Code
Description
Type
Cause
Solution
V6M_
Wiring Error
Line MZLP _
Alarm
Incoming
power is wired
incorrectly
Correct the Wiring
Verify transformer has the correct tap selected
Verify CB-1 or FU-4, FU-5, and FU-6 are not
tripped/blown
Verify RCD-1 is not tripped
Measure incoming power with system unplugged. If
line voltage is less than 100 VAC, contact qualified
electrician to correct the low voltage.
V8M_
No Line Voltage
MZLP _
Alarm
Incoming line
voltage is less
than 100 VAC.
Verify the MZLP is plugged in at J2 and the AWB is
plugged in at J5 and J6.
Check incoming voltage is correct for configuration.
V4M_
AWB High Line
Voltage
Alarm
Incoming
voltage is too
high
Verify the transformer has the correct tap (400, 480,
600) selected
Verify harness is plugged into J13 of the daughter
board. Verify it is secured to the solenoid.
WJ1_
Pump _
Solenoid is
disconnected
Alarm
Pump is not
turning on
when it should Replace Solenoid
WJ2_
Pump _
Solenoid High
Current
Alarm
Solenoid is
drawing too
much current
Inspect for short in harness. Inspect for a shorted
solenoid cable/short to the ground. Replace solenoid.
WSUX
Configuration
Error USB
Advisory
USB
configuration
is not loaded
Install software
334130A
43
Summary of Contents for 334130A
Page 10: ...Component Identification Electrical Control Enclosure Figure 3 Electrical Enclosure 10 334130A...
Page 57: ...Repair Figure 35 Inside of Electrical Control Enclosure 334130A 57...
Page 65: ...Parts Parts Therm O Flow 200 Supply Unit 334130A 65...
Page 68: ...Parts Electrical Module 68 334130A...
Page 69: ...Parts 334130A 69...