Appendix C: Graco Gateway to ControlLogix via Ethernet IP
78
312785B
The following settings mirror the I/O settings of the
ControlLogix configuration detailed earlier.
a.
Input Connection Point. Create a Gateway
block configuration (see Table 7).
b.
Output Connection Point. Create a Gateway
block configuration (see Table 8).
4.
Data Mapping. the connection points are now con-
figured so that:
Gateway_HMI:O >> PLC1:Block1
Gateway_HMI:I << PLC1:Block2
5.
Testing. Using the RSLogix5000 program, you can
modify tags Gateway_HMI:O and verify they are
written into Var1 and Var2, and verify changes made
in the Gateway to tags Var3 and Var4 are updated in
Gateway_HMI:I. Ensure the device is in the Run
mode, otherwise the data transfer will be ignored by
the Gateway.
Table 7: Input Connection Points
Connection Point
2
Data Offset
0000
Data Type
Long as Long
Block Size
2
Direction
Graco Gateway to Device
Table 8: Output Connection Points
Connection Point
3
Data Offset
0000
Data Type
Long as Long
Block Size
2
Direction
Device to Graco Gateway