DC Inverter Multi VRF System 

28 

Error Code 

Content 

Error Code 

Content 

PJ 

Failure startup of inverter compressor 

HJ 

Failure startup of inverter fan 

PP 

AC current protection of inverter 
compressor 

HP 

AC current protection of inverter fan 

Ed 

Low temperature protection for drive 
module 

— 

— 

Debugging: 

Status: 

Error Code 

Content 

Error Code 

Content 

A0 

Unit waiting for debugging 

AP 

Debugging confirmation when starting 
up the unit 

A1 

Inquiry of compressor operation 
parameters 

AU 

Long-distance emergency stop 

A2 

Refrigerant recovery operation of 
after-sales 

Ab 

Emergency stop of operation 

A3 

Defrosting 

Ad 

Limit operation 

A4 

Oil-return 

n0 

SE operation setting of system 

A6 

Heat pump function setting 

n1 

Setting of defrosting cycle K1 

A7 

Quiet mode setting 

n2 

Setting of upper limit of IDU/ODU 
capacity distribution ratio 

A8 

Vacuum pump mode 

n4 

Limit setting for max. capacity/output 
capacity 

A9 

IPLV test 

n6 

Inquiry of malfunction 

AA 

EU AA level EER test mode 

n7 

Inquiry of parameters 

AH 

Heating 

n8 

Inquiry of project code of IDU 

AC 

Cooling 

nA 

Heat pump unit 

AL 

Charge refrigerant automatically 

nH 

Heating only unit 

AE 

Charge refrigerant manually 

nC 

Cooling only unit 

AF 

Fan 

nE 

Negative code 

Error Code 

Content 

Error Code 

Content 

U0 

Preheat time of compressor is 
insufficient 

C4 

Malfunction of lack of IDU 

U2 

Wrong setting of ODU’s capacity 
code/jumper cap 

C5 

Alarm because project code of IDU is 
inconsistent 

U4 

Refrigerant-lacking protection 

C8 

Emergency status of compressor 

U5 

Wrong address for driving board of 
compressor 

C9 

Emergency status of fan 

U6 

Alarm because valve is abnormal 

CH 

Rated capacity is too high 

U8 

Malfunction of pipeline for IDU 

CC 

Malfunction of lack of main control unit 

U9 

Malfunction of pipeline for ODU 

CL 

Rated capacity is too low  

UC 

Setting of main IDU is successful 

CF 

Malfunction of multiple main control 
units   

UL 

Wrong button-dial 

CJ 

Address DIP switch code of system is 
shocking   

UE 

Charging of refrigerant is invalid   

CP 

Malfunction of multiple wired controller   

C0 

Communication malfunction between 
IDU, ODU and IDU’s wired controller 

CU 

Communication malfunction between 
IDU and the receiving lamp plate   

C2 

Communication malfunction between 
main control and inverter compressor 
driver 

Cb 

Overflow distribution of IP address 

C3 

Communication malfunction between 
main control and inverter fan driver 

— 

— 

Summary of Contents for GMV-12WP/A-T

Page 1: ...Owner s Manual Original Instructions Commercial Air Conditioners DC Inverter Multi VRF System Model GMV 12WP A T U...

Page 2: ...soon as possible and provide the following information 1 Content on the name plate model number cooling capacity production code ex factory date 2 Malfunction details before and after the malfunction...

Page 3: ...t is directly caused by corrosive gas 4 After verification defects are due to improper operation during transportation of product 5 Operate repair maintain the unit without abiding by instruction manu...

Page 4: ...or Installation Maintenance and Relocation 5 4 3 Assembly procedures 6 4 4 Connection Pipe 9 4 5 Installation of Connection Pipe 12 4 6 Vacuum Pumping Refrigerant Adding 16 4 7 Electric Wiring 17 5 Ch...

Page 5: ...the door and window frequently to keep good ventilation for avoiding oxygen deficit when gas heater or oil heater is used in the room 11 Never plug in or unplug the power plug directly to turn on or t...

Page 6: ...be within 50 135 of that of the outdoor unit Model Min sets of connectable IDUs Max sets of connectable IDUs GMV 12WP A T U 1 2 3 Can be connected to various indoor units When any one of the indoor u...

Page 7: ...m or flammable gas 4 Children under 10 years old must be supervised not to operate the unit 5 Select a location which is out of children s reach Keep the unit away from children 6 Make sure the locati...

Page 8: ...E If more than one accessory is to be used use the maximum dimension If the wall thickness is more than 350mm 13 3 4inch A 6 35mm 1 4inch a sleeve extension must be used 3 3 Piping Work Requirements R...

Page 9: ...at high pressure side When the pressure gauge reads 0 0 05 MPa completely close the valve gas valve at low pressure side Then stop operation immediately and cut off the power 4 When recycling the ref...

Page 10: ...e unit is to be installed in a small room relevant measures must be taken to prevent the refrigerant concentration in the room from exceeding the limit when the refrigerant leaks resulting in hypoxia...

