background image

2

Connecting Low Voltage Inputs

ControlKeeper® TouchScreen Logic Board

Figure 1.  16 size Enclosure with CKT Mounted

Connecting Low Voltage Inputs

The ControlKeeper T logic board can support a total of 

64 switch inputs. Of these 64 inputs, 32 of them may 

be dry contact closure inputs that are connected to 

the terminal blocks at the bottom of the ControlKeeper

 

Logic Board. Digital

 

switch inputs may also be used on 

the ControlKeeper. If no contact input type switches are 

being used, the full 64 switch inputs may consist of digital 

switches. If a combination of contact input switches and 

digital switches are being used, the combined total cannot 

exceed 64 inputs.
The ControlKeeper T Logic Board can support a total of 4 

analog inputs. The logic board contains 32 software analog 

inputs to allow these four physical analog inputs to be 

programmed at different switching thresholds to achieve the 

multi threshold application from a single analog input.
Regardless of input type used, it is recommended that all 

input wiring be done prior to applying power to the logic 

board or at the very least with the terminal blocks removed 

from the logic board. Please verify that there are no shorts 

to AC ground prior to connection of input devices.
Regardless of input type, the following notes apply.
1.  All low voltage wiring is Class 2 wiring.
2.  All low voltage wiring must enter the cabinet into the 

low voltage section of the enclosure. Low voltage 

wiring can be brought into the enclosure from the 

bottom or bottom left of the enclosure. If low voltage 

wire must be brought into the cabinet from the top 

section, there is a knockout reserved on the left side 

which will allow conduit to be run from the top of the 

enclosure into the low voltage wiring area. Failure to 

separate high voltage from low voltage wiring may 

cause interference with logic board function.

3.  All low voltage wiring must be run in separate conduit 

from line voltage wiring.

4.  Test all low voltage wiring for shorts to AC ground 

before connection to the ControlKeeper T panel.

5.  When powering peripheral devices such as motion 

sensors and photocells from the ControlKeeper T 

panel, there may be a limitation on the number of 

sensors that can be supported. This is also true if 

lighted switches or digital switches are being used 

with the system. Please contact Greengate for specific 

information on device limitations if using these devices.

6.  It is recommended that the terminal blocks be removed 

from the board or power removed from the logic board 

when doing initial switch input wiring.

Contact Input Switch Wiring

This section describes the wiring for dry contact closure 

devices. There are 32 switch input wiring terminals on the 

bottom of the ControlKeeper T to allow for wiring of the dry 

contact closure devices. 
1.  Use 18 AWG twisted, unshielded wire for all low 

voltage, dry contact closure device wiring.

2.  Maximum length for dry contact closure device wiring 

is 1000 feet.

3.  Ensure that the local remote jumpers have been moved 

to the local position (over pins 2 & 3) for both jumpers 

(J9 & J10) to enable 24 VDC to the low voltage switch 

channels. See Figure 2 below for location.

4.  Please see wiring detail in Figure 2 for details on 

connections of different devices to the ControlKeeper T 

system.

Figure 2.  ControlKeeper T Low-Voltage Switch Wiring

Summary of Contents for CKT LB

Page 1: ...on when performing maintenance on this equipment Failure to follow this warning and proper safety procedures could result in severe injury or death and or damage to the equipment 8 Document all wiring...

Page 2: ...e brought into the cabinet from the top section there is a knockout reserved on the left side which will allow conduit to be run from the top of the enclosure into the low voltage wiring area Failure...

Page 3: ...with the lighting control system The ControlKeeper T enclosures are capable of powering a number of these devices Please refer to the chart below for details on how many devices the transformer can s...

Page 4: ...10 to enable 24 VDC to the low voltage switch channels See Figure 3 for location Figure 3 Digital Switch Gateway Wiring Detail Analog Input Wiring This section describes the wiring for analog input de...

Page 5: ...using Belden 9841 or 89841 leave all shields disconnected making certain that shield is not exposed These wire types will be connected to a special terminal block on the right side of the controller...

Page 6: ...hat comes out of the top of the CKT logic panel into the Relay Stack Controller Card RSC located at the bottom of the enclosure This connection should be made to the left most terminal on the RSC See...

Page 7: ...means of overriding relays ON or OFF without the need of the logic board in place First there are individual relay override buttons for each relay located on the relay hardware Second there is an all...

Page 8: ...se the soft reset button on the controller If the LED does not resume normal flashing state contact technical support Digital Switch LEDs These LEDs labeled CAN TX and CAN RX will flash when digital s...

Page 9: ...all the time check that the Power LED on the RSC is lit then use the reset button on the ControlKeeper T and see if the LED resumes the blinking state If the Relay Status LED does not resume its norma...

Page 10: ...t to touch anywhere else on the screen If more than a minute goes by without all four corners being touched or if you touch anything other than the four corners you will leave the memory clear functio...

Page 11: ...ion 11 Network Termination Jumper 12 LCD Display Contrast Tuning Potentiometer 13 Local Remote Jumpers 14 Remote Power Connector DC Gnd 24V 15 Contact Input Switch Wiring Channels 16 Relay Stack Contr...

Page 12: ...le ControlKeeper T 1 Enlevez les d tritus et les rognures de m tal dans le bo tier 2 Assurez vous qu aucun c blage haute tension n est expos De plus il ne doit pas y avoir de c blage haute tension da...

Page 13: ...C blage des interrupteurs d entr e par contact Cette section d crit le c blage pour les dispositifs de fermeture contact sec Il y a trente deux bornes d entr e pour les interrupteurs sur le fond du C...

Page 14: ...tifs veuillez communiquer avec le soutien technique pour conna tre les limites exactes sur le nombre de dispositifs pouvant tre aliment par la carte logique C blage des capteurs de photod tection et d...

Page 15: ...es J9 et J10 pour mettre en service 24 V c c aux canaux d interrupteur basse tension Voir figure 3 pour l emplacement Figure 3 D tails du c blage de la passerelle pour interrupteurs num riques C blage...

Page 16: ...a carte logique 3 Tout le c blage basse tension doit tre achemin dans un tuyau s par du c blage de tension de ligne 4 V rifiez l absence de courts circuits de la mise la terre c a dans tous les c blag...

Page 17: ...d alimentation raccord en plastique blanc auquel six fils sont rattach s qui passe par le dessus du panneau de logique du ControlKeeper T pour rejoindre la carte de contr leur de relais en s rie RSC...

Page 18: ...tilisant ces m canismes de prise en charge sans que le panneau de logique ne soit en place Notes de prise en charge de relais individuel Les prises en charge de relais individuels sont situ es dans la...

Page 19: ...nique pour plus de d tails R seau DEL Le R seau DEL devrait uniquement clignoter quand une activit est pr sente sur le c blage r seau Si des instructions de communications ne sont pas transmises par l...

Page 20: ...muniquer avec le Soutien technique pour r soudre ce probl me Indicateur DEL de relais L indicateur DEL de relais indique que le relais est mis sous tension ou hors tension Si le relais a t mis sous te...

Page 21: ...n d affichage un coin apr s l autre dans le sens des aiguilles d une montre en vous assurant de ne pas toucher d autres endroits sur l cran S il se passe plus d une minute sans que les quatre coins so...

Page 22: ...son de r seau 12 Potentiom tre de r glage de contraste de l affichage LCD 13 Bretelles locales distance 14 Connexion alimentation distance DC Gnd 24 V 15 Canaux de c blage interrupteur d entr e contac...

Page 23: ...siones graves o la muerte o da os en el equipo 8 Documente todas las terminaciones y ubicaciones del cableado y del dispositivo de modo que los dispositivos se puedan configurar y programar correctame...

Page 24: ...lojamiento hacia el rea de conexiones de bajo voltaje De no separar los cables de alto y bajo voltaje se pueden generar interferencias en la funci n de la placa l gica 3 Todos los cables de bajo volta...

Page 25: ...olador Adem s si los tipos de interruptores son combinados el incandescente y el LED en el mismo controlador estas cantidades cambiar n Contacte a Soporte T cnico con los n meros y tipos de entradas q...

Page 26: ...de 24 VCC de entrada del interruptor 4 Conecte el hilo NEGRO del cable al terminal de conexi n a tierra en la parte trasera del GDS I y al terminal de conexi n a tierra del conector de alimentaci n re...

Page 27: ...ierdo o desde su superficie inferior Si se deben ingresar cables de bajo voltaje en el recinto desde la parte superior hay un expulsor reservado en el lateral izquierdo que permitir pasar el conducto...

Page 28: ...rese de limpiar el panel para que no queden residuos o fragmentos Aseg rese de que no hayan quedado fragmentos atrapados entre la placa del circuito y el alojamiento 2 Aseg rese de que no queden cabl...

Page 29: ...er T tiene dos modos de anular el encendido o el apagado de los rel s sin la necesidad de una placa l gica En primer lugar hay dos botones de anulaci n individual de rel s para cada rel ubicado en su...

Page 30: ...parpadear n cuando se pase informaci n del interruptor digital desde y hacia el dispositivo GDS I y el ControlKeeper T El LED CAN RX parpadea cuando el controlador recibe datos del BUS del interrupto...

Page 31: ...parpadeo Si el LED de estado del rel no retoma su estado de parpadeo normal luego del reinicio del ControlKeeper T contacte a Soporte T cnico Si el LED parpadea de manera continua sin parar ello indi...

Page 32: ...do de las agujas del reloj asegur ndose de no tocar en ninguna otra parte de la pantalla Si pasa m s de un minuto sin que se toquen todas las esquinas o si toca otra cosa saldr de la funci n de elimin...

Page 33: ...l para el bloque de rel 26 Interruptor de anulaci n individual de rel s 27 Indicador de estado del rel 28 LED de estado de la tarjeta de rel 29 Conexi n desde el carril central hacia el RSC 1 LED de e...

Page 34: ......

Page 35: ......

Page 36: ...sont la propri t de leur propri taire respectif Eaton es una marca comercial registrada Todas las marcas comerciales son propiedad de sus respectivos propietarios WARRANTIES AND LIMITATION OF LIABILI...

Reviews: