25
Gram
Commercial
Technical information
765041466
Description :
Operation- and servicemanual
Gram Process KPS
Compiled. Latest
revision. Deleted.
Date Name Date Name
Rev.no
Date Name
30.09.11 JP
000
Parameter
Description
Default
Min.
Max.
Adjustment
R01
Compressor start/stop hysteresis
2
C 0
C 20
C
R02
Min. interval between 2 compressor starts
2 min
0 min
30 min
R03
Compressor start delay from card activation
0 sec
0 sec
300 sec
R04
Compressor duty-cycle time w/ faulty room sensor in
storing
10 min
0 min
90 min
R05
Compr. ON time w/faulty room sensor – pos. storing
3 min
0 min
90 min
R06
Compr. ON time w/faulty room sensor – neg. storing
8 min
0 min
90 min
R07
Probe sensor min. temperature for process start
70
C 0
C 90
C
R08 Compressor
inhibition
temperature
90
C 0
C 100
C
R09
Compressor protection function activation time
24 hrs
0 hrs
240 hrs
R10
Pulse duration
2 sec
1 sec
10 sec
R11
Pause between pulses
4 sec
1 sec
10 sec
R12
Number of pulses
3
1
20
R13
Temperature at the end of the cooling cycle
-25
C -50
C 10
C
Sterilization
U01
Sterilization duration
20 min
1 min
99 min
Fans
F01
Evaporator fans activation hysteresis
2
C 0
C 20
C
F02
Condenser fans activation hysteresis
2
C 0
C 20
C
F03
Evaporator fans activation setpoint
5
C -50
C 50
C
F04
Condenser fans activation setpoint
15
C -50
C 50
C
F05
Evaporator fans during defrost
(0=fans off; 1=fans on)
0 0 1
F06
Condenser fans during defrost
(0=fans off; 1=fans on)
0 0 1
F07
Fans stop time after defrost
1 min
0 min
30 min
F08
Condenser fans stop delay
30 sec
0 sec
300 sec
F09
Evaporator fans control during quick cooling:
0=fans always on
1=fans controlled by evaporator temperature
0 0 1
F10
Evaporator fans control during storing:
0=fans in parallel with the compressor
1=fans controlled by evaporator temperature
0 0 1
F11
Evaporator fans inhibition temperature
70
C 0
C 90
C
PR1
Sampling time
10 min
1 min
60 min
Ventilation speed (P.W.M.)
CF1
Evaporator fan min. speed
30
0
100
CF2
Evaporator fan min. speed selectable in a quick cooling
cycle
50 0
100
I.F.R.
B01
Room temperature in phase 1
-45
C -50
C 50
C
B02
Surface temperature control start temperature
5
C -50
C 99
C
B03
First coefficient of the control relation
0
-50
50
B04
Second coefficient of the control relation
0
-50
50
B05
Third coefficient of the control relation
-8
-50
50
B06
Surface temperature initial value determining the end of
phase 1
-1
C -50
C 99
C
B07
Phase 2 formula coefficient
99
0
99