Installation and Maintenance

Service Manual

Appendix:

1.Standard length of connection pipe
● 5m, 7.5m, 8m.
2.Min. length of connection pipe is 3m.
3.Max. length of connection pipe and max. high difference.

More details please refer to the specifications.)

4.The additional refrigerant oil and refrigerant charging required after prolonging connection pipe
● After the length of connection pipe is prolonged for 10m at the basis of standard length, you should add 5ml of refrigerant oil 
for each additional 5m of connection pipe.
● The calculation method of additional refrigerant charging amount (on the basis of liquid pipe):
● Basing on the length of standard pipe, add refrigerant according to the requirement as shown in the table. The additional 
refrigerant charging amount per meter is different according to the diameter of liquid pipe. See the following sheet.
● Additional refrigerant charging amount = prolonged length of liquid pipe X additional refrigerant charging amount per meter 

Appendix 1: Reference Sheet of Celsius and Fahrenheit

Appendix 2: Configuration of Connection Pipe

Set temperature

Conversion formula for Fahrenheit degree and Celsius degree: Tf=Tcx1

.

8+32

Ambient temperature

 Fahrenheit 

display 

temperature

(℉)

Fahrenheit

(℉)

Celsius

(℃)

 Fahrenheit 

display 

temperature

(℉)

Fahrenheit

(℉)

Celsius

(℃)

 Fahrenheit 

display 

temperature

(℉)

Fahrenheit

(℉)

Celsius

(℃)

32/33

32

0

55/56

55.4

13

79/80

78.8

26

34/35

33.8

1

57/58

57.2

14

81

80.6

27

36

35.6

2

59/60

59

15

82/83

82.4

28

37/38

37.4

3

61/62

60.8

16

84/85

84.2

29

39/40

39.2

4

63

62.6

17

86/87

86

30

41/42

41

5

64/65

64.4

18

88/89

87.8

31

43/44

42.8

6

66/67

66.2

19

90

89.6

32

45

44.6

7

68/69

68

20

91/92

91.4

33

46/47

46.4

8

70/71

69.8

21

93/94

93.2

34

48/49

48.2

9

72

71.6

22

95/96

95

35

50/51

50

10

73/74

73.4

23

97/98

96.8

36

52/53

51.8

11

75/76

75.2

24

99

98.6

37

54

53.6

12

77/78

77

25

 Fahrenheit 

display 

temperature

(℉)

Fahrenheit

(℉)

Celsius

(℃)

 Fahrenheit 

display 

temperature

(℉)

Fahrenheit

(℉)

Celsius

(℃)

 Fahrenheit 

display 

temperature

(℉)

Fahrenheit

(℉)

Celsius

(℃)

61

60.8

16

69/70

69.8

21

78/79

78.8

26

62/63

62.6

17

71/72

71.6

22

80/81

80.6

27

64/65

64.4

18

73/74

73.4

23

82/83

82.4

28

66/67

66.2

19

75/76

75.2

24

84/85

84.2

29

68

68

20

77

77

25

86

86

30

Additional refrigerant charging amount for R22, R407C, R410A and R134a

Diameter of connection pipe

Outdoor unit throttle

Liquid pipe(mm)

Gas pipe(mm)

Cooling only(g/m)

Cooling and heating(g/m)

Ф6

Ф9.5 or Ф12

15

20

Ф6 or Ф9.5

Ф16 or Ф19

15

50

Ф12

Ф19 or Ф22.2

30

120

Ф16

Ф25.4 or Ф31.8

60

120

Ф19

/

250

250

Ф22.2

/

350

350

Summary of Contents for GWH28AAE-K3NNA1A/I

Page 1: ...GREE ELECTRIC APPLIANCES INC OF ZHUHAI Change for Life Service Manual Model GWH28ACE K3NNA1A Refrigerant R410A ...

Page 2: ...rol 11 6 1 Remote Controller Introduction 11 6 2 Brief Description of Modes and Functions 14 Part Ⅱ Installation and Maintenance 19 7 Notes for Installation and Maintenance 19 8 Installation 22 8 1 Installation Dimension Diagram 22 8 2 Installation Parts checking 24 8 3 Selection of Installation Location 24 8 4 Requirements for electric connection 24 8 5 Installation of Indoor Unit 24 8 6 Installa...

