background image

Page 8

Section 3: Installation

ISOLATION VALVES

Two 28mm isolating valves are supplied with the volumiser/

header. One of these must be fitted in the system flow pipe and 

the other in the system return pipe, close to where they are 

connected to the header/volumiser.

FLOW REGULATOR

A flow regulator is supplied with the heat pump. This must be fitted 

in the return pipe from the volumiser/header to the heat pump. 

Refer to Figure 3-3.

The flow regulator can be fitted vertically or horizontally but must 

be installed such that the arrow on the brass body points in the 

direction of flow. 

For an accurate and stable reading, ensure that there is straight 

pipe of at least 5 times the pipe diameter (i.e. for 28mm pipe: 5 x 

28mm = 140mm) before the inlet to the regulating valve.

During system commissioning, the flow regulator must be set to 

the achieve the required flow rate in the primary circuit between 

the heat pump and the volumiser/header. 
The required flow rate will be dependent on the required 

heat pump output (at design conditions) and the temperature 

differential between the heat pump flow and return. 
This flow rate can be calculated as follows:

Flow rate = Heat output (kW) ÷ Temperature differential (K) 

 

÷ Specific heat capacity of water (4.2kJ/kgK) *

Example:

Heat output = 12kW

Differential = 5K
Specific heat capacity of water = 4.2 kJ/KgK

Flow rate = 12 ÷ 5 ÷ 4.2 = 0.571 kg/sec
 

= 0.571 x 60 = 34.3 kg/min (or 34.3 litres/min)

! NOTE !

* The use of an antifreeze/inhibitor/biocide fluid will alter 

the value of Specific Heat Capacity but, as the difference is 

minimal, use 4.2kJ/kgK as a constant for the calculation of 

flow rate.

To set the flowrate, the system should be set to maximum 

demand, i.e. with all emitters and zone valves open. The flow rate 

is then adjusted by rotating the regulating valve until the required 

flow rate is indicated on the flow regulator scale.

• 

To increase the flow rate - rotate valve anticlockwise

• 

To decrease the flow rate - rotate valve clockwise

The actual flowrate must be read from the LOWER edge of the 

float, in the flow regulator window. Refer to Figure 3-3.

If two heat pumps of the SAME output are connected to the low 

loss header/volumiser, both flow regulators should be set to the 

SAME flowrate, as calculated for the output of each heat pump. 

If the two heat pumps are of DIFFERENT outputs:
a) 

Calculate the required flow rate for each heat pump, based 

on their respective outputs.

b) 

Set the flow rate of each heat pump separately, i.e. with only 

one heat pump operating at a time.

Figure 3-3: 

Flow regulator adjustment

Grant Aerona³ heat pumps are supplied with the circulating pumps 

set to the highest of three possible performance curves. In order 

to achieve the required flow rate it may be necessary to select 

one of the other pump performance curves. 

This is done by adjusting the setting of DIP switches DIP SW5 

and DIP SW6 on the Terminal PCB of the heat pump. Follow the 

guidance given in Section 8.3.6 of the Grant Aerona³ Installation 

and Servicing instructions supplied with the heat pump

3.8 

SYSTEM CONNECTIONS

The heating system flow and return connections can be made 

to either the right-hand or left-hand connections of the Grant 

Combined volumiser/low loss header, but BOTH connections 

must be made to the opposite side of the volumiser/header to 

the heat pump connections. Refer to Figures 3-1 and 3-2 for 

connection details.

A second pair of system flow and return connections, i.e. for a 

second zone, can also be connected to the volumiser/header, 

but must be connected to the same side as the other system 

connections. Refer to Figures 3-1 and 3-2 for connection details.

3.9 

VOLUMISER ONLY CONNECTIONS

It is possible, if required, to use the Grant Combined volumiser/

low loss header as a volumiser only, either using the integral 3kW 

immersion as a supplementary heater or not.

The volumiser/header must be fitted in the flow pipe from the heat 

pump as follows:
• 

The flow pipe from the heat pump should be connected to 

lowest connection on either the right-hand or left-hand side of 

the volumiser/header.

• 

The outlet pipe from the volumiser/header should be 

connected should be connected to one of the upper set of 

connections on either the right-hand or left-hand side of the 

volumiser/header.

Refer to Figure 3-4.

Summary of Contents for HPIDSYSLLHKIT

Page 1: ...UK DOC 0184 Rev 0 3 PROVISIONAL February 2022 Grant Combined Volumiser Low Loss Header Installation Instructions...

Page 2: ...y means without prior written consent IMPORTANT NOTE FOR USERS These installation instructions are intended to guide the installer in the installation of the Grant Combined Volumiser Low Loss Header S...

Page 3: ...RICAL 10 4 1 General 10 4 2 Electrical connections 10 4 3 Immersion heater 11 4 4 Electrical connections between lead and supplementary heat pumps 12 5 OPERATION 13 5 1 General 13 5 2 Aerona heat pump...

Page 4: ...nt Combined volumiser low loss header is an insulated rectangular tank fitted with an integral 3kW electric immersion heater This is housed within a weatherproof external casing with a removable cover...

Page 5: ...0 Inlet outlet connections 1 BSP Drain cock connection BSP Manual air vent connection BSP Materials Shell Mild steel Outer casing Galvanised mild steel polyester powder coated Insulation Mineral wool...

Page 6: ...G The Grant Combined volumiser low loss header is supplied wrapped in bubble wrap with a separate kit of components in a plastic bag located inside the top cover Refer to list of components given in S...

Page 7: ...System Return System Flow System Flow System Return Second Zone Figure 3 1 Heat pump connections on left hand side Heat pump 1 Flow Heat pump 2 Flow Heat pump 2 Return Heat pump 1 Return System Return...

Page 8: ...the flow regulator window Refer to Figure 3 3 If two heat pumps of the SAME output are connected to the low loss header volumiser both flow regulators should be set to the SAME flowrate as calculated...

Page 9: ...3 Installation Page 9 Flow from heat pump Flow from heat pump Alternative position Flow to system Flow to system Alternative positions Flow to system Alternative position Figure 3 4 Volumiser only con...

Page 10: ...ected to the heat pump terminal PCB Refer to Section 4 2 Electrical Connections 4 2 ELECTRICAL CONNECTIONS WARNING Ensure that all electrical supplies to the heat pump and volumiser header are isolate...

Page 11: ...on heat pump Terminal PCB to Terminal N A1 on the backup heater relay Refer to Figure 4 3 for header volumiser connection diagram 3 Tighten the cable gland to securely grip the cable 4 3 IMMERSION HEA...

Page 12: ...the immersion heater needs to be replaced it must be fitted to the volumiser header using the gasket provided on the unit Only use a correctly shaped spanner Stilsons or pipe grips should NOT be used...

Page 13: ...n 5 3 for the correct parameter settings If a second Grant Aerona heat pump is to be used refer to Section 5 5 for the correct parameter settings for the operation of a supplementary heat pump 5 3 PAR...

Page 14: ...me for a defrost should never be more than 5 minutes including the compressor protection off time of 3 minutes so the total power used during a defrost period by the immersion element would not be mor...

Page 15: ...Group Code Default Min Max Setting I 21 00 Enable outgoing water set point 0 Fixed set point 1 Climatic curve 1 0 1 0 I 21 01 Fixed outgoing water set point 45 C 23 0 60 0 55 NOTE Refer to the Aerona...

Page 16: ...GRANT ENGINEERING UK LIMITED Hopton House Hopton Industrial Estate Devizes Wiltshire SN10 2EU Tel 44 0 1380 736920 Fax 44 0 1380 736991 Email info grantuk com www grantuk com...

Reviews: