Notices for operation

Working principle and special functions for cooling

Principle:

Air conditioner absorbs heat in the room and transmit to outdoor and discharged,
so that indoor ambient temperature decreased, its cooling capacity will increase

or decrease by outdoor ambient temperature.

Anti-freezing function

If the unit is running in COOL mode and in low termperature, there will be frost formed

on the heat exchanger, when indoor heat exchanger temperature decreased below 0

,

the indoor unit microcomputer will stop compressor running and protect the unit.

Working principle and special functions for heating

Principle:

The unit absoebs heat from outdoor air,carrys and emits the

 

heat in indoors

to make indoor air temperature higher. Its heating capacity would be lower

according to the low weather of outdoor ambient. 

This heating air circulation system can enhance the indoor temperature

in a short while.

If outdoor temperature got lower, please operate with the other heating ventilating

equipments.

Defrosting:

When outdoor temperature is low but with high humidity, after a long while running,

frost will form on outdoor unit, that will affect the heating effect, at this time,

the auto defrosting function will act, the heat running will stop for 8-10mins.

During the auto defrost, the fan motors of indoor unit and outdoor unit will stop.

During the defrost, the indoor indicator flashes, the outdoor unit may emit  vapor.

This is due to the defrosting, it isn't malfunction.

After defrost finished,the heating will recover automatically.

Anti-freezing function:

In "HEAT" mode, under the following three states, if indoor heat exchanger didn't reach certain

temperature, indoor fan would not opera

t

e to prevent blowing out cool air:

(Within 3mins)

1.Heating starts. 2.Af

t

er Auto defrosting finished. 3.Heating under the low temperature.

The conditions of unit can't normally run

The following temperature range protection device may act, that may cause stop running.

"HEAT"

running

Under the relative humidity above 80%( doors and windows opened) when cooling or dehu-

midifying for a long time, there will be dew drip off near the air vent.

"COOL"

running

"DRY"

running

Outdoor temp above

Outdoor temp below

Indoor temp. above

Outdoor temp above

Indoor temp. below

Indoor temp. below

Summary of Contents for GWCN1407X2B8NK1BA

Page 1: ...8 09X2 B8NK1BA GWHN18 09X2 B8NK1BA OWNER S MANUAL Thank you for choosing GREE air conditioner for correct operation please read this owner s manual carefully before operating the unit and keep it carefully for consultation GREEN HARBOR Models GWCN14 07X2 B8NK3BA GWHN14 07X2 B8NK3BA GWCN18 09X2 B8NK3BA GWHN18 09X2 B8NK3BA GWHN14 07X2 B8NK2BA GWHN18 09X2 B8NK2BA ...

Page 2: ...0 22 24 17 Installation service Notices for installation Install indoor unit Install outdoor unit Test operation and check after installation Thank you for choosing this air conditioner please read this owner s manual carefully before operating the unit and keep it carefully for consultation Installation dimension diagram items should be forbidden This symbol stands for the items should be followe...

Page 3: ...ts that may cause overheating or fire Never damage the electric wire or use the electric wire which is not appointed Otherwise it will cause overheating or fire When cleaning it is necessary to stop driving and turn off the power supply Cut off power supply Otherwise it may cause electric shock or damage Rated voltage of this air cond itioner 230V with a tolerable fluctu ation at The compressor wi...

Page 4: ... shock Earth The ground be connected If not please ask the qualified person nel to install Furthermore don t conn ect each wire to the gas pipe water pipe drainage pipe or any other impr oper places Select the most appropriate temperature It can preclude the electricity wasted Keep room cool er than outside about Don t leave windows and doors open for a long time while operating the air conditi on...

Page 5: ...the body for a long time It can cause health problems Don t use the air conditioner for other purposes such as drying clothes preserving foods etc Notices for use The power cords of this air conditioner adopt X type connection please don t cut off or damage the power cords and control cords If they are damaged please ask the qualified personnel to change them To adjust the airflow and direction ap...