Page 3: ...1 Removal Procedure 49 11 1 Removal Procedure of Indoor Unit 49 11 2 Removal Procedure of Outdoor Unit 54 Appendix 59 Appendix 1 Reference Sheet of Celsius and Fahrenheit 59 Appendix 2 Configuration of Connection Pipe 59 Appendix 3 Pipe expanding method 60 Appendix 4 List of Resistance for Temperature Sensor 61 ...

Page 4: ...1 Technical Information Service Manual 1 Summary Part Ⅰ Technical Information Indoor Unit GWH28AAE K3NNA1A I Outdoor Unit GWH28AAE K3NNA1A O Remote Controller YAW1F ...

Page 5: ...70 Indoor Unit Fan Type GWH28ACE K3NNA1A I Product Code of Indoor Unit CA497N00800 CA497N00802 Fan Type Cross flow Diameter Length DXL mm Ф108X830 Fan Motor Cooling Speed SH H M L SL r min 1330 1200 1000 900 Fan Motor Heating Speed SH H M L SL r min 1330 1200 1000 900 Output of Fan Motor W 35 Fan Motor RLA A 0 35 Fan Motor Capacitor μF 3 Evaporator Form Aluminum Fin copper Tube Pipe Diameter mm Ф7...

Page 6: ...Fan Motor Speed rpm 850 Output of Fan Motor W 85 Fan Motor RLA A 0 8 Fan Motor Capacitor μF 4 5 Air Flow Volume of Outdoor Unit m3 h 1800 Fan Type Axial flow Fan Diameter mm Ф520 Defrosting Method Automatic Defrosting Climate Type T1 Isolation I Moisture Protection IPX4 Permissible Excessive Operating Pressure for the Discharge Side MPa 4 3 Permissible Excessive Operating Pressure for the Suction ...

Page 7: ...pe connecting indoor and outdoor unit Inlet and outlet pipe temperature of heat exchanger Fan speed of indoor unit Fan speed of outdoor unit Indoor Outdoor P MPa T1 C T2 C 27 19 35 24 28K 0 9 1 1 in 6 8 out 10 12 in 75 85 out 37 43 Super High High Rated heating condition C DB WB Model Pressure of gas pipe connecting indoor and outdoor unit Inlet and outlet pipe temperature of heat exchanger Fan sp...

Page 8: ...5 Technical Information Service Manual 3 Outline Dimension Diagram 3 1 Indoor Unit Unit mm Unit mm 3 2 Outdoor Unit 364 560 700 396 340 965 897 1122 247 329 79 154 43 207 685 230 Φ70 Φ70 43 ...

Page 9: ...t Outdoor unit COOLING HEATING 4 Way valve COOLING Discharge Suction Heat exchanger evaporator Heat exchanger condenser Valve Valve Valve Liquid pipe side Gas pipe side Accumlator Compressor Strainer Strainer Strainer Capillary Capillary Connection pipe specification Liquid pipe 1 4 6mm Gas pipe 5 8 16mm ...

Page 10: ...BU Blue Grounding wire YEGN Yellow Green BK Black VT Violet OG Orange Note Jumper cap is used to determine fan speed and the swing angle of horizontal lover for this model 6363247703 7 7 1 5 8 2 3 60 1 5 725 5 1 0 1 7 1 83 2 1 1 1 20 287 63 63 3 287 225 81 7 0 1 7 1 8 3 9 325 725 1 8 3 803 3 7 50 1 2 02725 6 1 8 6 1 211 7 1 63 2 5 5 9 5 1 35 17 5 8 7 2 5 63 67 33 1 78 5220 57 57 6 1625 7 03 6 1625...

Page 11: ...ed with the unit 7 127 0RWRU JURXQG RQO DSSOLHV WR WKH LURQ VKHOO PRWRU 3 35 17 5 8 7 2 5 5 1 8 1 8 1 3 8 1 203 6 5 0 1 1 1 1 225 81 7 7 0 32 5 5 20 11 5 1 203 3 2 1 8 1 0 1 1 8 8 1 203 217 725 1 8 1 3 8 3 02725 3 3 3 1 1 2875220 33 1 8 33 97 9 9 1 97 9 9 3 28778 57 7 03 287 78 6 1625 75 16 250 5 7 75 287 75 1 7 50 1 2 3 3 35 6685 6 7 5 5 6 6725 6 1 ė Ė ...

