9. Fault messages and rectification
43 / 54
Display
Liquid crystal display
Possible cause
Rectification
KLbasic /
KL24base
KLplus /
KL 24plus
Valve 3
failure
valve 3 error
(see maintenance instructions in Annex).
Valve 4
failure
valve 4 error
-
UV unit error
UV module not working
Check UV module and remaining lamp life
-
**error**
min. water
level
Compressed air line
leaking between control
unit and feed lifter, e.g.
due to loose hose
Check hose line for leaks
-
Alert flooding
Water level in 1 cham-
ber is too high
Compressed air line
blocked, e.g. due to kink
in hose
See Item 9.2
Check hose line for kinks
-
temperature
max.
Temperature sensor not
plugged in
Cabinet fan not working
Filters in cabinet and in
compressor are dirty
Direct sunlight on cabi-
net
The temperatures en-
tered in the Service
menu for switching on
the cooling fan and the
maximum temperature
are too high
Air compressor defec-
tive
Temperature sensor
defective
Plug temperature sensor onto rear of con-
trol unit
Check the functionality of the cabinet fan
Check air filter in cabinet
Provide site with shade
Ensure good aeration
Check air filter in air compressor
Check air compressor in manual mode
Have set temperatures checked by
maintenance company
Replace temperature sensor
-
**error**
temp.-sensor
No temperature sensor
Temperature sensor not
fully plugged into bush
Temperature sensor
defective
Replace sensor
Ensure a reliable connection between
control unit and temperature sensor, then
de-energise control unit for 10 sec. and
switch on again, check whether a temp.
sensor fault message is displayed.
Power failure
**error**
power failure
Power cut
System switched off via
maintenance switch
Switch cabinet is not
energised
FI fuse has blown
Wait for power to be restored
Switch system back on via maintenance
switch
Check supply line to switch cabinet
Establish cause for earth leakage circuit
breaker blowing and remedy (possible
cause: solenoid valve defective).