Modbus and I/O Data
26
312785B
Alarm Processing
See F
IG
. 29, Table 1, Table 2, and Table 3.
F
IG
. 29. Alarm Processing Flow Chart
Alarm Processing
Is Mix Ready
bit = 1?
Check if Potlife
Alarm: is Alarm_
Potlife bit = 1?
YES
NO
NO
YES
An Alarm Condition
has been found
previously.
Alarm_General = 1.
Two options:
• Purge or Color Change to remove
mixed material in the line.
• Place in Mix mode and spray the
Potlife Volume set in the ProMix
2KS.
NOTE: The Reset key only silences
the alarm. To clear the alarm you must
use one of these two options.
Go to next process,
as desired.
Determine the exact alarm
and solve what caused the
alarm, as required.
Reset the alarm.
Reset_Alarm = 1.