Page 12: ...cation wire 4 Fuse 5 Indoor fan driven capacitor 6 Neutral wire interface of cold plasma 7 Neutral wire interface of power supply 8 Interface of indoor fan 9 Live wire interface of cold plasma 10 Interface of up down swing motor 11 Interface of indoor fan feedback 12 Jumper cap 13 Interface of left right motor 14 Temperature sensor interface 2 3 4 5 6 7 8 9 10 11 12 13 14 1 ...

Page 13: ...nsformer 6 Terminal for high pressure protection 7 Terminal for low pressure protection 8 Terminal for outdoor ambient temp sensor 9 Terminal for outdoor pipe temp sensor 10 Terminal for communication wire 11 Protective tube 12 Terminal for neutral wire 13 Terminal for live wire 14 Wiring terminal of outdoor discharge temperature sensor Only for the models with this function 15 Current mutual indu...

Page 14: ...not Please refer to the actual models This is a general use remote controller it could be used for the air conditioners with multifunction For some function which the model doesn t have if press the corresponding button on the remote controller that the unit will keep the original running status After putting through the power the air conditioner will give out a sound Operation indictor is ON red ...

Page 15: ... OFF status press this button to set timer ON Press this button to start I FEEL function and will be displayed on the remotecontroller After this function is set the remote controller will send the detectedambient temperature to the controller and the unit will automatically adjust theindoor temperature according to the detected temperature Press this button againto close I FEEL function and will ...

Page 16: ...unit Press this button again to turn off the unit Press MODE and TURBO button simultaneously to and TURBO buttons simultaneously for 10s remote controller will send WIFI reset code and then the WIFI function will be turned on WIFI function is defaulted ON after energization of the remote controller turn on or turn off WIFI function When WIFI function is turned on the icon will be displayed on remo...

Page 17: ...temperature is 20 Cooling and heating unit When Tamb 19 Tcompensation unit will be in heating mode Tpreset 20 Cooling only unit When Tamb 22 or 72 unit will be in fan mode Tpreset 25 For cooling and heating unit under condition that 19 Tcompensation Tamb 26 For cooling only unit under condition that 22 Tamb 26 when unit is initially turned on in auto mode it will operate according to auto fan mode...

Page 18: ...nated For some models they can only be restated up after re energized Please refer to maintenance part for display information and disposal method for details 3 Drying mode Operation condition and process for drying mode When Tamb Tset 2 the system starts drying and cooling In this case the compressor and the ODU fan motor operate and the IDU fan motor operates at low speed When Tset 2 Tamb Tset 2...

Page 19: ...tube is resumed normally the ODU fan motor resumes operation Noise silencing protection When turning off the unit or during mode switchover the 4 way valve is closed In order to decrease noise the 4 way valve will delay 2mins to be closed Overcurrent protection this protection function is not available for those models whose cooling capacity 12000Btu h During operation process if controller detect...

Page 20: ...ation of turbo function the system operates at the maximum fan speed 5 Dry function Dry function can be set under cooling and drying modes During operation of drying function the fan will stop operation after operating for a period of time when turning off the unit 6 Auto fan speed control Auto fan speed control can be set under cooling heating and fan mode During operation of auto fan speed contr...

Page 21: ...ilure when turning off the unit Memory content OFF status mode up down swing light set temperature set fan speed general timer Fahrenheit Celsius General timer can be memorized Time of timer is calculated again from energization Clock timer can t be memorized 4 Special function 1 Health function for the model with health function During operation of the IDU fan motor press health button on the rem...

Page 22: ...unit adequately grounded The grounding wire can t be used for other purposes 6 Must apply protective accessories such as protective boards cable cross loop and wire clip 7 The live wire neutral wire and grounding wire of power supply must be corresponding to the live wire neutral wire and grounding wire of the air conditioner 8 The power cord and power connection wires can t be pressed by hard obj...

Page 23: ...ssure rise or compressor rupture resulting in injury 4 During refrigerant recovery make sure that liquid valve and gas valve are fully closed and power is disconnected before detaching the connection pipe If compressor starts running when stop valve is open and connection pipe is not yet connected air will be sucked in and cause pressure rise or compressor rupture resulting in injury 5 When instal...

Page 24: ...ing tape 4 Electroprobe 7 Electronic leakage detector 10 Pipe pliers pipe cutter 2 Screw driver 5 Universal meter 8 Vacuum pump 11 Pipe expander pipe bender 3 Impact drill drill head electric drill 6 Torque wrench open end wrench inner hexagon spanner 9 Pressure meter 12 Soldering appliance refrigerant container ...

