70
5.4 Dimension of Pipe between Indoor Branches
Select pipe between indoor branches according to the capacity of downstream indoor units; if
the capacity exceeds that of the outdoor unit, capacity of outdoor unit prevails.
GMV-12WP/A-T(U):
Total capacity of downstream indoor units C (Btu/h)
Pipe (mm/inch)
Liquid pipe (mm/inch)
C ≤19000
Φ
12.7
(
Φ
1/2)
Φ
6.35
(
Φ
1/4)
19000<C≤48500
Φ
15.9
(
Φ
5/8)
Φ
9.52
(
Φ
3/8)
48500<C≤
76400
Φ
19.05
(
Φ
3/4)
Φ
9.52
(
Φ
3/8)
5.5 Dimension of Pipe between Indoor Branch and IDU
Dimension of pipe between indoor branch and IDU should be consistent with the dimension of
indoor pipe.
GMV-12WP/A-T(U):
Rated capacity of IDU C(Btu/h)
Gas pipe (mm/inch)
Liquid pipe (mm/inch)
C≤9600
Φ
9.52
(
Φ
3/8)
Φ
6.35
(
Φ
1/4)
9600<C≤17000
Φ
12.7
(
Φ
1/2)
Φ
6.35
(
Φ
1/4)
17000<C≤48000
Φ
15.9
(
Φ
5/8)
Φ
9.52
(
Φ
3/8)