Page 11: ...ing the complete unit remove the panel to prevent damage 4 3 4 Install Main Unit Fig 7 Push the unit into the outer case Fig 8 Install the unit inside the metal outer case and then use screws to fix i...

Page 12: ...han 15mm 3 5inch 2 When the drain pipe is installed the highest position of the drain pipe can t exceed 3 5m 11 1 2feet above the bottom of unit and a water loop must be set at the highest position 3...

Page 13: ...stall the panel on the unit and press e buckle on both sides 4 4 Connection Pipe 4 4 1 Schematic Diagram of Piping Connection Fig 13 4 4 2 Allowable Length and Height Difference of Connection Pipe Y t...

Page 14: ...b Equivalent length 30 5 100 1 8 From the 1st branch to the farthest indoor pipe 15 49 2 8 b Height difference between ODU and IDU ODU at upper side 15 49 2 8 ODU at lower side 15 49 2 8 Height differ...

Page 15: ...Y type branch C 68200 FQ01A A 68200 C 102400 FQ01B A 102400 C 238800 FQ02 A 238800 C 460600 FQ03 A 460600 C FQ04 A 4 4 5 Dimension of Pipe between Indoor Branches Select pipe between indoor branches a...

Page 16: ...ction pipe should be as short as possible so is the height difference between indoor and outdoor units Keep the number of bends as little as possible Radius of curvature should be as large as possible...

Page 17: ...n Fig 22 Make sure indoor pipe is correctly connected Improper location of the center will prevent flared nut from being securely twisted Thread of nut will get damaged if the flared nut is twisted fo...

Page 18: ...or space limit outlet pipe can be installed from the front right or rear side Fig 24 4 5 6 Installation of Y type Branch 1 Y type Branch Fig 25 2 Y type branch has several pipe sections with different...

Page 19: ...able bear the pipe temperature For heat pump unit liquid pipe should bear 70 C 158 F or above and gas pipe should bear 120 C 248 F or above For cooling only unit both liquid pipe and gas pipe should...

Page 20: ...door valve as shown below Fig 28 4 6 2 Refrigerant Adding 1 Refrigerant quantity of outdoor unit before delivery Model GMV 12WP A T U Refrigerant Qty kg oz 0 8 28 2 1 The refrigerant amount charged be...

Page 21: ...8 Total length of each liquid pipe 6 35 A a b 5 5 5 15m 49 1 8feet Quantity of indoor unit 2 sets Therefore the minimum quantity of additional refrigerant 0 2 2 15 0 022 0 73kg 25 7oz 4 7 Electric Wir...

Page 22: ...o the following Liquid pipe Gas pipe Drain pipe Other places that are deemed as not secure by professional technicians 1 Before starting work check that power is not being supplied to the indoor unit...

Page 23: ...wiring reference of power supply and communication cable If there are differences between the figure structure and actual unit please refer to the actual unit 4 For engineering wiring please refer to...

Page 24: ...transportation 6 Calculate the quantity of refrigerant that needs to be added according to the pipe length Pre charge the refrigerant In case that the required charging quantity is not reached while...

Page 25: ...em has confirmed the quantity 2s later next step starts 00 16 Display circularly 00 16 displays the quantity of indoor unit identified by the system 05_ Detect ODU s internal communication and capacit...

Page 26: ...09_ Refrigerant judgments before startup 09 U4 Display circularly System is lack of refrigerant and display will be as in the left Please cut off power of IDU and ODU and check if there is leakage on...

Page 27: ...5s the system will enter normal standby status 15 error code Display circularly Malfunction occurs when debugging for cooling mode 16_ Heating debugging 16 AH Display circularly Debugging for heating...

Page 28: ...n the condensing temp will be lower 5 evaporating temp C F When ambient temp in cool mode is 25 35 C 77 95 F the evaporating temp is 0 10 C 32 50 F When ambient temp in heat mode is above 5 C 23 F the...

Page 29: ...s What to do Unit doesn t work Fuse or circuit breaker is cut off Replace fuse or reset the circuit breaker Power failure Restart unit when power is restored Power is not connected Connect the power R...

Page 30: ...ication combine division symbol and content symbol to check the corresponding error Indoor Error Code Content Error Code Content Error Code Content L0 Indoor Unit Error L9 Quantity Of Group Control In...

Page 31: ...pressure is too low bH Clock of system is abnormal P0 malfunction of driving board of compressor uniform H0 Malfunction of driving board of fan uniform P1 Driving board of compressor operates abnormal...

Page 32: ...rigerant automatically nH Heating only unit AE Charge refrigerant manually nC Cooling only unit AF Fan nE Negative code Error Code Content Error Code Content U0 Preheat time of compressor is insuffici...

Page 33: ...ent of air conditioners 8 1 Outdoor Heat Exchanger Outdoor heat exchanger shall be cleaned regularly which is at least once every two months You can use a dust catcher with nylon brush to clean away t...

Page 34: ...nitrogen or refrigerant to conduct the tests 9 After sales Service If there s quality defect or other problems in the product please contact Gree local after sales service department for help Warranty...