Page 25: ...ipe Space to the wall Space to the obstruction Space to the obstruction Space to the obstruction At least 50cm At least 200cm At least 30cm At least 30cm At least 50cm Space to the ceiling Space to the wall At least 15cm At least 15cm At least 15cm At least 250cm Space to the wall o o l f e h t o t e c a p S A t l e a s t 3 0 0 c m ...

Page 26: ...oor unit Make the bound pipes pass through the wall hole and then connect outdoor unit Neaten the pipes Vacuum pumping and leakage detection Check after installation and test operation Finish installation Note this flow is only for reference please find the more detailed installation steps in this section Select outdoor unit installation location Install the support of outdoor unit select it accor...

Page 27: ...unding with specialized grounding device by a professional Please make sure it is always grounded effectively otherwise it may cause electric shock 2 The yellow green wire in air conditioner is grounding wire which can t be used for other purposes 3 The grounding resistance should comply with national electric safety regulations 4 The appliance must be positioned so that the plug is accessible 5 A...

Page 28: ...e wall slightly downward to the outdoor side with the gradient of 5 10 As show in Fig 2 Note Left Wall Φ70mm Right Mark in the middle of it Level meter Rear piping hole Wall Space to the wall above 150mm Space to the wall above 150mm Φ70mm Rear piping hole Insulating pipe Torque wrench Open end wrench Indoor pipe Pipe Union nut Union nut Pipe joint Pipe Hex nut diameter Tightening torque N m Φ6 15...

Page 29: ...ly at the end 2 Make the power connection wire go through the cable cross hole at the back of indoor unit and then pull it out from the front side As show in Fig 12 3 Remove the wire clip connect the power connection wire to the wiring terminal according to the color tighten the screw and then fix the power connection wire with wire clip As show in Fig 13 Note Note Fig 11 Fig 12 Fig 13 Fig 14 Fig ...

Page 30: ...ver As show in Fig 21 2 Remove the screw cap of valve and aim the pipe joint at the bellmouth of pipe As show in Fig 22 Fig 18 Fig 19 Fig 20 Fig 21 Fig 22 1 After tightening the screw pull the power cord slightly to check if it is firm 2 Never cut the power connection wire to prolong or shorten the distance Note 5 Connect Outdoor Electric Wire 1 Remove the wire clip connect the power connection wi...

Page 31: ...valve and the nut of refrigerant charging vent 2 Connect the charging hose of piezometer to the refrigerant charging vent of gas valve and then connect the other charging hose to the vacuum pump 3 Open the piezometer completely and operate for 10 15min to check if the pressure of piezometer remains in 0 1MPa 4 Close the vacuum pump and maintain this status for 1 2min to check if the pressure of pi...

Page 32: ...erminal of PG motor is not connected tightly 3 Fan blade rotates unsmoothly 4 Malfunction of motor 5 Main board is broken 4 Malfunction protection of jumper cap C5 Operation of remote controller or control panel is available but the unit won t act 1 There s not jumper cap on the main board 2 Jumper cap is not inserted properly and tightly 3 Jumper cap is damaged 4 Controller is damaged 5 Zero cros...

Page 33: ...short circuited 9 Filter and heat exchange fins of indoor outdoor units are blocked 10 The system pipeline is blocked 11 The gas valve and liquid valve for outdoor unit are not completely opened 12 The OVC input is at high level 10 Low pressure protection of compressor E3 The complete unit stops 1 The main board and display panel are not connected well 2 The LPP terminal on the main board is not c...

Page 34: ... not working Abnormal fan speed fan speed is too low or the fan doesn t run 3 Compressor operates normally or not Is there any abnormal noise or oil leak Casing is too hot 4 System is blocked inside Dirt blockage Ice blockage Oil blockage Y valve is not fully open 5 Main board temperature sensor detects wrongly 15 Overload protection for compressor H3 The entire unit stops 1 Outdoor and indoor hea...

Page 35: ...en Malfunction diagnosis process Is the wiring terminal between the temperature sensor and the controller loosened or poorly contacted Start Insert the temperature sensor tightly Yes Yes Yes Yes Yes Yes No No No No No No Is malfunction eliminated Is malfunction eliminated Is malfunction eliminated Replace it with a temperature sensor with the same model Make the parts upright Is there short circui...

