Installation
Installation
Installation
Installation
Installing and servicing this equipment requires
access to parts which may cause electric shock
or other serious injury if work is not performed
properly.
• Do not install or service this equipment unless
you are trained and qualified.
• Be sure your installation complies with local,
state, and national codes for the installation
of electrical apparatus in a Class I, Div. I,
Hazardous Location or a Group II, Zone I
Explosive Atmosphere Location.
• Comply with all applicable local, state, and
national fire, electrical, and other safety
regulations.
Fig. 10 shows a typical electrostatic air spray system.
It is not an actual system design. For assistance
in designing a system to suit your particular needs,
contact your Graco distributor.
Warning
Warning
Warning Sign
Sign
Sign
Mount warning signs in the spray area where they
can easily be seen and read by all operators. An
English Warning Sign is provided with the gun.
Ventilate
Ventilate
Ventilate the
the
the Spray
Spray
Spray Booth
Booth
Booth
Provide fresh air ventilation to reduce the risk of fire
or explosion caused by the buildup of flammable or
toxic vapors when spraying, flushing, or cleaning
the gun. Do not operate the gun unless ventilation
fans are operating.
Electrically interlock the gun air supply with the
ventilators to prevent gun operation without
ventilating fans operating. Check and follow all local,
state, and national codes regarding air exhaust
velocity requirements.
High velocity air exhaust will decrease the operating
efficiency of the electrostatic system. Air exhaust
velocity of 100 ft/min (31 linear meters/minute) should
be sufficient.
3A2494D
15