Gree GMV MTAC VRF for North America
74
Branch shall be isolated by insulating material that can bear 120°C (248°F) or even higher temperature. The
attached foam of branch cannot be taken as insulating material.
6.1.5 Thermal Insulation for Pipeline
(1) For multi VRF system, every copper pipe should be labeled so as to avoid
misconnection.
(2) At the branch inlet, leave at least 500mm(19-3/4inch) straight pipe section.
(3) Thermal insulation for pipeline.
(4) dhhdf
1) To avoid condensate or water leakage on the connection pipe, the gas pipe and liquid
pipe must be wrapped with thermal insulating material and adhesive tape for
insulation from the air.
2) Joints of indoor and outdoor unit should be wrapped with insulating material and
leave no gap between pipe and wall. See Fig. 18.
Fig. 18
3) When wrapping the tape, the later circle should cover half of the former one. Don’t
wrap the rape too tight, otherwise the insulation effect will be weakened.
4) After wrapping the pipe, apply sealing material to completely seal the hole on the
wall.
(1) Thermal insulating material shall be able bear the pipe temperature. For heat pump unit, liquid pipe should
bear 70°C (158°F) or above and gas pipe should bear 120°C (248°F) or above. For cooling only unit, both
liquid pipe and gas pipe should bear 70°C (158°F) or above.
(2) Thermal insulating material of branches should be the same as that of the pipeline. The attached foam of
branches cannot be taken as insulating material.
6.1.6 Support and Protection of Pipeline
(1) Support should be made for hanging connection pipe. Distance between each support cannot be over
1m(3-1/4feet).
(2) Protection against accidental damage should be made for outdoor pipeline. When pipeline exceeds
1m(3-1/4feet), a pinch board should be added for protection.
Summary of Contents for GMV MTAC VRF Series
Page 1: ...GMV MTAC VRF for North America GC201908 I Capacity 12kBtu h Rated Frequency 60 Hz...
Page 5: ...Gree GMV MTAC VRF for North America 1 PRODUCT...
Page 11: ...Gree GMV MTAC VRF for North America 7 CONTROL...
Page 43: ...Gree GMV MTAC VRF for North America 39 Select language Select system of units...
Page 64: ...Gree GMV MTAC VRF for North America 60 Switchover of Software Languages...
Page 65: ...Gree GMV MTAC VRF for North America 61 INSTALLATION...
Page 88: ...Gree GMV MTAC VRF for North America 84 MAINTENANCE...
Page 117: ...JF00304109...