Multi Variable Air Conditioners Duct Type Indoor Unit
6
4 Installation Instructions
4.1 Installation of Indoor Unit
4.1.1 Outline Dimension and Installation Spots
Equip with a service port after lifting the unit. For the convenience of maintenance, the service
port should be on one side of the electric box and below unit’s lower level. Below are the outline
dimension applicable to indoor units of GMV-ND07~24PLS/B-T(U).
Fig 4.1.1
Below are dimensions of A, B, C, etc. for different models:
Unit: mm(in.)
Item Model
A
B
C
D
E
F
GMV-ND07~12PLS/B-T(U)
760
(30)
415
(16-3/8)
710
(27-15/16)
200
(7-14/16)
462
(18-3/16)
486
(19-2/16)
GMV-ND14~18PLS/B-T(U)
1060
(41-3/4)
415
(16-3/8)
1010
(39-12/16)
200
(7-14/16)
462
(18-3/16)
486
(19-2/16)
GMV-ND24PLS/B-T(U)
1360
(53-1/2)
415
(16-3/8)
1310
(51-9/16)
200
(7-14/16)
462
(18-3/16)
486
(19-2/16)
One duct-type unit is only for one room.
4.1.2 Punching of Bolt Spots and Bolt Installation
Punch holes on the installation area according to the 4 spots on the paper pattern; The punching
diameter may refer to the diameter of expansion bolt, about 60mm(2-3/8 in.) to 70mm(2-3/4 in.) depth,
as shown in Fig 4.1.2.1.