background image

 

Page 

19

 of 

28

 

Version 4.37 • CE • ALIS Tube Lamp

 

21 May 2019

 

 

 

6.

 

General points and good practices 

1.

 

All electrical installation work 

must

 be carried out in accordance with all applicable local wiring regulations,  

such as those published by CENELEC member organisations, or those covered by IEC60364. Failure to do so will 

invalidate any associated Product Warranty. 

2.

 

The ALIS Power Hub or Power Hub Panel 

must

 be earthed/grounded via a securely wired electrical connection. 

It is not sufficient to rely solely on the bonded chassis alone. 

3.

 

Ensure that all external cables are of a suitable cross-sectional diameter for the intended use. All external signals 

carrying cable for uses such as 0/10v must be of a suitably screened/shielded type, with the screen/shield 

connected to earth at the supply end only, 

never

 both ends. 

4.

 

For the connection of external wires 

always

 use insulated ‘bootlace’ terminals, which provide a safe and good 

connection, and which are well suited for the purpose. 

5.

 

Splices and cable joints 

must

 be housed within a junction box, which has an IP rating suitable for the 

environment. All cables 

must

 pass through suitable glands to maintain the rating. 

6.

 

Never

 use solid communication style wires such as telephone cable, even if making low voltage/current 

connections, it is not suitable for any of the connectors within the ALIS range and will in time fail. 

7.

 

Cable trunking and conduit. In certain instances, ALIS Bus cable may have to be routed through lidded electrical 

wire carriers. Should this situation arise please 

ensure

 that all ends are sealed, and lids correctly fitted to stop 

fauna (rodent) ingress. 

8.

 

Installations should 

never

 use no more than the required length of ALIS Bus for each ALIS Power Hub. Remove 

any excess end of line ALIS Bus cable at approximately 30cm (12 inches) past the final lamp. 

9.

 

ALIS Bus cable should 

never

 be knotted or looped. it is also 

important

 to avoid sharp bends, returns,  

and kinks. The minimum recommended bend diameter is 75mm (3 inches). 

10.

 

Please 

note

 that poorly made electrical connections are often the main cause of equipment failure, which  

in turn leads to livestock fatalities. 

11.

 

If the ALIS Bus passes through a hole or aperture (metal or otherwise) a suitable insulating grommet or gland 

must

 be fitted. 

12.

 

ALIS Bus cable should 

never

 be un-twisted, apart from through the lamp coupler. 

13.

 

Under no circumstances

 must the ALIS Bus be switched by any means, be that relay, contactor, isolator  

or circuit breaker, unless parts are supplied by Greengage Lighting for that purpose. If this is attempted the 

subsequent damage caused to the ALIS Power Hub will be irreparable and will not be covered by any Product 

Warranty. 

14.

 

Disconnecting the main electrical supply to the ALIS Power Hub as a means of regularly extinguishing the ALIS 

Lamps 

must

 always be avoided. 

15.

 

If switching the 0/10V control signal, the selection of the switching component is extremely important, please 

adhere to the instructions on the relevant circuit diagram, obtainable from 

[email protected]

 

Contact degradation can lead to the situation, particularly at low current levels, where the switching device 

operates mechanically but effectively remains open circuit causing the ALIS lamps to remain at full brilliance. 

Summary of Contents for ALIS CE

Page 1: ...4 37...

Page 2: ...Lift the upper coupler back on its hinge and check the position of the seal Due to the compression the seal may have stuck to the upper coupler If this has occurred then peel the seal off and positio...

Page 3: ...installers should contact Greengage Lighting Ltd technical support with any queries they may have at support greengage global Please follow these instructions carefully as deviation from them may inva...

Page 4: ...0 General guidance 11 3 1 ALIS bus termination 12 3 2 End termination 13 3 3 End termination rules 14 3 4 Hub supply cable termination CE 15 3 5 Hub supply cable termination UL 15 3 6 System connecti...

Page 5: ...ay be required depending on the exact suspension mounting method used and the composition of the surface mounting material Tape Measure Screwdrivers including terminal driver Cable cutters crimpers an...

Page 6: ...serves as guidance for an ALIS installation within an intensive livestock rearing building Installers must also follow all applicable local electrical installation standards and wiring regulations whe...

Page 7: ...90 C min and 300V minimum 4 ALIS Tube Lamps 0 6m 0 9m 1 2m ALS0013 ALS0012 ALS0011 Suitable for wet location use Do not submerse IP66 5 ALIS Tube Coupler ALS00015 ALS00015 Suitable for wet location us...

Page 8: ...et local regulations 11 ALIS Bus End termination module and enclosure ETM ETM Must be housed within a suitably sealed enclosure IP66 see section 3 2 12 P2M Supply Connector P2M N A Not applicable CE O...

Page 9: ...tting at an early stage with either the house builder or architect to ensure that correct placement of the ALIS lamps within the house is possible If not a redesign of the lighting plan may be require...

Page 10: ...in a dry and dust free location acceptable to local wiring regulations If this is not possible then they must be housed within a suitably sealed enclosure as per local wiring regulations Due to the he...

Page 11: ...ch as a system partition ensure the ALIS Tube Coupler is moved to at least 15cm from this point to allow movement during washout Once positioned within the Coupler Housing bring the two lid sections t...

Page 12: ...g care not to damage the inner insulation Strip the ends of the ALIS Bus inner insulation to 8mm 0 3 inch of exposed conductor ensuring there is not any conductor loss Slide the orange connector cover...

Page 13: ...to damage the cable conductors Strip the ends of the ALIS Bus to 5mm 0 2 inch of exposed conductor ensuring there is not any conductor loss as shown below Twist the exposed copper cable strands Inser...

Page 14: ...tions should be observed If the length of the ALIS bus is less than 100m then the ALIS Bus must be terminated by means of a shorting connection to keep the ALIS Bus in resonance with the Hub When the...

Page 15: ...connection a Connect the ALIS Bus to the ALIS Dimmer as shown in the ALIS system components diagram page 5 b Connect the ALIS Dimmer to the ALIS Power Hub as shown in the ALIS system components diagr...

Page 16: ...IS Tube End Connector 4 Check the ALIS ETM termination Ensure the ALIS Bus cable is properly terminated 5 Ensure the ALIS Dimmer is properly connected to the ALIS Bus 6 Ensure the ALIS Dimmer is prope...

Page 17: ...s when supply returns to normal Flashing alternate red and green 2 flashes per second 50 duty cycle Power required exceeds power available Too much load fitted to the ALIS Bus Remove excess load The s...

Page 18: ...ge level is ascertained attempt a power up reset If this does not resolve the fault replace the power hub firstly carrying out the check list on page 8 5 ALIS Tube s flashing or flickering If this is...

Page 19: ...ise please ensure that all ends are sealed and lids correctly fitted to stop fauna rodent ingress 8 Installations should never use no more than the required length of ALIS Bus for each ALIS Power Hub...

Page 20: ...CE Max Power 500W Load Regulation 0 500W Output 0 95 1 45 1 95 O P Frequency ALIS Bus 49 kHz 50 kHz 51 kHz O P Current ALIS Bus 1 805A 1 9A 1 995A Start Time Turn On Time 460mS 480mS 500mS 475W outpu...

Page 21: ...shock are not safe to touch Circuit connected to any FELV control terminal shall be insulated for the LV voltage of the control gear and any terminals connected to the FELV circuit shall be protected...

Page 22: ...requirements 2009 EN 61000 3 2 Electromagnetic compatibility EMC Limits Limits for harmonic current emissions equipment input current 16 A per phase 2014 EN 61000 3 3 Electromagnetic compatibility EMC...

Page 23: ...rposes EMC immunity requirements 2009 EN 62493 Assessment of lighting equipment related to human exposure to electromagnetic fields 2015 EN 60598 1 Luminaires Part 1 General requirements and tests 201...

Page 24: ...Limited Roslin Innovation Centre The University of Edinburgh Easter Bush Campus Midlothian EH25 9RG United Kingdom Date of Installation Site Information Client Telephone inc country code Address Mobi...

Page 25: ...er Hub Serial Number ALIS Dimmer Serial Number Length of Cable Number of ALIS Tube Couplers Length of ALIS Tube per Coupler Dimming Facility ALIS Pot 0 10VDc Pictures Please send pictures of the follo...

Page 26: ...Page 26 of 28 Version 4 37 CE ALIS Tube Lamp 21 May 2019 Appendix Connection diagram...

Page 27: ...ST 18i3 96052 Bamberg 49 951 9324 0 ENG 49 951 9324 198 Mounting Instruction Screw Connection Internet www wieland gesis GST 18i3 July 2004 Low Profile electric com 2004 Wieland Electric GmbH Email in...

Page 28: ...Page 28 of 28 Version 4 37 CE ALIS Tube Lamp 21 May 2019...

Reviews: