greenfan® bipolar ionizer Model 1600-01
© 2022 greenfan® inc.
8
to connect 120/24VAC transformer wire to 120VAC fan motor wire and 120/24VAC
transformer common wire to 120VAC neutral wire shown in
Figure 11
.
b) Connect greenfan® bipolar ionizer blue wire to one wire of 24VAC transformer and
connect greenfan® bipolar ionizer black wire to other wire of 24VAC transformer.
c) Install wire nut to insulate unused white wire of greenfan® bipolar ionizer.
d) The greenfan® bipolar ionizer will draw less than 130mA and 1.6W or greater at
24VAC and 50/60 Hz when air purifier or fan is energized or turned on.
e) After completing all steps of the air purifier mechanical and electrical installation
proceed to air purifier verification of proper operation.
5.3 Air Purifier Verification of Proper Operation
a) Verify all wires are correctly connected and wire nuts are tight and secure.
b) Plug in air purifier, turn on power, turn on fan, and verify green LED lamp is
illuminated on greenfan® bipolar ionizer indicating ions are being generated.
c) Turn off the power and verify LED lamp is not illuminated.
d) Install cover panel of the air purifier.
Figure 11. Installation schematic with 120/24VAC transformer
6.0 VENTILATION FAN INSTALLATION
6.1 Ventilation Fan Mechanical Installation
a)
WARNING:
Disconnect electrical power from the ventilation fan before and during