DC Inverter Multi VRF System
8
4.3.5 Install Power, Communication and Pipeline
Fig.9
Fig.10
(1) The diameter of drain pipe must be less than
Φ15mm (Φ3/5
inch).
(2) When the drain pipe is installed, the highest position of the drain pipe can’t exceed 3.5m (11-1/2feet) above the
bottom of unit and a water loop must be set at the highest position.
(3) After the drain pipe exits the drain outlet, it is straight up and not inclined.
(4) The refrigerant connection pipe needs to be insulated.