background image

4

Digital Temperature Interlock

Calibration

The temperature controller is preset by the factory to 
turn the fans on at 95°F. This is controlled by the set 
point on the temperature controller. The temperature set 
point may have to be adjusted slightly depending on 
both ambient and cooking conditions. The adjustment is 
made through the buttons on the temperature controller. 
The controller is capable of monitoring two separate 
sensors. If more than one sensor is utilized with a single 
controller, two set points can be adjusted. To adjust, 
follow these instructions:

1.  If setting set point 1 (St1), press 

Set

. The display 

shows St1 and then the current value of St1. 

 

If setting set point 2 (St2), press 

Set

 twice, slowly. 

The display shows St2 and then the current value of 
St2.

2.  Press the 

S

 or 

T

 to change the set point.

3. Press 

Set

 to confirm the new value of either St1 or 

St2.

4.  Check system operation before making additional 

adjustments.

Factory Selected Parameters

The factory will pre-program the controllers to be 
properly integrated into the control panel. Except for 
the set points, the other parameters should never need 
adjusting. However, there are three different types of 
parameters that are accessible on the controller. Access 
differs depending on the type: set point; frequently used 
parameters (P); and configuration parameters (c, d, F).

Setting type P parameters

Type P parameters (frequents) are indicated by a code 
beginning with the letter P, followed by one or two 
numbers. 

1. Hold the 

Prg

mute

 button, after 3 seconds the displays 

shows the firmware revision code (e.g. r2.1) is 
shown, after 5 seconds (in the event of alarms, first 
the buzzer is muted) the code of the first type P 
modifiable parameter, P1.

2. Press 

S

 or 

T

 until reaching the desired parameter.

3. Press 

Set

 to display the associated value.

4.  Increase or decrease the value using 

S

 or 

T

 

respectively, until reaching the desired value.

5. Press 

Set

 to 

temporarily

 save the new value and 

return to the display of the parameter code.

6.  Repeat operations from 4 to 5 to set other 

parameters.

7. To 

permanently

 save the new values of the 

parameters, press 

Prg

mute

 for 5 seconds, thus exiting 

the parameter setting procedure.

Setting type c, d, F parameters

Type c, d or F (configuration) parameters are indicated 
by a code beginning with letters c, d, F respectively, 
followed by one or two numbers.

1. Press 

Prg

mute

 and 

Set

 together for more than 5 

seconds. The display shows the number 0.

2. Press 

S

 or 

T

 until displaying the password:  77

3.  Confirm by pressing 

Set

4.  If the value entered is correct, the first modifiable 

parameter c0 will be shown, otherwise the standard 
display will resume.

5. Press 

S

 or 

T

 until reaching the parameter to be 

modified.

6. Press 

Set

 to display the associated value.

7.  Increase or decrease the value using 

S

 or 

T

 

respectively, until reaching the desired value.

8. Press 

Set

 to 

temporarily

 save the new value and 

return to the display of the parameter code.

9.  Repeat operations from 5 to 8 to set other 

parameters.

10. To 

permanently

 save the new values of the 

parameters, press 

Prg

mute

 for 5 seconds, thus exiting 

the parameter setting procedure.

Factory Selected Parameters

Parameter

Description

Factory Setting

St1

Set Point 1

95

St2

Set Point 2

95

c0

Operating Mode

1

P1

Set Point Differential

5.0

P2

Set Point Differential

5.0

P3

Dead Zone Differential

0

c6

Delay between two outputs

0

c9

Minimum relay on time

5

c10

Probe alarm output status 1

1

d10

Probe alarm output status 2

1

c11

Output Rotation

4

c13

Probe Type

3

P14

Probe 1 Calibration

0

P15

Probe 2 Calibration

0

c18

Unit of Measure

1

c19*

Function of probe 2

0 or 7

*Parameter c19 is factory set at 0. If controller is connected to two 
sensors, then the parameter is factory set at 7..

NOTE

The controller is pre-programed at the factory to  
operate with the digital temperature interlock 
components. No further parameter changes should  
be necessary.

Displaying the Inputs

1. Press 

T

.  The current input will be displayed, 

alternating with the value:

b1 : probe1
b2 : probe 2
di1 : digital input 1
di2 : digital input 2
St1 : set point 1
St2 : set point 2

2. Press 

S

 or 

T

 to select the input to be displayed.

3. Press 

Set

 for three seconds to confirm.

®

Summary of Contents for 474750

Page 1: ...ng equipment generates heat Basic controls will be provided with a temperature sensor and will consist of an 8 x 8 electrical box with controls and a labeled terminal strip to hook up incoming power and fan starters A temperature controller is used to keep the exhaust fans running when the temperature controller initially closes to prevent the fan from cycling on and off at startup and shut down F...

Page 2: ...ill void the warranty NOTE Resistive temperature detector s may be factory installed If so continue to the next section Resistive Temperature Detector s Hood Mounting Installation Control Box Mounting Locate an area with enough space to mount the control box and fasten to the wall Avoid installing the control box in environments with high magnetic and or radio frequency interference 2 Cut a 3 4 to...

Page 3: ...TD PN 384925 Octagon Cover PN 380926 Octagon Extension PN 830125 Electrical Connections Sensor Connections 1 Run two 18 awg stranded thermostat wires from each temperature sensor to the appropriate electrical circuit connections See Step 3 for connection options 2 In junction box connect leads on RTD to the 18 awg conductors using appropriate size wire nuts Wires are interchangeable with one anoth...

Page 4: ...ter code 6 Repeat operations from 4 to 5 to set other parameters 7 To permanently save the new values of the parameters press Prg mute for 5 seconds thus exiting the parameter setting procedure Setting type c d F parameters Type c d or F configuration parameters are indicated by a code beginning with letters c d F respectively followed by one or two numbers 1 Press Prg mute and Set together for mor...

Page 5: ...arters are NOT provided by manufacturer Starters to be provided by wired and mounted by others Wiring for additional sensors optional This is an example of a generic wiring diagram for standard control This diagram has 12 sensors which provide temperature interlock function for two exhaust fans and one supply fan All starters provided by others external to this control box ...

Page 6: ...eneric wiring diagram for temperature interlock integration into a KFCC This diagram has 2 sensors that provide temperature interlock function for one exhaust fan and one supply fan To see your job specific drawing look on the inside panel of the KFCC cabinet 12 inches 18 inches 6 inches LIG HT S FAN S ...

Page 7: ...g testing if fans do not start automatically in the first 10 minutes of cooking equipment activation manually start fans to avoid accidental fire system dump due to heat build up Troubleshooting 1 Controller s display E01 or E02 and fans will not shut off E01 and E02 represent probe faults Check probe resistance between the two leads when disconnected from the system At room temperature 77 F the p...

Page 8: ...n off directly after turning the fan switch off it will sense when the cooking operations have cooled and then turn off Replacement Parts Part Number Description 384925 Temperature Sensor RTD MAMAC TE 700 0 3 A 384920 Temperature Controller CAREL iR33 DN33 DN33W7HR20 830125 Extension Octagon drilled SC55151 1 2 380928 732396 J Box Plate 380926 Cover Octagon Box SC 54 C 1RACO 722 384905 Terminal Bl...

Reviews: