SUMMIT-MULTI – INSTALLATION/OPERATION MANUAL
5IM-OF-K6C0-01
Jun/11
8
2.7 ASSEMBLE & INSTALL BURNER
ASSEMBLE
Check burner model is correct for furnace rating required. Assemble as
per burner manufacturer’s instructions.
SET END CONE
Beckett AFG - see manufacturer’s instructions. Riello - Set turbulator as
per furnace operating decal.
SELECT NOZZLE
Select oil input, nozzle required and burner configuration as shown on
furnace operating decal.
INSTALL NOZZLE
Install nozzle, check for clean seating and tighten nozzle adaptor.
ELECTRODES
See burner manufacturer’s instructions for correct setting.
INSERTION
See Figure – 1 and section
7.0 GENERAL SPECIFICATIONS
.
MOUNT BURNER
Tighten top nut first so burner tips down slightly. The burner is always
installed in an upright position by four (4) nuts.
PUMP BY- PASS
For one pipe system; use a factory setting (no plug).
PLUG
WIRING
Refer to Figure – 4, 5 or 6 for correct burner connections.
THERMOSTAT
Connect
thermostat
terminals.
2.8 CHANGING
NOZZLE
NOZZLE CHANGE
If a new nozzle of a different size is installed, change the heating blower
speed according to the operating decal or section
3.0 BURNER
SPECIFICATIONS
. Applicable to
Classic Air
units only.
2.9 SET BURNER FOR EFFICIENT OPERATION
SET END CONE
Beckett MB air tube with L1 head – see burner manual. Riello set
turbulator using furnace operating decal.
PUMP PRESSURE
Refer to section
3.0 BURNER SPECIFICATIONS
or operating decal.
BURNER AIR
Refer to section
3.0 BURNER SPECIFICATIONS
or operating decal.
SAMPLING HOLE
On smoke/vent pipe, between appliance breech and draft control, punch
or drill a 1/4” round opening. Not applicable to Direct Vent.
DRAFT PRESSURE
Using an accurate draft meter; adjust the draft control to obtain -0.03” wc
draft pressure at the breech-sampling hole. Use two barometrics if
necessary. Not applicable to Direct Vent.
BURNER SETTING
After 15 minutes of normal operation, check SMOKE for zero to trace
reading and measure CO
2
. Re adjust the burner controls as required.