A/A DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
25
2 MAIN LOGIC
2.1 Cooling
Acc.to control
logic
Cooling mode
3min
Firstly switch off to step 0 and
then switch off step 60
150s atfer the compressor is stoped
180steps
Send out switch-off command
Acc.to control
logic
capacity demand
>0
send out cooling
command
Indoor fan
(cooling)
4-way valve
3s
Xsteps
30s
ON
ON
ON
OFF
OFF
OFF
Outdoor fan
EXV
compressor
OFF
60s
60s
After the cooling command is sent out, the indoor fan will run at high speed for 5 seconds before it is put into
operation according to the setting. Then, it is started to calculate the system load demand value. If the load is 0, the
other loads except the indoor fan will not be put into operation (The water pump will run according to the pump
control logic behind). If the load is >0, the EXV will be firstly opened to step X; then the indoor fan is started. After 30
seconds, the compressor is started at initial frequency 40Hz and will be maintained for 3 minutes. After that, the
compressor, EXV and outdoor fan will adjust according to logic.
Summary of Contents for U-MATCH GFH09K3CI
Page 4: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 1 PRODUCT...
Page 25: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 22 CONTROL...
Page 27: ...A A DC INVERTER U MATCH AIR CONDITIONERS CONTROL 24 1 2 Heating Operation...
Page 62: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 59 5 3 7 Dimensions...
Page 63: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 60 INSTALLATION...
Page 102: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 99 MAINTENANCE...
Page 121: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 118 IPM module protection...
Page 122: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 119 DC busbar overvoltage protection...
Page 123: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 120 DC busbar undervoltage protection...
Page 124: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 121 Abnormal noise from PFC inductor...
Page 125: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 122 Radiator overheat protection...
Page 126: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 123 Tripping...
Page 130: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 127 Tripping...
Page 138: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 135 Model GUHD48NM3CO Model GUHD60NM3CO...
Page 183: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 180 7 8 A B C 9 A B 0 5 0 1kgf c C 10 A B...
Page 195: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 192 4 5 6...
Page 197: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 194 5 6 A B 0 5 0 1kgf c C 7 8 A B C...
Page 227: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 224 Model GUHD24NK3CO Exploded View...
Page 247: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 244 Model GKH18K3CI Exploded View...
Page 264: ...261 JF00300705...