6
ENGLISH
PROBLEMS
PROBLEMS
ORIGIN
SOLUTIONS
Green
Light does not light.
Electric supply is
not working.
Led is fused.
Check and fix the electric
supply if necessary.
Check and replace the led
if necessary.
Amber
led is lighten (alarm).
Thermostat
is
damaged.
Replace
or
fix
the
thermostat, then restart the
heater.
If alter restarting the amber
light keeps shining or we
are not able to restart then
the security switch is
damaged and must be
replaced.
Red
led shines at 1 to 2 minutes
intervals.
Low water flow
or
air
in
the
system.
Backwash the filter to
restore flow.
Fix unusual air entry.
Resistances do not work with
amber
Light off.
Thermostat
is
impaired.
Resistances
are
out of order.
Check
and
replace
if
necessary.
Check resistance between
two poles of resistance
fork
48Ω for 3Kw
25Ω for 6Kw
16Ω for 9Kw
12Ω for 12Kw
22Ω for 18Kw
Replace resistances if thy
do not reach those values.
Flow switch not
working properly.
Check
flow
switch
operation.
Check for continuity with
paddle pushed. Replace if
necessary.
ARS out of order.
Check with continuously
activated (not intermittent)
flow switch, after 1,5
minutes, the resistances are
not turned on. If flow
switch is working properly
then replace ARS.