Design & Selection

6 Selection of the Water Tank

6.1 Specifications of the Water Tank

SXVD200LCJ/A-K 

220~240V-1Ph-50Hz
A single coil with the electric heater is integrated, used for floor heating system 

SXVD300LCJ/A-K 
SXVD200LCJ2/A-K 

220~240V-1Ph-50Hz
Dual coils with the electric heater are integrated, used for floor heating system and the solar system

SXVD300LCJ2/A-K 
SXVD200LCJ/A-M 

380~415V-3Ph-50Hz
A single coil with the electric heater is integrated, used for floor heating system

SXVD300LCJ/A-M 

SXVD200LCJ2/A-M 

380~415V-3Ph-50Hz
Dual coils with the electric heater are integrated, used for floor heating system and the solar system

6�2 Volume Selection of the Water Tank

6.2.1 Selection Based on Water Consumption Per Capita

Building Type

Unit

Daily Water Consumption (L) 

Water Temperature (°C)

House

Per person, Per day 

40~80

60

Villa

Per person, Per day

70~110

60

6�2�2 Selection Based on Sanitary Utensils 

Utensil Type

Daily Water 

Consumption (L) 

Water Temperature (°C)

Bathtub, Sprinkler system (with shower)

150

40

Bathtub, Sprinkler system (without shower)

125

40

Shower

70~100

37~40

Wash Basin

3

30

6� 2�3 Selection of the Water Tank

Selection of the water tank should consider the flow rate of the shower head, duration of use per person 

and daily water consumption.

Volume  of the Water Tank=

t(design temperatuere)-t(entering cold water temperatuere)

t(water tank temperatuere set point)-t(entering cold wa ter temperature)

•consumptio

n

t (design temperature): generally it is 60°C ;
t (entering cold water temperature): it differs for different regions.
t ( water tank temperature set point): it is the target heating temperature of the water tank
α: correction factor

Empirical Values for Volume Correction of the Water Tank

                        Duration of Use 

                           (min/Person)

Flow Rate of the Shower Head 
                    (L/min)

10

15

20

25

30

40

4

0.48

0.71

0.94

1.18

1.42

1.89

6

0.71

1.06

1.42

1.77

2.12

2.83

8

0.95

1.42

1.89

2.36

2.83

3.77

10

1.18

1.77

2.36

2.95

3.54

4.72

15

1.76

2.65

3.54

4.42

5.31

7.08

Empirical values are worked out under conditions of 80L consumption (per day per person), 8L/min flow rate 

of the shower head, and 10 minutes use duration per person.

7 Examples for Model Selection

7�1 General Introduction to the Example Project 

For a two-floor house, there is a master room and a both room for each floor and both of 

them require floor heating. Other rooms use the heat pump for heating in winter. The master 

room covers 28m

2

 and the both room covers 12m

2

.

Summary of Contents for Versati II Series

Page 1: ...Change for life GREE ELECTRIC APPLIANCES INC OF ZHUHAI Air to water Heat Pump Monobloc Versati Design and Selection ...

Page 2: ...oils 4 4 Quantity and Location of the Water Traps and Collectors 5 4 1 Design Requirements on Loop Quantity for Circulation Water 5 4 2 Requirements on Installation of the Water Trap Collector 6 5 Section of FCU 7 5 1 FCU Type Selection 7 5 2 Matching of Capacity 7 6 Selection of the Water Tank 8 6 1 Specifications of the Water Tank 8 6 2 Volume Selection of the Water Tank 8 7 Examples for Model S...

Page 3: ... of thermostat and specification should be complied with installation of this manual The Bypass valve must be installed to secure enough water flow rate and should be installed at the collector CASE 2 Connecting Sanitary Water Tank Notes In this case three way valve should be installed and should be complied with installation of this manual Sanitary water tank should be equipped with internal elec...

Page 4: ...Hot water Notes Two way valve is very important to prevent dew condensation on the floor and Radiator while cooling mode 3 Way valve 1 is controlled by user while the pool pump is actived 3 Way valve 1 switches to pool loop while the pool pump is shuted down 3 Way valve 1 switches to under floor FCU loop 3 Way valve 2 is automatic controlled by monobloc unit while running water heating mode 3 Way ...

Page 5: ...ies and power inputs are based on the following conditions FCU or radiator a Cooling conditions b Heating conditions Indoor Water Temp 12 C 7 C Indoor Water Temp 40 C 45 C Outdoor Air Temp 35 C DB 24 C WB Outdoor Air Temp 7 C DB 6 C WB 2 3 Flowchart of Model Selection Calculate the load Preliminary selection of unit Finish unit selection Actual capacity Load Calculate the load YES NO 2 4 Design Pr...

Page 6: ...oils Tube spacing of the underfloor coils which will directly affect heat dissipation of the floor depends on the tube material indoor design temperature supply water temperature and floor material Heat Dissipation of Commonly Used Coils Tube material PE X Indoor temperature 18 C Average water temperature 45 C Floor Material Thermal Resistance m2 K W Tube Spacing mm Heat Dissipation W m2 Tube Spac...

Page 7: ...on Loop Quantity for Circulation Water 1 One water trap collector is allowed for at most eight loops When quantity of loops exceeds 12 then two traps collectors should be used or it will cause uneven water distribution 2 The maximum flow rate of the water trap collector should be less than 0 8m s 3 The inlet and outlet of each loop should be connected to the water trap collector and the inner diam...

Page 8: ...ap collector should be installed on the wall or inside the special box For housing constructions it is generally installed in the kitchen 2 The valve for the water trap collector should be installed horizontally and keep a distance of at least 300mm to the ground 3 The water supply valve should be installed upstream of the water trap collector and the return valve should be installed downstream of...

Page 9: ... would start stop frequently which is adverse for oil return When load of the FCU is too large the unit would always run under high frequency which is unhelpful for energy conservation Type Air Volume m3 h Cooling Capacity kW Heating Capacity kW Static Pressure Pa Appearance Wall mounted type 166 1020 2 1 5 4 3 15 8 5 Concealed ceiling type 213 2380 1 85 12 8 3 1 21 12 30 Floor ceiling type 213 20...

Page 10: ...ction of the Water Tank Selection of the water tank should consider the flow rate of the shower head duration of use per person and daily water consumption Volume of the Water Tank t design temperatuere t entering cold water temperatuere t water tank temperatuere set point t entering cold wa ter temperature consumption t design temperature generally it is 60 C t entering cold water temperature it ...

Page 11: ...0 18m3 h It can be see that the arranged piping system for the bathroom does not meet the technical requirement and must be used in common for the master room 7 2 4 Arrangement Design of the Underfloor System for the Master and Both Rooms According to the calculation results the total heat load for the master and bath rooms is 3196W heat dissipation per unit area is 82W m2 tube spacing of the heat...

Page 12: ...n Heat demand for a single layer 3196W Heat loss for a single layer 1016W Total heat load for a single layer 4212W Total heat load of the building 8424W Capacity of the main unit should be larger than 8424W so we can select GRS CQ10Pd NaC K ...

Page 13: ......

Reviews: