background image

4

Design & Selection

3 Selection of the Underfloor Coils

3.1 Calculation of Unit Load for Floor Heating

Empirical Values of Floor Heating Load Per Square Meter

House W/m

2

Dining Room

100~120

Mater Room

100~110

Guest Room

110~130

Study Room

90~110

Villa W/m

2

Dining Room

110~140

Mater Room

100~120

Guest Room

100~130

Study Room

100~120

Notes

Villas whose load is generally larger than the houses should take the value between the middle and the 

maximum empirical values listed above.

The top lever whose load is generally larger than the middle or bottom layer should take the maximum 

empirical value.

The guest room whose load is generally much large should take the value between the intermediate and 

the maximum empirical values listed above.

For those whose external walls or glass areas are large, it is recommended to take the load calculation.

The heating load for the bathroom is generally 500W/room.

3.2 Selection of Tube Spacing of the Underfloor Coils

Tube spacing of the underfloor coils which will directly affect heat dissipation of the floor depends on the 

tube material, indoor design temperature, supply water temperature and floor material.

Heat Dissipation of Commonly Used Coils

(Tube material: PE-X, Indoor temperature:18°C, Average water temperature:45°C)

Floor Material

Thermal Resistance

m

2

·K/W

Tube Spacing

mm

Heat Dissipation

W/m

2

Tube Spacing

mm

Heat Dissipation

W/m

2

Stone

0.02

200

147.0

150

159.8

Wood

0.075

200

111.2

150

117.8

The dissipated heat of the floor coil is larger than the load for the floor heating system; however the 

deviation cannot be larger than 10%.

3.3 Selection of Loop Quantity of Coils for Each Room
3.3.1Type of Underfloor Coils

When selecting underfloor coils, we should consider both their comfortability and heating capacity. The most 

commonly used coils are as shown below. 

Square-shaped Coil (Recommended)

  

U-shaped Coil

Length of coils are calculated as below:
Square-shaped coil: =L*W/tube spacing=area/tube spacing
U-shaped coil: =L-1+L*W/tube spacing=L-1+area/tube spacing
The reason why the square-shaped coils are recommended is because they can keep even temperature 

Summary of Contents for Versati II Series

Page 1: ...Change for life GREE ELECTRIC APPLIANCES INC OF ZHUHAI Air to water Heat Pump Monobloc Versati Design and Selection ...

Page 2: ...oils 4 4 Quantity and Location of the Water Traps and Collectors 5 4 1 Design Requirements on Loop Quantity for Circulation Water 5 4 2 Requirements on Installation of the Water Trap Collector 6 5 Section of FCU 7 5 1 FCU Type Selection 7 5 2 Matching of Capacity 7 6 Selection of the Water Tank 8 6 1 Specifications of the Water Tank 8 6 2 Volume Selection of the Water Tank 8 7 Examples for Model S...

Page 3: ... of thermostat and specification should be complied with installation of this manual The Bypass valve must be installed to secure enough water flow rate and should be installed at the collector CASE 2 Connecting Sanitary Water Tank Notes In this case three way valve should be installed and should be complied with installation of this manual Sanitary water tank should be equipped with internal elec...

Page 4: ...Hot water Notes Two way valve is very important to prevent dew condensation on the floor and Radiator while cooling mode 3 Way valve 1 is controlled by user while the pool pump is actived 3 Way valve 1 switches to pool loop while the pool pump is shuted down 3 Way valve 1 switches to under floor FCU loop 3 Way valve 2 is automatic controlled by monobloc unit while running water heating mode 3 Way ...

Page 5: ...ies and power inputs are based on the following conditions FCU or radiator a Cooling conditions b Heating conditions Indoor Water Temp 12 C 7 C Indoor Water Temp 40 C 45 C Outdoor Air Temp 35 C DB 24 C WB Outdoor Air Temp 7 C DB 6 C WB 2 3 Flowchart of Model Selection Calculate the load Preliminary selection of unit Finish unit selection Actual capacity Load Calculate the load YES NO 2 4 Design Pr...

Page 6: ...oils Tube spacing of the underfloor coils which will directly affect heat dissipation of the floor depends on the tube material indoor design temperature supply water temperature and floor material Heat Dissipation of Commonly Used Coils Tube material PE X Indoor temperature 18 C Average water temperature 45 C Floor Material Thermal Resistance m2 K W Tube Spacing mm Heat Dissipation W m2 Tube Spac...

Page 7: ...on Loop Quantity for Circulation Water 1 One water trap collector is allowed for at most eight loops When quantity of loops exceeds 12 then two traps collectors should be used or it will cause uneven water distribution 2 The maximum flow rate of the water trap collector should be less than 0 8m s 3 The inlet and outlet of each loop should be connected to the water trap collector and the inner diam...

Page 8: ...ap collector should be installed on the wall or inside the special box For housing constructions it is generally installed in the kitchen 2 The valve for the water trap collector should be installed horizontally and keep a distance of at least 300mm to the ground 3 The water supply valve should be installed upstream of the water trap collector and the return valve should be installed downstream of...

Page 9: ... would start stop frequently which is adverse for oil return When load of the FCU is too large the unit would always run under high frequency which is unhelpful for energy conservation Type Air Volume m3 h Cooling Capacity kW Heating Capacity kW Static Pressure Pa Appearance Wall mounted type 166 1020 2 1 5 4 3 15 8 5 Concealed ceiling type 213 2380 1 85 12 8 3 1 21 12 30 Floor ceiling type 213 20...

Page 10: ...ction of the Water Tank Selection of the water tank should consider the flow rate of the shower head duration of use per person and daily water consumption Volume of the Water Tank t design temperatuere t entering cold water temperatuere t water tank temperatuere set point t entering cold wa ter temperature consumption t design temperature generally it is 60 C t entering cold water temperature it ...

Page 11: ...0 18m3 h It can be see that the arranged piping system for the bathroom does not meet the technical requirement and must be used in common for the master room 7 2 4 Arrangement Design of the Underfloor System for the Master and Both Rooms According to the calculation results the total heat load for the master and bath rooms is 3196W heat dissipation per unit area is 82W m2 tube spacing of the heat...

Page 12: ...n Heat demand for a single layer 3196W Heat loss for a single layer 1016W Total heat load for a single layer 4212W Total heat load of the building 8424W Capacity of the main unit should be larger than 8424W so we can select GRS CQ10Pd NaC K ...

Page 13: ......

Reviews: