Version 4.37 • CE • ALIS Tube Lamp
21 May 2019
7.
Specifications
7.1 ALIS Power Hub electrical
7.1.1 Input Specifications 230VAC (CE)
Parameter
Description
Minimum
Nominal
Maximum
VAC RMS
Input Supply
198
230
264
Frequency
AC RMS (Hz)
47
50
60
AC Start Up
Input Start Voltage (V)
178
180
182
AC Shut Down
Input Stop Voltage (V)
157
159
161
Current
Current RMS (A)
-
-
3.7
Insulation information:
Secondary output circuit of IPH500 is separated from its Primary input circuit by basic insulation; Control circuit
(SELV) is separated from Primary/Secondary circuits by reinforced insulation.
7.1.3 Output Specifications 230VAC (CE)
Parameter
Description
Minimum
Nominal
Maximum
Power Rating 230VAC (CE)
Max Power
-
-
500W
Load Regulation
0-500W Output
+/
- 0.95%
+/
- 1.45%
+/
- 1.95%
O/P Frequency
ALIS Bus
49 kHz
50 kHz
51 kHz
O/P Current
ALIS Bus
1.805A
1.9A
1.995A
Start Time
Turn On Time
460mS
480mS
500mS
475W output rating is only guaranteed for US mains supplies. The 475W rating must be
de-rated to maximum 425W for supplies below 100 VAC.Voltage
7.2 ALIS Power Hub environmental
Parameter
Description
Minimum
Nominal
Maximum
Operating Temperature
Thermal Environment
-
40˚C
25˚C
40˚C
Non-operating Temperature
Thermal Environment
-
40˚C
-
70˚C
Storage Temperature
ALIS Bus
-
40˚C
-
100˚C
Operating Humidity
Non-condensing
0%
-
85%
Non-operating Humidity
Non-condensing
0%
-
95%
Operating Altitude Maximum
3,000m or 10,000 feet
Non-operating Altitude Max
15,000m or 50,000 feet
Enclosure rating. Indoor use
IP10 or NEMA Type 1.
95% RH is achieved with a dry bulb temperature of 55˚C and a wet bulb temperature
of 54˚C.