765041982
Rev. 000
20
Temperature-controlled cooling (Soft Chill)
This program gently cools down to the selected, desired value
(controlled using room sensor).
Both compressors perform the cooling in parallel. The second compressor starts 15
seconds after the first one.
The program is started by pressing the button
.
Temperature changes with Soft Chill:
The program is governed solely by the room
sensor. The air temperature and goods being chilled are thus taken into account. The
elapsed time has no effect on the course of the program. The cooling system works with
start/stop cycles with a gradient up to the preset storage temperature. The process stops
as soon as the temperature value reaches 0 °C, and the controls switch to the storage
program.
After pressing the
button, it will be lit continuously. The
P
,
+ and
-
buttons will be blinking. The curve symbol for Soft
Chill will light up.
The secondary display shows the program
name "SCL", and the tertiary display the selected, desired
temperature value. The + and
-
buttons are used to
change the desired value, and
P
for starting the program.
The primary display will now show the current temperature in the
room, the secondary display the program name "PCL" and the
tertiary display the selected, desired temperature value. The
curve symbol is now continuously displayed. In addition, the
connected elements will now be continuously lit: both
compressors, both fan.
When the desired value is attained, an
acoustic signal will be emitted.
After the signal, defrosting is commenced
(if such is required based upon the
evaporator sensor's temperature). Then it
subsequently switches to the storage
program. Hence the desired value for the
storage program must always be set and
checked before starting "SCL"!
Summary of Contents for BAKER SF 550
Page 1: ...765041982 Rev 000 1 Operating and servicemanual BAKER SF 550 PROCESS KP 60 KP 82...
Page 7: ...765041982 Rev 000 7 Min 40 mm...
Page 12: ...765041982 Rev 000 12 Fig 5...
Page 33: ...765041982 Rev 000 33 Changing the door hinge side 1 2 3 4...
Page 34: ...765041982 Rev 000 34 5 6 7...
Page 35: ...765041982 Rev 000 35 8 9 10 11 12 13 14...
Page 36: ...765041982 Rev 000 36 15 16...
Page 37: ...765041982 Rev 000 37 17 18 19 20...
Page 38: ...765041982 Rev 000 38 21 22 23...
Page 39: ...765041982 Rev 000 39 Wiring diagram KP 82...
Page 40: ...765041982 Rev 000 40 Wiring diagram SF 550 KP 60...
Page 41: ...765041982 Rev 000 41 Piping diagram KP 82...
Page 42: ...765041982 Rev 000 42 Piping diagram SF 550 KP 60...