background image

30

6.6.2. - Thermostat

Thermostat is used for time- and temperature controlled additional heating.

Settings range: On, Off, Inverted

6.6.2.1. - TH Set

Taget temperature at thermostat sensor 1. Below this temperature, additional heating is switched 

on, till TH set + hysteresis is reached.

Settings range: 0-100°C / Default setting: 50

6.6.2.2. - TH hysteresis

Hysteresis of setpoint temperature.

Settings range: -20 to +20K / Default setting: 10K

Temperature values which are set too high can lead to scalding or damage to the 
system. Scalding protection must be provided by the customer!

Danger!

Caution

In Energy savings mode, different settings may apply, see e.g. T eco.

6.6.2.3. - Thermostat sensor 1

T set is measured with thermostat sensor 1.
When thermostat sensor 2 is connected, the relay switches on when T set is undershot at 

thermostat Sensor 1, and switches off when T set + hysteresis at thermostat sensor 2 is 

exceeded.

Settings range: S1-S8, VFS1-2, active storage / Default setting: none

6.6.2.4. - Thermostat sensor 2

Optional switch off sensor

When T set + hysteresis is exceeded at the optional thermostat sensor 2, the relay is switched off.

Settings range: S1-S8, VFS1-2, active storage / Default setting: none

6.6.2.5. - T eco

For Energy saving mode
When Energy saving mode is active: During solar charge T eco is used instead of TH set. When 
the temperature drops below T eco at thermostat sensor 1, the relay is switched on and heats up 

to T eco + hysteresis.

Settings range: 0-100°C / Default setting: 40°C

Special functions

R

el

a

y

 f

u

nc

ti

on

s

For Energy saving mode

Loading this storage activates the Energy saving mode

When this storage is charge by solar, additional heating is only switched on when the temperature 
is below T eco.

Settings range: (Storage sensors) / Default setting: fi rst storage

6.6.2.6. - Storage

Summary of Contents for Grant Solar GS222020X

Page 1: ...UK DOC 0107 Rev 1 0 November 2015 Grant Solar SD3X Solar Controller East West Systems Product code GS222020X Installation and Servicing Instructions...

Page 2: ...ection 25 5 6 Seizing protection 25 5 7 Collector alarm 25 6 Special functions 26 6 1 Program selection 26 6 2 Pump menu 26 6 2 1 Type of pump 26 6 2 2 Pump 26 6 3 Speed control R1 R2 27 6 3 1 Modes 2...

Page 3: ...0 10V for high efficency pumps 6 PT1000 temperature sensor inputs 2 VFS RPS direct sensor inputs Version 4 1 mechanical relay change over contact 2 electronical relays for speed control of standard pu...

Page 4: ...applicable DIN EN standards and the installation and operating instruction of the additional system components must also be observed The controller does not under any circumstances replace any safety...

Page 5: ...and function of the unit or the entire system Danger Description of controller The controller has been manufactured and tested with regard to high quality and safety requirements The unit is subject t...

Page 6: ...6 bar 0 1 bar 0 1 6 bar 0 2 5 bar 0 4 bar 0 6 bar 0 10 bar Network connections CAN Bus Permissible cable length of sensors and appliances Collector and outdoor sensor 30m other PT1000 sensors 10m VFS...

Page 7: ...tistical graphics etc Individual configuration of special functions Extensive setting menus with explanations Menu block can be activated to prevent unintentional setting changes Resetting to previous...

Page 8: ...specialist and in compliance with the applicable regulations Do not use the controller if the housing shows visible damage Caution Low voltage cables such as temperature sensor cables must be routed...

Page 9: ...to the selected position and mark the 3 mounting holes Make sure that the wall surface is as even as possible so that the housing does not become distorted when it is screwed on 5 Using a drill and s...

Page 10: ...rewdriver Fig C 2 4 and make electrical connections on the controller 4 Refit terminal connection cover and fasten screw 5 Switch on mains voltage and place controller in operation C 2 3 C 2 4 Install...

Page 11: ...pecific area of application with the appropriate permissible temperature range Sensor cables for S1 and S5 can be extended to a maximum of 30m using a cable with a cross section of at least 0 75mm Sen...

Page 12: ...of High Efficiency pumps LTDC Version V3 V4 V2 0 10V PWM signal output e g for control of High Efficiency pumps S6 Temperature sensor 6 12V power supply Connection of sensor earth to the grey lower te...

Page 13: ...1 2 3 S1 S1 S1 S2 S2 S2 R1 V1 R3 R3 4 5 6 T T S1 S1 S2 S2 S4 R1 R3 R2 V2 R1 V1 7 8 9 S1 S2 R3 S1 S1 S2 S2 S3 S3 S4 S3 R3 R3 R1 V1 R1 V1 R1 V1 12 11 10 Caution The following illustrations should be vie...

Page 14: ...storages and switching valve Solar with thermostat and switching valve Solar with cooling 1 collector cooling Solar with storage transfer Solar with storage and solid fuel boiler Solar with cooling 2...

Page 15: ...Solar with 3 storages and 3 pumps Solar with storage transfer and thermostat 2x Solar Solar with heating circuit and thermostat Solar with storage and solid fuel boiler and S4 Solar with cooling 3 col...

Page 16: ...th heat exchanger Solar with heat exchanger and 2 zones storage Solar with heat exchanger and 2 storages Solar with 2 collector surfaces heat exchanger storage and 3 pumps Solar with 2 collector surfa...

Page 17: ...status LED 2 lights up when a relay is active the red LED blinks when an error occurs Inputs are made with 4 buttons 3 4 which functions change context sensitive The esc key 3 is always used to cancel...

Page 18: ...back to the previous value so you can look at the selected setting again or adjust it if desired Pressing the esc more than once Caution Observe the explanations for the the individual parameters on...

Page 19: ...Function control of the system with operating hours etc Automatic mode manual mode or switch unit off Set parameters needed for normal operation E 4 Menu sequence and menu structure Solar and frost p...

Page 20: ...selecting Exit statistics Statistics Caution For analysis of the system data it is essential for the time to be set accurately on the controller Please note that the clock does not continue to run if...

Page 21: ...d consumer are switched on and off by pressing a key with no regard to the current temperatures and the parameters which have been set The measured temperatures are also shown to provide an overview a...

Page 22: ...tions apply for speed control see 6 3 Speed control R1 R2 Caution Switch on switch off temperature difference for sensor X If this temperature difference between the reference sensors is exceeded and...

Page 23: ...off If the temperature falls below this value again and the other conditions are also met then the controller switches the pump and or valve on again Danger Temperature values that are set too high ca...

Page 24: ...ing of system components by automatic shutdown of the solar pump If SProt Ton is exceeded for 1 minute at the collector the pump is switched off and stays off The pump is activated again when the temp...

Page 25: ...erature drops below the set value Frost stage 1 If the collector temperature drops further to the set value Frost stage 2 the controller switches the pump on continuously If the collector temperature...

Page 26: ...unpredictable errors The power supply of HE pumps with 0 10V PWM pumps can be connected to the corresponding relay V1 R1 R2 V2 since the relays are switched on and off with the signal If the program...

Page 27: ...the pump is switched off Mode M3 After the purging time the controller switches to the set min speed If the temperature at the reference sensor collector is greater than the setpoint to be set subseq...

Page 28: ...is specified here During the setting the pump runs at the specified speed and the flow rate can be determined Settings range 70 to 100 Default setting 100 The minimum speed of the pump at relay R1 is...

Page 29: ...t setting Valve The flow sensor for the bypass function is selected in this menu Do not install in the return flow Settings range S1 S8 VFS1 VFS2 Default setting none Special functions Examples System...

Page 30: ...et is undershot at thermostat Sensor 1 and switches off when T set hysteresis at thermostat sensor 2 is exceeded Settings range S1 S8 VFS1 2 active storage Default setting none 6 6 2 4 Thermostat sens...

Page 31: ...und heats up to T eco hysteresis when solar charge is active Settings range On Off Default setting Off 6 6 2 8 Periods Thermostat activity times Set the desired periods of time when the thermostat sho...

Page 32: ...C 6 6 4 2 Co hysteresis If the temperature at th drops below Co T set hysteresis the relay is switched off Settings range 0 100 Default setting 40 6 6 4 3 Cooling sensor Reference sensor of the cooli...

Page 33: ...urn flow sensor and storage sensor the relay is switched on Settings range 5 20 K Default setting 8 K Switch off temperature difference When this difference is exceeded between return flow sensor and...

