Frequently Asked Questions

What temperature is the temperature controller set 
to from the factory?

 95º 

Fahrenheit.

Will the temperature interlock automatically start/
stop the fans?

 

When connected properly to fan starters the 
temperature interlock will automatically control 
the fans without input from the user. However, the 
intended use of the temperature interlock is as back-
up to manual control.

May I connect the power going to my fan directly 
through the control box?

 

No, the control box should only use control voltage 
only (24-120V), and a separate 120V power source 
is required to run the temperature interlock controls. 
Greenheck recommends the use of starters sized for 
each fan.

Can I use one control box for multiple hood systems?

 

This can be done, however, it is not recommended. 
Any one of the temperature controllers would turn on 
all hoods running on that control box. It is better to 
have one hood/fan per control box, plus a significant 
energy savings can be obtained if one or more of the 
hoods is not in operation.

Can I still turn my fan on and off?

  

Yes, the temperature interlock is designed to be 
operated with a typical on/off switch. The fan may not 
turn off directly after turning the fan switch off, it will 
sense when the cooking operations have cooled and 
then turn off.

Replacement Parts

Part 

Number

Description

384925

Temperature Sensor (RTD) 
MAMAC TE-700-0-3-A

384920

Temperature Controller 
CAREL iR33-DN33 DN33W7HR20

830125

Extension, Octagon (drilled)  
SC55151-1/2 (380928)

732396

J-Box Plate

380926

Cover, Octagon Box  
SC#54-C-1RACO 722

384905

Terminal Block, Single Pole,  
DIN-RAIL MT, ABB ZS6

384908

Jumper, DIN-RAIL  
Terminal Block Two Pole ABB JB6-2

463570

Evergreen Compression Seal 
1/4-inch, #302

Codes and Standards Compliance

• UL 

710

•  National Fire Protection Association (NFPA 96)

•  International Mechanical Code (IMC) 2006  

Section 507.2.1.1

8

474750 • Digital Temperature Interlock, Rev. 3, November 2012 

Copyright 2012 © Greenheck Fan Corporation

As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications 
without notice.

Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the 
Library under Warranties.

®

Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: [email protected] • Website: www.greenheck.com

Our Commitment

AMCA Publication 410-96, Safety Practices for Users and Installers of Industrial and Commercial Fans, provides additional safety 
information. This publication can be obtained from AMCA International, Inc. at www.amca.org.

Summary of Contents for 474750

Page 1: ...ng equipment generates heat Basic controls will be provided with a temperature sensor and will consist of an 8 x 8 electrical box with controls and a labeled terminal strip to hook up incoming power and fan starters A temperature controller is used to keep the exhaust fans running when the temperature controller initially closes to prevent the fan from cycling on and off at startup and shut down F...

Page 2: ...ill void the warranty NOTE Resistive temperature detector s may be factory installed If so continue to the next section Resistive Temperature Detector s Hood Mounting Installation Control Box Mounting Locate an area with enough space to mount the control box and fasten to the wall Avoid installing the control box in environments with high magnetic and or radio frequency interference 2 Cut a 3 4 to...

Page 3: ...TD PN 384925 Octagon Cover PN 380926 Octagon Extension PN 830125 Electrical Connections Sensor Connections 1 Run two 18 awg stranded thermostat wires from each temperature sensor to the appropriate electrical circuit connections See Step 3 for connection options 2 In junction box connect leads on RTD to the 18 awg conductors using appropriate size wire nuts Wires are interchangeable with one anoth...

Page 4: ...ter code 6 Repeat operations from 4 to 5 to set other parameters 7 To permanently save the new values of the parameters press Prg mute for 5 seconds thus exiting the parameter setting procedure Setting type c d F parameters Type c d or F configuration parameters are indicated by a code beginning with letters c d F respectively followed by one or two numbers 1 Press Prg mute and Set together for mor...

Page 5: ...arters are NOT provided by manufacturer Starters to be provided by wired and mounted by others Wiring for additional sensors optional This is an example of a generic wiring diagram for standard control This diagram has 12 sensors which provide temperature interlock function for two exhaust fans and one supply fan All starters provided by others external to this control box ...

Page 6: ...eneric wiring diagram for temperature interlock integration into a KFCC This diagram has 2 sensors that provide temperature interlock function for one exhaust fan and one supply fan To see your job specific drawing look on the inside panel of the KFCC cabinet 12 inches 18 inches 6 inches LIG HT S FAN S ...

Page 7: ...g testing if fans do not start automatically in the first 10 minutes of cooking equipment activation manually start fans to avoid accidental fire system dump due to heat build up Troubleshooting 1 Controller s display E01 or E02 and fans will not shut off E01 and E02 represent probe faults Check probe resistance between the two leads when disconnected from the system At room temperature 77 F the p...

Page 8: ...n off directly after turning the fan switch off it will sense when the cooking operations have cooled and then turn off Replacement Parts Part Number Description 384925 Temperature Sensor RTD MAMAC TE 700 0 3 A 384920 Temperature Controller CAREL iR33 DN33 DN33W7HR20 830125 Extension Octagon drilled SC55151 1 2 380928 732396 J Box Plate 380926 Cover Octagon Box SC 54 C 1RACO 722 384905 Terminal Bl...

Reviews: