INSTALLATION SITE INSTRUCTIONS
Outdoor Unit
9
Do not install the unit at a location where the distance exceeds the maximum pipe length indicated
in the table. The maximum length of the connection pipe is listed in the System Requirements section.
CAUTION
WARNING
Outdoor Unit
Minimum Distances
in (mm)
A
40 (1000)
B
20 (500)
C
20 (500)
D
80 (2000)
E
20 (500)
Air inlet
Air outlet
A
B
C
D
E
The unit should be installed level on a pad that can support twice the weight of the unit.
If the outdoor unit will be exposed to strong winds, it must be adequately secured.
1. Install the outdoor unit at a location that is capable of withstanding twice the weight of the unit.
2. Install the outdoor unit where it is convenient to connect refrigerant lines to the indoor unit.
3. I nstall the outdoor unit where the condensate water can be drained unobstructed during the
heating mode to a safe location.
4. Do not locate the unit where the noise may be objectionable to neighbors.
5. Provide the space shown below, so that the air flow is not blocked and future service and
maintenance can be performed.
Select a site that allows the following:
Minimum Outdoor Clearances