background image

6. 

AMD-xx-TD

 series more than one section high will be 

shipped separately in individual sleeves. Using the provided 
RJ-45 cable connect the bottom probe on the top section to 
the top probe on the bottom section. The bottom section has 
the transmitter mounted to it.

Do not twist 
or bow. Mount 
damper plumb  
in the opening.

A

B

AF = BE

AB = CD

C

D

E

F

Installation - 

Failure to follow instructions will 

void all warranties

1.  Ensure the AMD-XX-TD series dampers is mounted 

with measurement probes upstream of the damper.

2.  Your duct opening or opening square should measure 

1/4 inch (6mm) larger than damper dimension and 
should be straight and level.

3.  Use shims between damper frame and duct opening 

or opening space to prevent distortion of frame by 
fasteners holding it in place. Brace at every horizontal 
mullion and vertically brace at every 8 feet (2.4m) of 
damper width for strength. Dampers in high velocity 
(2000 fpm [610m per second]) may require more 
bracing.

    NOTE: Greenheck dampers are specifically designed 

and engineered for structural integrity based on model 
and conditions. Attachment, framing, mating flanges, 
and anchoring of damper assemblies into openings, 
ductwork, or walls is the responsibility of the installer. 
Design calculations for these retaining and supporting 
members should be determined by field engineers for 
that particular installation.

4. Individual damper sections, as well as entire multiple 

section assemblies must be completely square and 
free from racking, twisting, or bending. Measure 
diagonally from upper corners to opposite lower 
corners of each section.

5. Damper blades, axles, and linkage must operate 

without binding. Before system operation, you can 
cycle dampers after installation to assure proper 
operation. On multiple section assemblies all sections 
should open and close simultaneously.

Setup and Operation for AMD-xx-TD 
Series Damper

All AMD-xx-TD’s are supplied with a Vari-Green® 
airflow rate transmitter that is factory wired to one or 
more Vari-Green airflow measurement probe(s). The 
transmitter has been configured at the factory with 
customer supplied parameters. For normal applications 
the transmitter’s configuration should not need to be 
modified in the field. However, if field configuration is 
necessary please reference the Vari-Green transmitter 
Installation, Operation, and Maintenance Manual 
available at

 

www.greenheck.com.

Once electrical power is applied, the transmitter will 
go through a standard start-up sequence during which 
it will identify and enable each airflow sensor. This will 
take approximately 25 seconds. Once the start-up 
sequence has been complete, the transmitter’s display 
will show the measured volumetric airflow rate, velocity, 
and ambient air temperature (see below). Under normal 
operation, a blinking green dot in the upper right corner 
of the display signifies that the processor is functioning 
correctly, and two flashing arrows indicate that the 
sensor(s) and transmitter are communicating normally.

You can order AMD-xx-TD’s with or without a factory 
supplied controller. When a factory supplied controller 
is ordered, the controller can be configured for either 
analog operation or operation via a BACnet MS/TP 
connection. Setup and operation for these different 
options are described on the following pages.

AMD-xx-TD Series

3

Summary of Contents for AMD TD Series

Page 1: ...stallation 3 10 Setup Operation for AMD xx TD Series Dampers 3 AMD xx TD Series without a Factory Supplied Controller 4 AMD xx TD Series Ordered with a Factory Supplied Actuator 4 5 Analog Factory Supplied Controller 4 BACnet Enabled Factory Supplied Controller 5 Setting the Actuator Controller s BACnet Configuration 6 9 Optimal Placement for AMD xx TD 10 11 Minimum Installation Requirements 12 Mai...

Page 2: ... of such foreign materials include but are not limited to a Mortar dust b Drywall dust c Firesafing materials d Wall texture e Paint overspray Spreader Bar Attachments Multi section dampers 6 Damper should be sufficiently covered as to prevent overspray if wall texturing or spray painting will be performed within 5 feet 1 5m of the damper Excessive dirt or foreign material deposits on the damper can...

Page 3: ...pposite lower corners of each section 5 Damper blades axles and linkage must operate without binding Before system operation you can cycle dampers after installation to assure proper operation On multiple section assemblies all sections should open and close simultaneously Setup and Operation for AMD xx TD Series Damper All AMD xx TD s are supplied with a Vari Green airflow rate transmitter that is...

Page 4: ...s 1 2 5 Measured Velocity Max Velocity Measured Voltage 10 Measured Velocity 2 000 3 5 10 Measured Velocity 700 fpm and Measured CFM Measured Velocity Area Measured CFM 700 fpm 4 ft2 Measured CFM 2 800 cfm AMD xx TD Series Ordered with a Factory Supplied Controller When you order a factory supplied controller it comes with a Greenheck exclusive VAF24 BAC GTD actuator which has the controller integ...

Page 5: ...mper such that it maintains a desired cfm setpoint The setpoint is established by the BACnetSetpoint datapoint Table 1 lists all of the BACnet datapoints The BACnet Setpoint is a percentage of the MaxCFMSetpoint datapoint which is set at the factory based on the maximum velocity which is selected at the time the unit is ordered Example 3 Determine the BACnet setpoint for a 24 in x 24 in AMD with a...

Page 6: ...work Connections Right click on the Local Area Connection and select Properties Access IP Address Settings 1 Select Internet Protocol Windows 7 or 8 Select Internet Protocol Version 4 TCP IPv4 the click on Properties Windows XP Select Internet Protocol TCP IP the select Properties 2 Change the IP Address to the value shown below Then hit the Tab key and the Subnet mask will populate Then click OK ...

Page 7: ...en the Setpoint Source is set not set to BACnet this variable has no impact on controlling the damper SafetyStatus BI 1 C Represents the status of the safety circuit Inactive Open Failure Active Closed OK MaximumFPM MV 1 C Represents the maximum setpoint velocity in fpm The value this variable is set to corresponds to a 10 VDC input to the actuator This value is set at the factory based on maximum...

Page 8: ...s MS TP Address is done via the integrated web server BACnet Standard Device Profile BACnet Application Specific Controller B ASC BACnet Interoperability Building Blocks supported Data Sharing ReadProperty B DS RP B Data Sharing ReadPropertyMultiple B DS RPM B Data Sharing WriteProperty B DS WP B Device Management DynamicDeviceBinding B DM DDB B Device Management DynamicObjectBinding B DM DOB B De...

Page 9: ...ion APDU_Timeout Number_Of_APDU_Retries Max_Master 2 Max_Info_Frames2 Multistate Input Description State_Text Multistate Value Description State_Text Relinquish_Default1 Priority_Array1 Present_Value Multistate Output Description State_Text Relinquish_Default1 Priority_Array1 Present_Value The properties Object_Name and Location of the Device Object support up to 255 characters all other character...

Page 10: ... 1 5D 90 Elbow Without Vanes 1 2D 1D Round Sweep Elbow Optimal Placement for AMD xx TD Damper Series Fans 2D Centrifugal Fan Discharge 3 4D Centrifugal Fan Inlet 3D Vane Axial Fan Discharge 1D Vane Axial Fan Inlet AMD xx TD Series 10 ...

Page 11: ...TD Damper Series Takeoffs 1 5D Branch Takeoff 2 1D Branch Takeoff B1 Transitions 1 2D Į Į Transition 1 Bellmouth Inlets 1 2D Į Į Transition 3 Circular Duct D Duct Diameter 4 x Width x Height H Rectangular Duct D AMD xx TD Series 11 ...

Page 12: ...ts When installing the AMD xx TD the installation should match as closely as possible to one othe examples shown on pages 10 and 11 Failure to match the installation examples may negatively affect the performance and accuracy of the AMD xx TD Avoid locating the AMD xx TD where they will be exposed to condensing moisture such as downstream of a coil or humidifier Design requirements for installing t...