Appendix A - Parameters list
Page 66
Appendix A
Parameters list
Backlight display paramters
level
Parameter
function description
Display and input value
remarks
Group
code
Default
Min.
max.
Unit
U
02 03
Back light display at door open
0=OFF
1=ON
1
0
1
-
U
02 04
Time to turn off the back light display
60
10
300
10 sec
U
02 05
Time to back to normal display screen
120
10
300
10 sec
Water temperature set points
level
Parameter
function description
Display and input value
remarks
Group
code
Default
Min.
max.
Unit
I
21 00
Enable outgoing water set point
0=fixed set point
1=climatic curve
1
0
1
-
I
21 01
Fixed outgoing water set point
45.0
23.0
60.0
0.5°C
I
21 02
Maximum outgoing water temperature in Heating mode (Tm1)
45.0
23.0
60.0
0.5°C
I
21 03
Minimum outgoing water temperature in Heating mode (Tm2)
30.0
23.0
60.0
0.5°C
I
21 04
Minimum outdoor air temperature corresponding to maximum
outgoing water temperature (Te1)
-4
-20.0
50.0
0.5°C
I
21 05
Maximum outdoor air temperature corresponding to maximum
outgoing water temperature (Te2)
20.0
0.0
40.0
0.5°C
I
21 41
Hysteresis of water set point in heating
8.0
0.5
10.0
0.5°C
I
21 51
Low tariff deferential water set point for Heating
5.0
0.0
60.0
0.5°C
DHW (Domestic Hot Water)
level
Parameter
function description
Display and input value
remarks
Group
code
Default
Min.
max.
Unit
I
31 01
DHW production priority setting
0=DHW is unavailable
1= DHW is available, and priority DHW over space heating
2= DHW is available, and priority space Heating over DHW
1
0
2
-
I
31 21
Maximum time for DHW request
60
0
900
1 min
I
31 22
Minimum time for space heating
15
0
900
1 min
Heat pump unit
level
Parameter
function description
Display and input value
remarks
Group
code
Default
Min.
max.
Unit
I
41 00
The heat pump turns ON/OFF based on
1=water set point
1
0
1
-
I
41 11
Maximum frequency of Night mode
80
50
100
5%
S
41 30
Maximum outgoing water set point in CH and DHW
55.0
23.0
60.0
0.5°c
Water pump
level
Parameter
function description
Display and input value
remarks
Group
code
Default
Min.
max.
Unit
I
42 00
Type of configuration of main water pump
0=always ON
1=ON/OFF based on buffer tank temperature
2=ON/OFF based on detect cycles
0
0
2
-
To be set to
the following
combinations
parameter 5111=0
→Parameter
4200=0 or 2
parameter 5111=1
→Parameter
4200=0 or1 or 2
I
42 01
Time ON main water pump for detect cycle
3
1
15
1min
I
42 02
Time OFF main water pump
5
5
30
1min
I
42 03
Delay time OFF main water pump from OFF compressor
3
1
15
1min
I
42 11
OFF time for unblock pump function start
48
0
240
1hr
I
42 12
Time ON main water pump for unblock pump function
5
0
10
1sec