27
Parameter list
Alarmindstillinger
Parameter
Description
Setting range
Default
A
Alarm settings
A1
Temperature limit for condenser
sensor
(Compressor stop, Cond.alarm)
0 … 99 °C
65
A2
Reset temperature
0 ... 99 °C
40
A3
Interval for alarm repetition
5 … 30 min
5
"Præsentation", Visning i display
Parameter
Description
Setting range
Default
P
"Presentation": Display
P1
Display of setpoint after
defrosting
0 … 99 min.
30
P2
Tolerance for setpoint
00 = +0/-0 / 01 = +1/-1,
02 = +2/-2 / 03 = +3/-3,
04 = +4/-4 / 05 = +5/-5
3
P3
Display refreshing
0 … 99 sek.
10
P4
Temperature scale
Celsius = C / Fahrenheit = F
C