9. Fault messages and rectification
44 / 54
Display
Liquid crystal display
Possible cause
Rectification
KLbasic /
KL24base
KLplus /
KL 24plus
-
modem error
Batteries in module are
not yet fully charged
Modem has no mains
voltage
No SIM card inserted in
modem
SIM card not logged into
mains
Wait 5 minutes until batteries are charged
Connect modem to the mains
Insert SIM card in modem
Wait until card has logged in or move
antenna into position where reception is
available.
Unusual water levels - remedying a fault
9.2
Observation
Possible cause
Rectification
The water level in the
pre-treatment section
is unusually high, but
is normal in the aera-
tion section.
The lifter at valve 1 is not activated.
The pump time for lifter 1 has too
short a setting.
The feed lifter is blocked.
The air supply to the feed lifter is
leaking.
In manual mode, activate valve 1
and check function of lifter.
Have time for valve 1 extended by
service company
Allow pre-treatment section to be
pumped empty and clean lifter
Allow pre-treatment section to be
pumped empty and seal hose
connections
The water level in the
pre-treatment section
and aeration basin is
unusually high.
System running in holiday mode.
System running continuously in cycle
pause.
Control unit settings are incorrect.
The discharge lifter is blocked.
The air hose to the discharge lifter is
leaking.
Flooding in the discharging system is
not allowing water to drain from the
system.
Control unit is defective.
Exit holiday mode (see Item 6.3.4)
Have control unit settings checked
by a maintenance specialist
Allow SBR reactor to be pumped
empty and clean lifter
Allow SBR reactor to be pumped
empty and seal hose connections
Wait for flooding to drain away
Contact maintenance company
The system smells,
the cleaned
wastewater is cloudy
and/or discoloured
Too little air is being drawn into the
system
Aeration on one side only due to de-
fective membrane unit
Have aeration time extended by
service company
Check aeration pattern, contact
maintenance company
Aeration pattern is
one-sided and/or
large air bubbles are
forming in some are-
as
Membrane unit defective
Seal on aerator bar leaking
Contact maintenance company
Contact maintenance company
Solenoid valves
switching unusually
loudly
Valve seat of solenoid valve is dirty
Screw open and clean solenoid
valve