Water-cooled Heat Recovery DC Inverter VRF
5
3.2.1 Space requirement for single-module unit
For easy maintenance, at least one of the left side and right side of ODU should be over 500 mm
away from the barrier so that maintenance person can access the rear part of the unit.
Unit:mm(in.)
Fig.3.1
3.3 Piping Work Requirements
Requirements.
R410A Refrigerant System
Outer diameter mm(in.)
Wall thickness mm(in.)
Type
Φ6.35(1/4)
≥0.8(1/32)
O
Φ9.52(3/8)
≥0.8(1/32)
O
Φ12.70(1/2)
≥0.8(1/32)
O
Φ15.9(5/8)
≥1.0(3/76)
O
Φ19.05(3/4)
≥1.0(3/76)
1/2H
Φ22.2(7/8)
≥1.2(1/21)
1/2H
Φ28.60(1-1/8)
≥1.2(1/21)
1/2H
Φ34.90(1-3/8)
≥1.3(2/39)
1/2H
Φ41.30(1-5/8)
≥1.5(1/17)
1/2H
Φ44.5(1-3/4)
≥1.5(1/17)
1/2H