Page 34: ...in the relay is switched off Settings range 20 to 2 C Default 5 6 6 6 3 Hys max To protect the cooling unit itself from damage the relay is switched off as soon as the temperature at the reference sen...

Page 35: ...provide complete protection against Legionella because the controller is dependent on sufficient energy being fed in and it is not possible to monitor the temperatures in the entire range of the stor...

Page 36: ...ault setting 4 K Special functions 6 6 8 2 Setpoint Setpointtemperature of the target storage When this temperature is detected in the target storage heat transfer is switched off Settings range 0 90...

Page 37: ...the sensor for the heat source Settings range S1 S8 VFS1 2 Active storage Default setting none 6 6 9 3 Diff Tmin Minimum temperature at source sensor to enable the difference relay When the temperatu...

Page 38: ...6 10 3 SF Tmax Maximum temperature in the storage If this is exceeded the relay is switched off Settings range Off to 100 C Default setting 70 C This determines the sensor that is used as boiler sens...

Page 39: ...0 6 bar 0 10 bar Default setting Off 6 6 12 3 Pmin Minimum pressure If this value is undershot an error message is displayed and the relay is switched on Settings range Off 0 0 to 1 6 bar Default set...

Page 40: ...10 to 30 C Special functions Relay functions 6 6 16 3 Room sensor This menu determines the sensor for the room temperature Settings range S2 to S7 RC 6 6 16 4 Periods Set the desired periods of time...

Page 41: ...e S1 S8 VFS1 2 active collector active storage Default setting S1 6 9 1 2 Return sensor This determines the sensor that is used to measure the return temperature Settings range S1 S8 VFS1 2 Aktiver Co...

Page 42: ...6 10 1 Pressure monitor 6 10 1 1 RPS1 RPS2 6 10 1 2 Pmin 6 10 1 3 Pmax A message is shown when the pressure drops below set minimum or exceeds the set maximum pressure No relay is switched for that se...

Page 43: ...ings range 100 100 Default setting 0 Caution All of the settings that have been made can be reset thus returning the controller to its delivery state 6 13 Factory settings The entire parametrisation a...

Page 44: ...ata logger are set Activate oder deactivate the ethernetfunction 6 19 2 1 Ethernet 6 19 2 2 MAC Adress 6 19 2 3 Auto Configuration DHCP 6 19 2 4 IP Adress 6 19 2 5 Subnetz 6 19 2 6 Gateway 6 19 2 7 DN...

Page 45: ...Service values languages Menu 7 Menu lock can be used to secure the controller against unintentional changing of the set values The menu is closed by pressing esc or selecting Exit menu lock 7 Menu lo...

Page 46: ...emperature resistance table for Pt1000 sensors on page 7 Collector alarm Means that the collector has fallen fell below the temperature set under menu 5 6 Collector alarm on page 25 Restart Means that...

Page 47: ...e error e g pump and exchange it Then first recommission the controller and check the function of the switch outputs in manual mode as described under 3 2 Manual on page 21 Danger Danger Repairs and m...

Page 48: ...check plausibility of the current measurement values see 1 Measurement values on page 20 Check the switch outputs consumers in manual mode see 3 2 Manual on page 21 Possibly optimise the parameter set...

Page 49: ...rging or manual operation Settings range Solar 50 to 100 Default setting 100 Heating 0 to 50 Default setting 0 J 17 3 0 10V off This voltage is put out when the pump is turned off Pumps that can detec...

Page 50: ...Signal 0 20 25 50 100 Stop Start 5 PWM off 5 20 PWM on 25 PWM max 90 90 J 2 3b Technical data PWM and 0 10V PWM 20 to 100 1kHz Designed for a load of 10K Ohm Technical data PWM Technical data 0 10V 0...

Page 51: ...tions the service values are a proven and successful method for remote diagnosis Write down the service values see 8 Service values on page 45 at the time that the suspected malfunction occurs Send th...

Page 52: ...GRANT ENGINEERING UK LTD Hopton House Hopton Industrial Estate Devizes Wiltshire SN10 2EU Telephone 44 0 1380 736920 Fax 44 0 1380 736991 Email info grantuk com Website www grantuk com...

Reviews: