section 10: servicing
Page 51
10.7 monitor Display function
The heat pump operating conditions, as listed in Table 10-3, can be
displayed and checked on either the remote controller or Terminal
PCB.
Door open
figure 10-1:
Remote controller buttons
Display on remote controller
1. Press Return
n
button for three seconds to enter monitor
mode and display the user level value of parameter group 01.
A 2 digit code number of parameter group 01 (default value
is 00) will be displayed on the left of remote controller screen.
The corresponding parameter value will displayed on the right
of the screen (default value is ----. )
2. Press the Up or Down
q
buttons to change the code number
and then press the Set
p
button to display the parameter
value. Only code numbers from 00 to 09 can be displayed.
3. To return to normal display, press and hold the Menu
l
button
for three seconds or simply do nothing and leave it for about
ten minutes.
Display on Terminal PCB display
1.
Set the DIP SW4 on the Terminal PCB to ‘ON’ (up) to display
the monitor number and monitor data alternately.
2.
Push the Pump SW. of the Terminal PCB to switch the display
number alternately.
3. To return to normal display, set the DIP SW4 to ‘OFF’ (down).
Terminal PCB
Pump SW.
ON
OFF
number
change number
Pump SW.
moniter data
alternately
DIP SW4 = ON
figure 10-2:
Display on Terminal PCB display
table 10-3:
Monitor display
terminal
PcB
remote controller
function description
Display and input value
number
level
Parameter
Default
minimum
maximum
Unit
Group
code
d0
U
01 00
Circulating water return temperature
-
-20
100
1°C
d1
U
01 01
Compressor operating frequency
-
0
200
1Hz
d2
U
01 02
Discharge temperature
-
-20
150
1°C
d3
U
01 03
Power consumption value
-
0
9900
100W
d4
U
01 04
Fan control number of rotation
-
0
1000
10rpm
d5
U
01 05
Defrost temperature
-
-20
100
1°C
d6
U
01 06
Outdoor air temperature
-
-20
100
1°C
d7
U
01 07
Water pump control number of rotation
-
0
9900
100rpm
d8
U
01 08
Suction temperature
-
-20
100
1°C
d9
U
01 09
Circulating water flow temperature
-
-20
100
1°C