Page 36: ...e connection of PG motor control terminal is firm Turn on the unit again measure whether the output voltage on control terminal for PG motor is more than 50V within 1 min after the louvers are opened Tighten the screw reassemble the blade motor and shaft bearing rubber base sub assy to make sure there is no foreign object between them Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No No No No No No No No...

Page 37: ...the mainboard is defined abnormal Malfunction diagnosis process Start Is there jumper cap on the mainboard Is the jumper cap inserted correctly and tightly Replace the jumper cap with the same model Appearance of the jumper cap Assemble the jumper cap with the same model Insert the jumper cap tightly Is malfunction eliminated Is malfunction eliminated Is malfunction eliminated Replace the mainboar...

Page 38: ...harges slowly The zero cross detectioncircuit of the mainboard is defined abnormal Malfunction diagnosis process Turn power off for 1minute the turn back on The unit returns to normal Conclusion U8 is displayed due to power off on while the capacitor discharges slowly U8 is still displayed The zero cross detection circuit of the mainboard is defined abnormal Replace the mainboard with the same mod...

Page 39: ...e OVC terminal on the main board with the high pressure switch on the complete unit well no Malfunction is eliminated no If the wire of high pressure switch is loosened please connect the wires according to the circuit diagram If the high pressure switch is broken or poorly contacted please replace it yes Malfunction is eliminated no Adjust the volume of refrigerant according to the requirement of...

Page 40: ...able contact Is the malfunction eliminated Is the higher than the acting value of the low pressure switch Add refrigerant Is the malfunction eliminated Test when denergized a closed circuit between the two terminals led out from Replace the low pressure switch Is the malfunction eliminated The controller is defined abnormal replace it No Yes No No Yes No No Yes End No Yes Yes Yes Yes ...

Page 41: ...g mode System is abnormal but resist ancev alue of discharge sensor for compressor temperature is abno rmal Replace con trol panel End Check the system Eliminate the block age inside the system Check wiring and fan capacitor replace motor Check the unit to let air come in and come out smoothly Replace temperature sensor Problem is solved Problem is solved Problem is solved Problem is solved no no ...

Page 42: ... compressor running abnormally Is there abnormal sound or oil leakage is the temperature of the shell too high etc no no no no yes no no Replace the control panel End Normal fluctuation is within 10 of the rated voltage on the nameplate yes Malfunction is eliminated no Adjust the supply voltage to maintain it within normal range yes Malfunction is eliminated no Clean the indoor and outdoor heat ex...

Page 43: ...40 Installation and Maintenance Service Manual 9 Communication malfunction E6 Poor contact any line may lead to communication malfunction ...

Page 44: ... motor is not working Abnormal fan speed fan speed is too low or the fan doesn t run Malfunction is eliminated Malfunction is eliminated Malfunction is eliminated End Compressor doesn t work normally Strange noise or leakage occurs Make compressor run normally Remove blockage in the system System is blocked inside dirt block ice block oil block Y valve not fully open Temperature sensor of main boa...

Page 45: ...ed Malfunction is eliminated Malfunction is eliminated Malfunction is eliminated Malfunction is eliminated Check motor and re install the motor to make it run normally Make compressor run normally Remove blockage in the system Replace high pressure switch Check the leaking status of refrigerant and charge refrigerant Fan motor is not working Abnormal fan speed fan speed is too low or the fan doesn...

Page 46: ...d for details Malfunction of compressor Compressor can t operate Refer to point 5 of maintenance method for details 9 3 Maintenance Method for Normal Malfunction 1 Air Conditioner Can t be Started Up 2 Poor Cooling Heating for Air Conditioner 3 Horizontal Louver Can t Swing Possible Causes Discriminating Method Air conditioner Status Troubleshooting No power supply or poor connection for power plu...

Page 47: ...in pipe Replace drain pipe Wrapping is not tight Water leaking from the pipe connection place of indoor unit Wrap it again and bundle it tightly 5 Compressor Can t Operate Possible causes Discriminating method air conditioner status Troubleshooting Wrong wire connection or poor connection Check the wiring status according to circuit diagram Connect wires according to wiring diagram to make sure al...

Page 48: ...al 10 Exploded View and Parts List 10 1 Indoor Unit The component is only for reference please refer to the actual product 42 41 43 44 15 16 18 17 31 33 35 36 37 39 40 1 2 3 4 5 6 7 8 9 10 11 12 13 14 19 20 21 22 24 23 26 25 27 28 29 34 30 32 38 ...

