Version 4.37 • CE • ALIS Tube Lamp
21 May 2019
3.2 End termination
All ALIS Dimmer Models.
The correct termination of the ALIS BUS is critical to the overall system performance.
See also section 3.3 of this manual. Connect the ALIS End Termination Module (ETM) or shorting terminal block
to the far open end of the ALIS Bus. The ALIS bus insulation must be properly stripped to ensure there is no to
damage the cable conductors.
Strip the ends of the ALIS Bus to 5mm (0.2 inch) of exposed conductor, ensuring there is not any conductor loss
as shown below. Twist the exposed copper cable strands.
Insert the cable into the terminator fully, ensuring no bare cable can be seen as shown and tighten connections.
This must be a perfect connection with no frayed copper strands. The ETM or short must be housed within an
IP66 terminal enclosure, example below.
A.
ETM (68nF) ALIS Bus connection
B.
Short ALIS Bus connection
Note: All cable points must have glands fitted for strain relief and to maintained IP rating.