BOARD ERROR
CODES
•
The Compressor´s failure light-indicator:
- The number of times the Compressor´s back red-light blinks, indi-
cates the type of failure:
-
1x
On hold;
-
5x
The Compressor´s temperature is too high, (possible causes:
lack of refrigerant or dirt);
-
6x
Bad connection with the Condenser Fan;
-
7x
Short circuit at the Condenser Fan, engine or connection line;
-
9x
Failure at the Condenser Fan´s controlling;
-
10x
Failure at the Condenser Fan;
-
11x
The Condenser Fan lost contact with the Compressor.
•
In case of any of the following incidents,
see for available solutions:
5.
INCIDENT
SOLUTION
The system is not
properly cooling
First, select the cooling mode and then select the
appropriate temperature and speed
Check for any obstruction at the air-in/outlet
Check for any dirt at the Condenser´s surface
Check for enough refrigerant quantity at the
system and if low/high tension are normal
Water on the
Evaporator Unit´s
surface
Formation of water drops at the air-outlet and on
the device´s surface is considered normal, due to
the humid environment
Tension failure on
the Evaporator
Unit
Check for low battery or if the power supply is
appropriate (DC 12 / 24V)
Check if low voltage protection is too high
Sensor failure on
the Evaporator
Unit
Check if the sensor´s temperature is correct
Check if the display shows a higher temperature
compared to normal room temperature, if so,
replace the sensor
Evaporator Unit
shows failure on
the Condenser
Unit
Lack of refrigerant
Check for normal high and low voltage
Check for dirt at the Condenser
Led failure
indicator