Page 49: ...1 20 Fan Motor 15012145 15012145 1 21 Connecting pipe clamp 26112514 26112514 1 22 Drainage Hose 0523001405 0523001405 1 23 Stepping Motor 1521240210 1521240210 1 24 Crank 73012005 73012005 1 25 Guide Louver 200004000048 20000200003001B 1 26 Axile Bush 10542036 10542036 2 27 Right Side Plate 200086000011 20008600001101P01 1 28 Decorative Strip Right 230001000065D 230001000065D 1 29 Shield Cover of...

Page 50: ... and Maintenance Service Manual 10 2 Outdoor Unit The component is only for reference please refer to the actual product 1 2 3 4 6 7 8 9 11 10 5 13 15 17 18 20 14 16 25 26 27 23 28 22 29 24 30 31 12 21 32 19 33 34 35 ...

Page 51: ...1 12 Valve Cover 22245002 1 13 Handle 26233053 1 14 Condenser Assy 011002000339 1 15 4 Way Valve Assy 030152000221 1 16 Magnet Coil 4300040047 1 17 Clapboard 01245200018 1 18 Motor Support Sub Assy 01705036 1 19 Rear Grill 01473061 1 20 Coping 012049000007P 1 21 Electric Box Cover 01425200102 1 22 Fan Motor 1501506310 1 23 Left Side Plate 01305093P 1 24 Handle 26233053 1 25 Capacitor CBB61S 330107...

Page 52: ...ve horizontal louver a b Panel Clasps Left filter and right filer Axile bush Open the panel Loosen the clasp shown in the fig and then pull the left filter and right filer outwards to remove them Push out the axile bush on horizontal louver Bend the horizontal louver with hand and then separate the horizontal louver from the crankshaft of step motor to remove it Horizontal louver Location of step ...

Page 53: ...WIFI Electric box cover 2 Screw Detecting plate WiFi Panel Display Screws Front panel Panel rotation Groove 3 Remove panel 4 Remove electric box cover 2 and detecting plate WIFI 5 Remove front case sub assy Front case sub assy Front case sub assy Middle clasp Left clasp Right clasp Screw caps Screws Screws Remove the screws fixing front case Note 1 Open the screw caps before removing the screws ar...

Page 54: ...the power cord Remove the wiring terminal of power cord Lift up the main board and take it off electric box Cold plasma generator Grounding screw Indoor tube temperature sensor Electric box assy Main board Wiring terminal of motor Wiring terminal of stepping motor Screw Screw Wire clip Circlip Holder Connector Soft sheath Power cord Wire binder Step motor Screws clasps Instruction Some wiring term...

Page 55: ...emove the connection pipe clamp First remove the left side of evaporator from the groove of bottom shell and then remove the right side from the clasp on the bottom shell Remove 3 screws fixing evaporator assy Adjust the position of connection pipe on evaporator slightly and then lift the evaporator upwards to remove it connection pipe clamp Evaporator assy Clasp Groove Clasp Rear Case assy ...

Page 56: ...blade and motor lift the motor and cross flow blade upwards to remove them 8 Remove motor and cross flow blade Motor clasp screws Remove 3 screws fixing motor clamp and then remove the motor clamp a Clasps Clasps Loosen the connection clasps between vertical louver and bottom case to remove vertical louver 9 Remove vertical louver ...

Page 57: ... big handle Remove the screw connecting the valve cover and right side plate and then remove the valve cover a 1 Remove big handle valve cover and top cover Remove the screws connecting the top cover with cabinet right side plate and left side plate lift the top cover upwards to remove it b handle right side plate screw valve cover top cover screw screw screw cabinet right side plate ...

Page 58: ...on plate and chassis lift the outer case upwards loosen the clasps of outer case with right side plate and left side plate and then remove the outer case a b 2 Remove grille and cabinet screw grille screw cabinet Remove the screws connecting the right side plate with electric box assy valve support chassis and condenser side plate and then remove the right side plate 3 Remove right side plate righ...

Page 59: ...e stopper to remove the motor support motor support chassis stopper 5 Remove motor support sub assy and motor Remove the 6 screws fixing the motor and then remove the motor screw screw motor 6 Remove electric box assy electric box assy Remove the screws fixing electric box assy pull out each wiring terminal lift the electric box assy upwards to remove it Note When pulling out the wiring terminal p...

