A/A DC INVERTER U-MATCH AIR CONDITIONERS PRODUCT
18
Continue
d:4
Indoor unit
GTH60K3CI
Model
Outdoor unit
GUHD60NM3CO
kW 16
Cooling
Btu/h 54500
kW 17.5
Nominal Capacity
Heating
Btu
/
h
59700
Cooling kW
5
Power Input
Heating kW
4.86
EER/COP
W
/
W
3.20/3.60
Indoor Unit
GTH60K3CI
Power Supply
-
220-240V-50Hz-1Ph
Heat Exchange
-
Cross Fin Coil
Type
-
Centrifugal fan
Drive
-
Direct
Motor Output
kW
0.25×1
Fan
Air Flow
m3
/
h
2300
Sound Pressure Level(H/M/L)
dB(A)
58/55/52
Air Filter
-
Standard washable synthetic
Drain Piping
mm
Φ
17×1.75
Dimensions (W×H×D)
1700×245×700
(Outline/Package)
mm
1825×330×825
Weight(Net/Gross) kg
65/73
Outdoor Unit
GUHD60NM3CO
Power Supply
-
380-4150V-50Hz-3Ph
Heat Exchange
-
Cross Fin Coil
Type
-
Axial fan
Motor Output
kW
0.082×2
Fan
Fan Motor Speed
rpm
800±20
Type
-
ROTARY
Compressor
Power Input
W
4220
Type
-
R410A
Control
-
Electronic Expansion Valve
Refrigerant
Charge kg
5.5
Dimensions (W×H×D)
1085×1365×427
(Outline/Package)
mm
1140×1390×475
Weight(Net/Gross) kg 127/133
Liquid mm
Φ
3/8"
Gas mm
Φ
3/4"
Piping Connections
Max. Length
m
50
Max. Height Difference
m
30
Summary of Contents for U-MATCH GFH09K3CI
Page 4: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 1 PRODUCT...
Page 25: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 22 CONTROL...
Page 27: ...A A DC INVERTER U MATCH AIR CONDITIONERS CONTROL 24 1 2 Heating Operation...
Page 62: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 59 5 3 7 Dimensions...
Page 63: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 60 INSTALLATION...
Page 102: ...GREE COMMERCIAL AIR CONDITION A A DC INVERTER U MATCH AIR CONDITIONERS 99 MAINTENANCE...
Page 121: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 118 IPM module protection...
Page 122: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 119 DC busbar overvoltage protection...
Page 123: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 120 DC busbar undervoltage protection...
Page 124: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 121 Abnormal noise from PFC inductor...
Page 125: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 122 Radiator overheat protection...
Page 126: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 123 Tripping...
Page 130: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 127 Tripping...
Page 138: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 135 Model GUHD48NM3CO Model GUHD60NM3CO...
Page 183: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 180 7 8 A B C 9 A B 0 5 0 1kgf c C 10 A B...
Page 195: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 192 4 5 6...
Page 197: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 194 5 6 A B 0 5 0 1kgf c C 7 8 A B C...
Page 227: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 224 Model GUHD24NK3CO Exploded View...
Page 247: ...A A DC INVERTER U MATCH AIR CONDITIONERS MAINTENANCE 244 Model GKH18K3CI Exploded View...
Page 264: ...261 JF00300705...