Elbow Without Vanes 1 2D 1D Round Sweep Elbow Optimal Placement for AMD xx TD Damper Series Fans 2D Centrifugal Fan Discharge 3 4D Centrifugal Fan Inlet 3D Vane Axial Fan Discharge 1D Vane Axial Fan Inlet AMD xx TD Series 10 ...

Page 11: ...TD Damper Series Takeoffs 1 5D Branch Takeoff 2 1D Branch Takeoff B1 Transitions 1 2D Į Į Transition 1 Bellmouth Inlets 1 2D Į Į Transition 3 Circular Duct D Duct Diameter 4 x Width x Height H Rectangular Duct D AMD xx TD Series 11 ...

Page 12: ...ts When installing the AMD xx TD the installation should match as closely as possible to one othe examples shown on pages 10 and 11 Failure to match the installation examples may negatively affect the performance and accuracy of the AMD xx TD Avoid locating the AMD xx TD where they will be exposed to condensing moisture such as downstream of a coil or humidifier Design requirements for installing t...