Page 6: ... capacity noise index are tested before leaving factory The max input power are tested under the max cooling condition 27 24 18 and max heating condition Indoor outdoor Cooling only 900 2 36 58 430 2 730 2 R22 0 85 2 T1 I 8 2 65 3 2 2 2200 2 GWCN14 07X2 B8NK1BA IP24 900 2 910 2 36 58 430 2 730 2 755 2 R22 0 90 2 8 2 65 3 2 2 3 4 2 2200 2 GWHN14 07X2 B8NK1BA Cooling and heating 2400 2 50Hz 230V Coo...

Page 7: ...acity noise index are tested before leaving factory The max input power are tested under the max cooling condition 27 24 18 and max heating condition Indoor outdoor Cooling only 1200 2 36 58 430 2 955 2 R22 0 80 2 T1 I 8 2 65 4 2 2 2500 2 GWCN18 09X2 B8NK1BA IP24 1200 2 1200 2 36 58 430 2 955 2 1050 2 R22 0 90 2 8 2 65 4 2 2 4 6 2 2500 2 GWHN18 09X2 B8NK1BA Cooling and heating 2850 2 50Hz 230V Coo...

Page 8: ...ng equipments Defrosting Whenoutdoortemperatureislowbutwithhighhumidity afteralongwhilerunning frostwillformonoutdoorunit thatwillaffecttheheatingeffect atthistime theautodefrostingfunctionwillact theheatrunningwillstopfor8 10mins Duringtheautodefrost thefanmotorsofindoorunitandoutdoorunitwillstop Duringthedefrost theindoorindicatorflashes theoutdoorunitmayemit vapor Thisisduetothedefrosting itisn...

Page 9: ...r unit SET TEMP DRY Air out COOL HEAT only for cooling and heating type unit RUN Air out Air in Air in Wireless remote control Manual switch Front panel Filter Guide louver Display Wall pipe Bind tape Connection wire Drainage pipe Zoom in the display 7 ...

Page 10: ...temperature will be changed quickly Thetemperaturesettingrangeis16 30 COOL HEAT COOL button HEAT button At operating pressing this button could enter into the COOL mode directly At operating pressing this button could enter into the HEAT mode directly Pressing this button once the guide louver will start swinging at certain angle when repressed it will stop swinging Pressing this button will displ...

Page 11: ...OW OFF At AUTO FAN or HEAT modes the BLOW function cannot be set and there is no BLOW displayed Pressing this button enter into SLEEP state or quit the SLEEP state After unit is turned off and cancel the SLEEP function At FAN and AUTO mode the SLEEP function cannot be set It is for SLEEP At COOL DRY mode Enter into SLEEP state and after one hour running later the temp of main unit be increased 1 2...

Page 12: ...This function may be not available for some units 4 Press TURBO button can realize the ON and OFF of TURBO function The above operation please refers to Page 8 Page 9 for details Introduction for special functions About AUTO mode When AUTO mode is selected the setting temperature will not be displayed on the LCD of the wireless remote control according to the indoor temperature unit will automatic...

Page 13: ...less remote control will not be used for a long time please otherwise it can cause the malfunction of the wireless remote control take them out and don t let the leakage liquid damage the wireless remote control The operation should be in its receiving range It should be placed at where is 1m away from the TV set or stereo sound sets If the wireless remote control cannot operate normally please ta...

Page 14: ...wash the panel or it could cause deformation or discolouration Install front panel Place two supporters of the front panel into the slots along the direction of arrows cover and clasp the front panel As show in Fig 4 a b Fig 4 Along the arrowhead direction open an angle at both slots of front panel then pull the air filter downward and take it out As show in Fig 5 a b Cleaning NOTE There are micro...