Page 60: ...gas valve Unsolder the welding joint connecting the valve with capillary and condenser unsolder the welding joint connecting the gas valve and air return pipe remove the 2 bolts fixing the gas valve to remove the gas valve Unsolder the welding joint connecting the liquid valve and Y shaped pipe remove the 2 bolts fixing the liquid valve to remove the liquid valve Note Before unsoldering the weldin...

Page 61: ...4 way valve assy with capillary sub assy compressor and condenser remove the 4 way valve Note Before unsoldering the welding joint wrap the 4 way valve with a wet cloth completely to avoid damage to the valve caused by high temperature Remove 3 foot nuts on compressor and then remove the compressor Note Protect the ports of discharge pipe and suction pipe to avoid foreign objects to enter it ...

Page 62: ...ius degree Tf Tcx1 8 32 Ambient temperature Fahrenheit display temperature Fahrenheit Celsius Fahrenheit display temperature Fahrenheit Celsius Fahrenheit display temperature Fahrenheit Celsius 32 33 32 0 55 56 55 4 13 79 80 78 8 26 34 35 33 8 1 57 58 57 2 14 81 80 6 27 36 35 6 2 59 60 59 15 82 83 82 4 28 37 38 37 4 3 61 62 60 8 16 84 85 84 2 29 39 40 39 2 4 63 62 6 17 86 87 86 30 41 42 41 5 64 65...

Page 63: ...lowing steps A Cut the pip Confirm the pipe length according to the distance of indoor unit and outdoor unit Cut the required pipe with pipe cutter B Remove the burrs Remove the burrs with shaper and prevent the burrs from getting into the pipe C Put on suitable insulating pipe D Put on the union nut Remove the union nut on the indoor connection pipe and outdoor valve install the union nut on the ...

Page 64: ...8 6 66 88 33 10 63 72 2 439 111 0 737 5 63 46 34 10 2 73 2 358 112 0 717 4 60 23 35 9 779 74 2 28 113 0 697 3 57 18 36 9 382 75 2 206 114 0 678 2 54 31 37 9 003 76 2 133 115 0 66 1 51 59 38 8 642 77 2 064 116 0 642 0 49 02 39 8 297 78 1 997 117 0 625 1 46 6 40 7 967 79 1 933 118 0 608 2 44 31 41 7 653 80 1 871 119 0 592 3 42 14 42 7 352 81 1 811 120 0 577 4 40 09 43 7 065 82 1 754 121 0 561 5 38 1...

Page 65: ... 0 983 5 84 61 34 13 59 73 3 144 112 0 956 4 80 31 35 13 04 74 3 04 113 0 93 3 76 24 36 12 51 75 2 94 114 0 904 2 72 41 37 12 76 2 844 115 0 88 1 68 79 38 11 52 77 2 752 116 0 856 0 65 37 39 11 06 78 2 663 117 0 833 1 62 13 40 10 62 79 2 577 118 0 811 2 59 08 41 10 2 80 2 495 119 0 77 3 56 19 42 9 803 81 2 415 120 0 769 4 53 46 43 9 42 82 2 339 121 0 746 5 50 87 44 9 054 83 2 265 122 0 729 6 48 42...

Page 66: ...74 62 11 32 101 3 22 15 362 9 24 51 41 63 10 93 102 3 13 14 342 8 25 49 19 64 10 54 103 3 04 13 323 9 26 47 08 65 10 18 104 2 96 12 306 2 27 45 07 66 9 83 105 2 87 11 289 6 28 43 16 67 9 49 106 2 79 10 274 29 41 34 68 9 17 107 2 72 9 259 3 30 39 61 69 8 85 108 2 64 8 245 6 31 37 96 70 8 56 109 2 57 7 232 6 32 36 38 71 8 27 110 2 50 6 220 5 33 34 88 72 7 99 111 2 43 5 209 34 33 45 73 7 73 112 2 37 ...

Page 67: ...Rd Qianshan Zhuhai Guangdong China 519070 Tel 86 756 8522218 Fax 86 756 8669426 Email gree gree com cn Http www gree com HONG KONG GREE ELECTRIC APPLIANCES SALES LIMITED Add Unit 2612 26 F Miramar Tower 132 Nathan Road TST Kowloon HK Tel 852 31658898 Fax 852 31651029 ...

Reviews: