J. - Appendix
Manual pump settings (see „6.2. - Pump menu“ on page 26)
Appendix Manual pump settings
J.19.1. - Pump
In this menu, preconfi gured profi les for various pumps can be selected. Please note that individual settings
are still possible even when a profi le has been selected.
J.19.2. - Output Signal
This menu determines the type of pump used: Solar pumps perform at their highest power when the signal
is also maxed, heating pump on the other hand are set to highest power wenn the control signal is at the
lowest. Solar = normal, heating = Inverted.
Settings range: Normal, Inverted / Default setting: Normal
J.19.3. - PWM off
This signal is put out when the pump is switched off (Pumps that can detect cable break need a minimum
signal).
Settings range: (Solar:) 0 to 50% / Default setting: 0% - (Heating:) 50% to 100% / Default setting: 100%
J.19.4. - PWM on
This signal is needed to turn the pump on at minimum speed.
Settings range: (Solar:) 0 to 50% / Default setting: 10% - (Heating:) 50% to 100% / Default setting: 90%
J.19.5. - PWM Max
This determines the the output signal for the highest speed of the pump, that is used e.g. during purging or
manual operation.
Settings range: (Solar:) 50 to 100% / Default setting: 100% - (Heating:) 0% to 50% / Default setting: 0%
J.17.3 - 0-10V off
This voltage is put out when the pump is turned off (Pumps that can detect cable break need a minimum
voltage).
Settings range: (Solar:) 0,0 to 5,0 V / Default setting: 1,0 V - (Heating:) 5,0 to 0,0 V / Default setting: 4 ,0 V
J.17.4 - 0-10V on
This voltage is needed to turn the pump on at minimum speed.
Settings range: (Solar:) 0,0 to 5,0 V / Default setting: 1,0 V - (Heating:) 5,0 to 10,0 V / Default setting: 9,0 V
J.17.5 - 0-10V Max
This determines the output voltage for the highest speed of the pump, that is used e.g. during purging or
manual operation
Settings range: (Solar:) 5,0 to 10,0 V / Default setting: 10,0 V - (Heating:) 0,0 to 5,0 V / Default setting: 0,0
V
J.19.6. - Speed when „On“
This menu determines the calculated and displayed speed of the pump. If e.g. 30% is set here and the
signal set in „PWM on/0-10V on“ is put out, 30% speed is displayed. When the signal set in „PWM max/0-
10V max“ is put out, 100% speed is displayed. Everything in between is calculated accordingly.
Settings range: 10 to 90 % / Default setting: 30 %
J.19.7. - Show signal
Displays the set signal in text and a graphical diagram.
Caution
This function has no infl uence on the regulation, but changes only the speed displayed.