Gree GMV MTAC VRF for North America
68
Dimension
A
Allow for wall finishing
B
Allow for floor finishing
Min.(mm/inch)
Min. (mm/inch)
Max(mm/inch)
No Accessories
6.4(1/4)
6.4(1/4)
—
With Subbase
45(1-3/4)
89(3-1/2)
127(5)
With Lateral Duct
19(3/4)
6.4(1/4)
—
(1) If more than one accessory is to be used, use the maximum dimension. If the wall thickness is more than
350mm(13-3/4in.) - (A +6.mm4(1/4in.)), a sleeve extension must be used.
(2) See the manual for detailed installation instructions.
4 Installation of Electronic Expansion Valve Assy (unit with
external EXV)
The EXV of indoor unit is built-in.
5 Installation of Refrigerant Pipeline
5.1 Allowable Length and Height Difference of Connection Pipe
Y type branch joint is adopted to connect indoor and outdoor units. Connecting method is
shown in the figure below:
NOTICE!
Equivalent length of one Y-type branch is 0.5m(1-5/8feet).
le Length and Height Difference of Connection Pipe
Piping parameters of GMV-12WP/A-T(U):
—
Allowable value
Fitting pipe
m
feet
Total length (actual length) of fitting pipe
30
98-3/8
L1+a+b
Length of farthest fitting pipe (m)
Actual length
30
98-3/8
L1+b
Equivalent length
30.5
100-1/8
From the 1
st
branch to the farthest indoor pipe
15
49-2/8
b
Height difference between ODU and IDU
ODU at upper side
15
49-2/8
—
ODU at lower side
15
49-2/8
—
Height difference between IDUs
10
32-6/8
—
Summary of Contents for GMV MTAC VRF Series
Page 1: ...GMV MTAC VRF for North America GC201908 I Capacity 12kBtu h Rated Frequency 60 Hz...
Page 5: ...Gree GMV MTAC VRF for North America 1 PRODUCT...
Page 11: ...Gree GMV MTAC VRF for North America 7 CONTROL...
Page 43: ...Gree GMV MTAC VRF for North America 39 Select language Select system of units...
Page 64: ...Gree GMV MTAC VRF for North America 60 Switchover of Software Languages...
Page 65: ...Gree GMV MTAC VRF for North America 61 INSTALLATION...
Page 88: ...Gree GMV MTAC VRF for North America 84 MAINTENANCE...
Page 117: ...JF00304109...