Code
Description
Type
Cause
Solution
Reduce flow rate
Increase temperature of accessory upstream.
Faulty accessory heater measure resistance between
heater leads.
Change Low Temp Alarm
T1
★
_
Low Temp. Unit
_ Zone _
Alarm
Zone
temperature
too low
Replace accessory
Reduce flow rate
Change Low Temp Alarm
T2
★
_
Low Temp. Unit
_ Zone _
Deviation
Zone
temperature
too low
Add zone (temperature) upstream
Change High Temp Alarm
T3
★
_
High Temp.
Unit _ Zone _
Deviation
Temperature
reading has
risen too high
Verify setpoint upstream is not hotter than this zone’s
setpoint
Ensure inlet and outlets are not obstructed.
T4C_
AWB
Temperature
Runaway
Transformer
Alarm
Cooling fan
not working
or inlet is
blocked/dirty
Verify fan is plugged in.
Ensure inlet and outlets are not obstructed.
T4M_
AWB High
Transformer
Temp
Alarm
Transformer
Temperature
is too High
Verify fan is plugged in.
Change High Temp Alarm
T4
★
_
High Temp.
Unit _ Zone _
Alarm
Temperature
reading has
risen too high
Verify setpoint upstream is not hotter than this zone’s
setpoint
Check RTDwiring and harness/connector integrity.
T6
★
_
Sensor Err. Unit
_ Zone _
Alarm
Bad RTD
Reading
Replace RTD
T6C_
AWB Invalid
Thermistor
Reading
Alarm
Transformer
thermistor
temperature
is incorrect
Verify thermister is securely connected to J7 of the
AWB. Replace transformer if necessary.
Check fuses on MZLP connected to that Zone
Check wiring to device
T8V _
No Temp. Rise
Unit _ Zone _
Alarm
Temperature
reading does
not change.
Check heater resistance on device
V1I_
Low CAN
Voltage, MZLP
_
Alarm
Bad or
overloaded
power supply
Verify power supply voltage is 24 VDC. If voltage is
low, disconnect the power lines and re-check voltage
reading. If voltage is still low, replace power supply. If
voltage is correct after disconnecting the power lines.
Connect items one at a time until the voltage drops
to isolate the bad module.
V1M_
Low Voltage
Line AWB, Unit
_
Deviation
The voltage
to the AWB
is below
threshold
Verify transformer voltage top matches incoming
voltage. Verify incoming voltage is correct.
V4I_
High CAN
Voltage, MZLP
_
Alarm
Bad or
overloaded
power supply
Verify power supply voltage is 24 VDC. If voltage is
high, replace power supply unit.
42
334130A
Summary of Contents for 334130A
Page 10: ...Component Identification Electrical Control Enclosure Figure 3 Electrical Enclosure 10 334130A...
Page 57: ...Repair Figure 35 Inside of Electrical Control Enclosure 334130A 57...
Page 65: ...Parts Parts Therm O Flow 200 Supply Unit 334130A 65...
Page 68: ...Parts Electrical Module 68 334130A...
Page 69: ...Parts 334130A 69...