Page 15: ...ether ground wire is properly connected Check that whether the batties of air conditioner are changed Check that whether the installation stand of the outdoor unit is damaged or not If damaged please contact the dealer Maintain after use Turn off main power Clean the filter as well as indoor and outdoor units bodies Clear dust and obstructions from the outdoor unit Repaint the rubiginous place on ...

Page 16: ... with our authorized maintenance center There s unusual smell blowing from the outlet after operation is started Sound of water flow can be heard during the operation When unit is started when operating compressor starts or stops or when unit is stopped sometimes there is swoosh or gurgle sound This sound is due to refrigerant flowing but not malfunctions from the air outlet vent In COOL mode some...

Page 17: ...sert it Is it in its receiving range Or obstructed On Page 11 Check the voltage in wireless remote control batteries On Page 11 inside is charged otherwise replace the Whether the wireless remote control is damaged If water leakage in the room The air humidity is on the high side Condensing water over flowed The connection position of indoor unit drainage pipe is loose If water leakage at outdoor ...

Page 18: ...rder to avoid condensing water be vaporized again restrain temperature rising defrosting there is water flowing out or vapor be produced Indoor unit cannot deliver air If unit is running under the high humidity for a long outlet grill and drip off time the moisture will be condensed on the air Immediately stop all operations and plug out contact the dealer in following situations There is harsh so...

Page 19: ...ithstand the full weight and vibration of the unit And will not increase the noise Be sure to leave enough space to allow access for routine maintenance The height of the installed location should be 200cm or more from the floor Select a place about 1m or more away from TVset or any other electric appliances Select a place where the filter can be easily taken out Make sure that the indoor unit ins...

Page 20: ...and be fix by screw otherwise it would cause electric shock The user power must offer the reliable earthing terminal Please don t connect the earthing wire with the following place Tap water pipe Gas pipe Contamination pipe Other places that professional personnel consider them unreliable It should be reliably earthed and it should be connected to the special earth device the installation work sho...

Page 21: ...sion diagram Above Above Above Above Installation dimension diagram Space to the ceiling Space to the wall Air outlet side Space to the floor Space to the wall Air outlet side Space to the wall Air inlet side 57 2cm 37 8cm Above Above Abo ve ...

Page 22: ... downward slant Do not wrench or bend the drain pipe or flood its end by water When the long drainage pipe passing through indoor wrap it with insulation materials Wrenched Bent Flooded Electrical wiring the terminal on N the black one to 2 the brown Power connection wire Fig 7 Install indoor unit Blue Black Brown Yellow green 1 Open the front panel to disassemble the screw cap take off the filter...

Page 23: ...dy case wrap the piping electric wire water pipe with tape and put them th rough the piping hole As show in Fig 10 Hang the mounting slots of the indoor unit on the upper tabs of the rear panel and check if it is firm enough As show in Fig 11 The height of the installed location should be 2m or more from the floor Install the connection pipe Align the center of the piping flare with the relevant v...

Page 24: ...oling and heating unit connecting power cord Note cooling and heat pump type Wrong wiring may cause spare parts In malfunction door After the cable fixed make sure unit there should be a free space between Out the connection and fixing place on the door lead wire unit Connection diagram of indoor unit and outdoor unit In door unit Out door unit Blue Black Brown Yellow Green Blue Black Brown Yellow...

Page 25: ...eakage detector to test the outdoor unit and pipeline connection leak or not Fig 13 pump Air purging and leakage test 1 Take out the nut cover of the inlet for refrigerant 2 Align the center of the piping and tighten the conical nut with hands 3 Tighten the conical nut with spanner 4 Take off the valve cover of liquid valve and gas valve and nut of Freon charge nuzzle 5 Loosen the valve stem of li...

Page 26: ...e the part Has the unit been connected to a secure earth connection It may cause electrical leakage Is the power cord specified It may cause electric malfunction or damage the part Is the inlet and outlet been covered It may cause insufficient cooling heating capacity Has the length of connection pipes and refrigerant capacity been recorded The refrigerant capacity is not accurate Test Operation B...

Reviews: