Setup
20
3A5278B
Automation Output Signals
Pump On Off Control
Through the gateway, the pump can only be turned on if the operation mode is set to Spray, Run Pump A, Run Pump
B, Run Pump AB, or Park.
All non-zero values will also be treated as a request to turn pump on.
Operation Mode Control
The pump must be off for the operation mode to be changed.
All other values will be rejected.
Volume Ratio Target Ctrl
The target volume ratio can only be set when the system is in volume mode. See
Ratio in thousandths. That is:
1200 = 1.2:1 ratio
1800 = 1.8:1 ratio
Acceptable range is 1.0:1 to 10.0:1 (1,000 to 10,000). All other values will be rejected.
Reset Alarms
Values
Pump On Off
0
Pump is off
1
Pump is on
Values
Operation Mode
0
Spray
1
Run Pump A (recirc)
2
Run Pump B (recirc)
3
Run Pump AB (recirc)
4
Park
8
Inactive (system off)
Values
Units
0
Reset alarms
1
Must set to 0 before setting to 1 to reset
alarms again